Bastion SKAT-UPS 3000-IN-4x9 operating manual
Bastion
An eight-page operating manual published by Bastion for the SKAT-UPS 3000-IN-4x9 line-interactive UPS: 3000 VA / 1800 W output, 2 minutes of battery runtime at full load and four internal 12 V 9 Ah batteries.
On this page
Overview
The manual (document code FIASh.436518.114 RE) covers the technical characteristics, construction, operation and usage rules of the SKAT-UPS 3000-IN-4x9 from the Russian manufacturer Bastion. The unit is an interactive (line-interactive) UPS intended for personal computers and similar loads with a 220 V nominal supply. With mains present it stabilises the voltage and fast-charges the battery; when the mains leaves its permitted range or fails completely it transfers to battery automatically, and it returns to mains operation when the supply is restored.
The specification table has 31 rows. Output power is 3000 VA and 1800 W, which corresponds to a power factor of 0.6. The input voltage window is 162 to 290 V at 50 ±1 Hz and the output is 220 V ±10%. Transfer time to battery is 8 to 10 ms and the output waveform is a stepped approximation of a sine wave. Runtime at full load is 2 minutes; the four sealed maintenance-free 12 V, 9 Ah lead-acid batteries recharge to 90% capacity in 6 to 8 hours.
Mechanical and environmental data sit in the same table: at most 145 x 213 x 436 mm (W x H x D) unpacked, at most 23.9 kg, an operating range of +5 to +40 °C, relative humidity up to 80% at 25 °C and an IP20 enclosure rating. The four battery-backed outlets are IEC 320 C13 and CEE 7/4 types. A USB port provides monitoring and power management, and an RJ-45 port provides surge protection for a telephone or modem line.
The remainder of the document covers safety rules, start-up steps and warranty terms. Operation without earthing is prohibited; the unit must not sit closer than 1 m to a heat source and its ventilation openings must stay clear. The front-panel button switches only the output, so the unit keeps charging the battery whenever it is plugged in. The warranty is 3 years for the unit and 12 months for the batteries, with a stated service life of 10 years. The manual carries no publication date.
Key points
- Topology: interactive (line-interactive); output 3000 VA / 1800 W.
- Runtime at full load is 2 minutes.
- Input voltage 162...290 V (50 ±1 Hz); output 220 V ±10%.
- Transfer time to battery is 8...10 ms; output is a stepped sine approximation.
- Battery set: 4 sealed lead-acid blocks, 12 V, 9 Ah; recharge to 90% in 6...8 hours.
- Outputs: 4 battery-backed outlets, IEC 320 C13 and CEE 7/4.
- Dimensions at most 145 x 213 x 436 mm, mass at most 23.9 kg, enclosure IP20.
- Operating conditions: +5...+40 °C, relative humidity up to 80% at 25 °C.
- Maximum absorbed surge energy 185 J; USB interface, RJ-45 line protection.
- Warranty 3 years on the unit, 12 months on the batteries; service life 10 years.
Using it in design
- Use this model only for loads that tolerate an 8...10 ms break and a stepped-sine output; for server power supplies with active PFC, evaluate a double-conversion UPS.
- Size the load against the 1800 W active-power limit, not the 3000 VA figure.
- Compare the 2-minute full-load runtime with the generator start time or the controlled shutdown time.
- Check the 23.9 kg mass, IP20 rating and +5...+40 °C range against room conditions; an earthed socket is mandatory.
- Reflect the 12-month battery warranty and the 6...8 hour recharge time in the maintenance plan.
Who should read it
Electrical designers and procurement engineers selecting small single-phase UPSs for network rooms, edge cabinets and office loads.
Document contents
- Технические характеристики
- Комплект поставки
- Устройство и работа
- Меры безопасности
- Подготовка к работе
- Гарантийные обязательства
- Свидетельство о приёмке
Publication details
- Authors
- Bastion
- Publisher
- Bastion
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Bastion Bastion SKAT-UPS 3000-IN-4x9 operating manual. Bastion. https://cnr.bast.ru/media/files/materials_1c/453/operating_instructions-FIASh_436518_114_RE_actual.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.