DSPM Power Lynx 3 three-phase online UPS technical specifications

DSPM

A 10-page guide specification, number 084-0036-01, in which DSPM sets out the tender requirements for its Power Lynx 3 three-phase, online, double-conversion UPS in three parts: operation at 0-40 °C, 10 minutes of battery autonomy at full load and 25 °C, inverter overload of 125% for 1 minute and UL 924 listing.

On this page

Overview

The document follows the three-part specification layout used in North American tendering: General, Products and Execution. It is written so that a designer can carry it straight into a project specification; the output power and the input and output voltage fields are left blank and the reader is referred to the product datasheet for power ranges. The system consists of a solid-state inverter, a temperature-compensated rectifier and battery charger, a static switch rated 100% for continuous duty, an internal maintenance bypass switch, a battery plant and a control panel. Lighting loads and other critical loads are the target.

The general part lists the standards: IEEE 587-1980/ANSI C62.41 for surge withstand, FCC Part 15 Subpart J Class A, UL 924, NEMA PE 1, NEMA 250 and NFPA 70. The manufacturer must show at least twenty years of documented experience, run a factory test that includes a battery discharge test before shipment and supply the test report on request. Environmental conditions are 0-40 °C operating, -20 to +60 °C non-operating, 5-95% non-condensing humidity and 1000 m altitude; operation up to 2000 m is allowed where ambient temperature stays below 28 °C.

The products part fixes electrical performance in numbers. Input voltage tolerance is -15% / +10%, frequency is 60 Hz and power walk-in ramps from 0 to 100% over 10 seconds. Output voltage regulation is ±3%, voltage distortion is at most 5% on a 100% linear load and below 8% on a 100% non-linear load. Voltage deviation on a load step is ±5% for a 50% step and ±8% for a 100% step, and voltage returns to within 3% of nominal in 50 ms.

Operating modes are defined as normal, emergency (battery), recharge, static bypass and manual bypass. The battery is valve-regulated sealed lead calcium (VRLA); float voltage is 2.3 VDC per cell and temperature compensation is -3 mV per cell per °C referenced to 25 °C. Deep-discharge protection, a battery circuit check and a selectable partial discharge test are required. The execution part calls for on-site start-up by the manufacturer's field service engineer and for user training. The specification is written around one product; substitutions need written approval at least 10 days before bid closing.

Key points

  1. Scope: three-phase, online, double-conversion UPS; the static switch is rated 100% for continuous duty.
  2. Environment: operating 0-40 °C, non-operating -20 to +60 °C, batteries at 25 °C; humidity 5-95% non-condensing; 1000 m altitude, 2000 m below 28 °C.
  3. Audible noise is 45 dBA at 3 feet.
  4. Input: -15% / +10% voltage tolerance, 60 Hz, 0-100% power walk-in over 10 seconds, magnetising inrush below nominal current for less than one cycle.
  5. Output: ±3% regulation, THD at most 5% on linear load and below 8% on non-linear load, frequency 60 Hz ±0.1 Hz when free running.
  6. Dynamic response: ±5% on a 50% load step, ±8% on a 100% step; recovery to the 3% band within 50 ms.
  7. Overload: inverter 125% for 1 minute and 145% for 10 seconds; bypass above 150% for 30 seconds and above 200% for one cycle.
  8. Battery: VRLA lead calcium, 10 minutes at full load at 25 °C, float 2.3 VDC/cell, compensation -3 mV/cell/°C.
  9. Equipment containing batteries is not stored for more than three months without being powered for 8 hours to recharge them.
  10. Warranty: 12 months from installation or 18 months from shipment, whichever comes first; batteries 1 year full replacement plus 9 years pro-rated.

Using it in design

  • When writing your own UPS specification, use the part structure (General, Products, Execution) and the numeric acceptance criteria (regulation, THD, step response, overload) as a checklist.
  • In the selectivity and fault-clearing study, compare the bypass withstand (above 150% for 30 seconds, above 200% for one cycle) with the trip curves of downstream breakers.
  • For generator sizing, include the 10-second power walk-in and the low magnetising inrush in the step-load calculation.
  • Design cooling that holds the battery room at 25 °C, and confirm the -3 mV/cell/°C compensation coefficient in the charger settings.
  • For sites above 1000 m, write the 28 °C ambient limit into the UPS room cooling design point.
  • Add to the site programme the 8-hour battery recharge needed when storage exceeds three months and the on-site start-up step with the manufacturer's engineer.

Who should read it

Electrical engineers writing UPS tender specifications, consultants evaluating bids and owner's representatives setting commissioning acceptance criteria.

Document contents

  1. Part 1 General
  2. 1.1 Summary
  3. 1.2 Standards
  4. 1.3 Submittals
  5. 1.4 Qualifications & Quality Assurance
  6. 1.5 Delivery, Storage, and Handling
  7. 1.6 Environmental Requirements
  8. 1.7 Warranty
  9. 1.8 Service and Spare Parts
  10. 1.9 Maintenance, Accessibility and Self Diagnostics
  11. Part 2 Products
  12. 2.1 Acceptable Manufacturers/Product
  13. 2.2 Product Specification
  14. 2.3 Modes of Operation
  15. 2.4 Component Description
  16. 2.5 System Controls and Indicators
  17. 2.6 Mechanical Design and Ventilation
  18. 2.7 Battery
  19. 2.8 Optional External Maintenance Bypass
  20. Part 3 Execution
  21. 3.1 Site Testing Start-Up
  22. 3.2 Maintenance Training

Publication details

Authors
DSPM
Publisher
DSPM
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

DSPM DSPM Power Lynx 3 three-phase online UPS technical specifications. DSPM. https://dspowerm.co/downloads/uninterruptible_power_systems_indoor_three_tech_specs.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.