Technical guideFree to readYear not stated

Bastion SKAT-UPS 1000-ON operating manual

Bastion

A 36-page Russian-language operating manual from Russian manufacturer Bastion for the single-phase on-line double-conversion SKAT-UPS 1000-ON: rated 1000 VA apparent and 800 W active power, two external 12 V batteries (24 V string, 17 to 120 Ah), charging current up to 10 A, efficiency of at least 89% in normal mode at rated load, and a weight of only 4.9 kg.

On this page

Overview

The manual covers the unit's technical data, construction, operating principle, installation and safe operating rules. The SKAT-UPS 1000-ON is an on-line UPS for indoor use feeding loads rated 220 V, 50 Hz; the output voltage can be set by the user to 200, 208, 220, 230 or 240 V. The intended use is computers and computer networks and other critical loads in communications, finance, transport and research organisations. Its distinguishing feature is that the batteries are not internal: two 12 V sealed lead-acid batteries are connected externally and are not part of the delivery.

The technical table has 40 rows. The input voltage window depends on load: at 50% to 100% load the lower threshold for moving to battery is 155 V and the upper 270 V; below 50% load they are 115 V and 300 V. Input frequency is accepted from 40 to 70 Hz and generator supply is supported. The table gives rated output power as 1000 VA and 800 W; in the same table the output power factor row reads not less than 1.0 and the rated load current 4.5 A. Static output voltage accuracy is ±1%, and voltage distortion is at most 3% on linear load and 5% on non-linear load.

Transfer from normal mode to battery mode takes 0 ms and to bypass mode at most 4 ms. On overload the unit moves to bypass after 1 minute at 105% to 125% and after 30 seconds at 125% to 130%. Efficiency at rated load is at least 89% in normal mode, 86% in battery mode and 95% in bypass and ECO mode. According to the manual, two 40 Ah batteries give about 1.5 hours of runtime at maximum load. Above 40 °C the load is reduced by 12% for every 5 °C, and operation above 50 °C is prohibited. The appendices explain ECO mode settings, battery discharge thresholds, LED and audible indications and the communication ports.

Key points

  1. Rated output 1000 VA and 800 W; rated load current 4.5 A; maximum input current 6.1 A.
  2. Battery: 2 x 12 V sealed lead-acid (external, not supplied), recommended capacity 17 to 120 Ah; charging voltage 27.4 V ±0.1%; charging current up to 10 A.
  3. Efficiency (at rated load, minimum): normal mode 89%, battery mode 86%, bypass and ECO mode 95%.
  4. Transfer time: 0 ms from normal mode to battery mode, at most 4 ms to bypass mode.
  5. Thresholds for moving to battery: below 155 V and above 270 V at 50% to 100% load; below 115 V and above 300 V under 50% load.
  6. Input power factor at least 0.99 at full load; input frequency range 40 to 70 Hz; generator operation supported.
  7. Dimensions 145 x 214 x 286 mm (W x H x D); net weight at most 4.9 kg; degree of protection IP20.
  8. Operating temperature 0 to +40 °C; 12% load reduction for every 5 °C above 40 °C; altitude up to 1500 m without derating.
  9. Low battery warning at 21.9 to 22.1 V; load disconnection to prevent deep discharge at 20.6 to 21.0 V.
  10. Communication: RS-232, USB, intelligent slot (relay interface or SNMP adapter) and an EPO connector.

Using it in design

  • Size the load against the 800 W active power limit; do not read the 1.0 power factor row in the table as 1000 W without confirmation from the manufacturer.
  • Set backup time through external battery capacity: about 1.5 hours at maximum load with 2 x 40 Ah; for longer, choose batteries up to 120 Ah and work out recharge time at the 10 A charging current.
  • Provide separate space, ventilation and 24 V DC cable protection for the external batteries, which are not housed in the unit.
  • At remote unattended points, bring low battery and fault signals into the monitoring system through the relay interface or SNMP adapter.
  • Use the 89% normal-mode efficiency in heat load calculations and apply the load reduction for ambients above 40 °C.

Who should read it

Engineers selecting small long-backup UPS units for security, communications and edge equipment, and field installation teams.

Document contents

  1. Технические характеристики
  2. Входные параметры
  3. Выходные параметры
  4. Перегрузочная способность
  5. Условия эксплуатации
  6. Комплект поставки
  7. Устройство и работа изделия
  8. Коды рабочих состояний и режимов ИБП
  9. Установка и монтаж аккумуляторных батарей
  10. Подключение
  11. Подготовка к работе
  12. Обслуживание АКБ
  13. Аварийные сообщения и предупреждения
  14. Выбор режима и настройка ECO параметров
  15. Описание светодиодной индикации и звуковой сигнализации
  16. Описание коммуникационных портов

Publication details

Authors
Bastion
Publisher
Bastion
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bastion Bastion SKAT-UPS 1000-ON operating manual. Bastion. https://cnr.bast.ru/media/files/materials_1c/491/operating_instructions-FIASh_436518_407_RE_actual.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.