Elettro SAT-KK 1–3 kVA technical sheet
Elettro Services & Equipment
A one-page sheet from Italian manufacturer Elettro Services & Equipment describing the SAT-KK and SAT-KK-PLUS single-phase online double-conversion transformerless UPS series (VFI-SS-111): 1000, 2000 and 3000 VA, with 800, 1600 and 2400 W on SAT-KK and 900, 1800 and 2700 W on SAT-KK-PLUS, and efficiency above 98% in ECO mode.
On this page
Overview
The sheet is the low-power page of the standard single-phase online UPS catalogue of Elettro Services & Equipment. The series is online double conversion and transformerless, classified VFI-SS-111 under IEC 62040-3, with single-phase pure sine-wave input and output. An input power factor correction (PFC) circuit, microprocessor control with self-diagnostics, automatic bypass and an LCD display are standard. ECO mode is selectable; cold start from battery and automatic restart on mains return are supported. Autonomy can be extended with a battery box.
The technical table gives three power ratings in two versions. SAT-KK is 1000 VA / 800 W, 2000 VA / 1600 W and 3000 VA / 2400 W (power factor 0.8); SAT-KK-PLUS delivers 900, 1800 and 2700 W at the same VA ratings (power factor 0.9). SAT-KK is offered in tower and rack chassis and PLUS in tower chassis, which makes nine distinct models. Input is 230 VAC single phase with an accepted range of 170-295 VAC and a power factor above 0.98. Output is selectable at 208/220/230/240 V with ±2% accuracy.
Overload behaviour is defined in two steps: the connected load is dropped with an alarm when a load between 108% and 150% lasts more than 30 seconds, or a load between 150% and 200% lasts more than 300 ms (thresholds carry a ±5% tolerance). Output voltage distortion is below 3% on linear load. Efficiency is 92% with mains present and above 98% in ECO mode. Batteries are 12 V 7 Ah or 12 V 9 Ah blocks depending on model, between 2 and 6 in number; typical autonomy is 8-15 minutes depending on load and recharge time is 6-8 hours.
Mechanical data is given per model. The tower chassis is 144 x 361 x 215 mm for 1000 VA (PLUS 144 x 409 x 215 mm) and 191 x 428 x 337 mm for 2000 and 3000 VA (PLUS 191 x 466 x 337 mm). The rack chassis is 440 x 380 x 86.5 mm (2U) for 1000 VA and 440 x 520 x 131 mm (3U) for 2000 and 3000 VA. Tower weights run from 11 kg to 26 kg. The PLUS series has an EPO contact and a programmable output socket. An SNMP adapter and a relay alarm board are options. Compliance is to EN 62040-1-2, EN 62040-2 and EN 62040-3.
Key points
- SAT-KK: 1000 VA / 800 W, 2000 VA / 1600 W, 3000 VA / 2400 W; SAT-KK-PLUS: 1000 VA / 900 W, 2000 VA / 1800 W, 3000 VA / 2700 W.
- Class VFI-SS-111; online double conversion, transformerless, single-phase input and output.
- Input: 230 VAC, range 170-295 VAC, 40-55 Hz (50 Hz) or 55-65 Hz (60 Hz) autosensing, power factor > 0.98.
- Output: 208/220/230/240 V ±2%, 50/60 Hz ±0.2% (on battery), THD < 3% on linear load.
- Efficiency: 92% with mains present, > 98% in ECO mode.
- Overload: the load is dropped after 30 seconds between 108% and 150% and after 300 ms between 150% and 200%.
- Battery: 12 V 7 Ah or 9 Ah, 2-6 blocks; typical autonomy 8-15 minutes; recharge time 6-8 hours.
- Rack chassis: 440 x 380 x 86.5 mm (2U, 11 kg) for 1000 VA, 440 x 520 x 131 mm (3U, 21 kg) for 2000 VA, the same size (26 kg) for 3000 VA.
- Environment: 0-40 °C, relative humidity < 90% non-condensing, noise < 55 dBA at 1 m.
- Compliance: EN 62040-1-2, EN 62040-2, EN 62040-3.
Using it in design
- Compare the load against the W value and choose the PLUS version where needed: at 3000 VA, SAT-KK carries 2400 W and SAT-KK-PLUS 2700 W.
- For in-rack use, record in the rack plan that the rack version is offered on SAT-KK only and needs 3U and 520 mm of depth at 2000-3000 VA.
- Because overload is defined as dropping the load, not transferring to bypass, leave margin so loads with high inrush do not cross the 108% threshold.
- If the typical 8-15 minutes of autonomy is not enough, add a battery box and allow for a recharge time longer than 6-8 hours.
- Use 92% efficiency for the heat load; if the design relies on the 98% ECO figure, record the reduced protection in the design decision.
- Where the unit will be wired into the emergency shutdown circuit, specify the PLUS version, which has the EPO contact.
Who should read it
Electrical designers and IT infrastructure engineers selecting a 1-3 kVA single-phase UPS for network racks, control systems and small IT loads.
Document contents
- Features
- Option
- Model and Power
- Input
- Output
- Efficiency
- By Pass
- Batteries
- General Notes: dimensions and weight
- Compliance
Publication details
- Authors
- Elettro Services & Equipment
- Publisher
- Elettro Services & Equipment
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Elettro Services & Equipment Elettro SAT-KK 1–3 kVA technical sheet. Elettro Services & Equipment. https://www.elettroservices.com/elt/wp-content/uploads/2020/03/4-CATALOGUE-UPS-STANDARD-SINGLE-PHASE-ON-LINE.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.