ELIT TPH KING technical specification table
ELIT
A product page from Italian manufacturer ELIT Srl describing nine models of the transformerless double-conversion (VFI-SS-111) TPH KING three-phase UPS series: 10 kVA / 9 kW to 80 kVA / 72 kW, output power factor 0.9, 95.5% efficiency at full load and parallel operation of up to 20 units.
On this page
Overview
The page covers the TPH KING series, which ELIT positions for server rooms, networks, telecommunication systems, industrial processes and medical equipment. The series is a transformerless double-conversion UPS classified VFI-SS-111 under IEC 62040-3. It is built from a rectifier, inverter, static switch, manual bypass and battery. Three cabinet sizes are offered so that longer backup times fit in the same enclosure without additional battery cabinets. The front panel has a 2x20 character LCD, a mimic diagram and keys.
The technical table gives nine models in kVA/kW: 10/9, 15/13.5, 20/18, 25/22.5, 30/27, 40/36, 50/45, 60/54 and 80/72. Input is 3x380/220, 3x400/230 or 3x415/240 V plus neutral. Input voltage tolerance depends on load: -23%/+15% up to 100% load, -30%/+15% below 80% and -40%/+15% below 60%. At full load the input power factor is 0.99, current distortion is at most 3% and there is no inrush current. Output is 400 V 3Ph+N with ±1% static stability and ±4% dynamic deviation on a 0-100% load step.
Efficiency is given at two points: 95.5% at 100% load and 95% at 50% load in online mode, and 98% in offline mode. Overload capability is 125% for 10 minutes and 150% for 1 minute at power factor 0.8. Short-circuit capability is 3 In for 40 ms from the inverter and 10 In for 10 ms through the bypass. The battery is maintenance-free VRLA at ±288 VDC nominal, charged on an IU curve to DIN 41773 and recharged to 90% in 5 hours.
Parallel operation is optional and field-upgradable; up to 20 units can be connected for capacity or redundancy. The architecture uses decentralised bypass: every UPS has its own static bypass and an output parallel isolator that separates it from the system. The page also defines the EPO connection (normally closed contact, 0.5 mm² screened cable, 100 m maximum) and the generator-running signal, which can disable the static bypass or block the charger. Weights without batteries range from 60 kg to 200 kg.
Key points
- Models (kVA/kW): TPH 10 10/9, TPH 15 15/13.5, TPH 20 20/18, TPH 25 25/22.5, TPH 30 30/27, TPH 40 40/36, TPH 50 50/45, TPH 60 60/54, TPH 80 80/72.
- Class VFI-SS-111, transformerless double conversion; output power factor 0.9.
- Input: power factor 0.99 at full load, THDi ≤ 3%, voltage tolerance -23%/+15% at 100% load and -40%/+15% below 60% load.
- Efficiency: 95.5% at 100% load and 95% at 50% load online; 98% in offline mode.
- Output: 400 V 3Ph+N, ±1% static, ±4% dynamic, THDv < 2% on linear and < 4% on non-linear load, crest factor 3:1.
- Overload: 125% for 10 minutes, 150% for 1 minute (at power factor 0.8); short circuit: inverter 3 In for 40 ms, bypass 10 In for 10 ms.
- Battery: VRLA, ±288 VDC, 5 hours to 90%; battery storage at most 6 months at ambient temperature.
- Parallel: optional, up to 20 units, decentralised bypass architecture.
- Cabinet sizes: 345x710x720, 345x710x1045, 440x910x1420 and 500x850x1600 mm; weight without batteries 60-200 kg; at least 20 cm rear clearance.
- Noise at 100%/50% load from 55/49 dBA to 62/55 dBA; IP20; EMC class C3.
Using it in design
- Read capacity from the kW column: the 80 kVA model is fully loaded at 72 kW of IT load, so plan the next rating up or a parallel unit for growth.
- Use 95.5% (full load) and 95% (half load) in the heat load calculation; in an N+1 system units run near half load, so base it on 95%.
- In the selectivity study, compare the short-circuit contribution of 3 In for 40 ms from the inverter and 10 In for 10 ms through the bypass with the instantaneous trip thresholds of downstream breakers.
- On sites with generators, wire the GEN-ON contact and set the bypass-disable and charger-block options to suit the generator rating.
- Because of the decentralised bypass, design equal-length bypass cables for every unit in a parallel system and show the parallel isolators on the single-line diagram.
- In the layout, include the 20 cm rear ventilation clearance, and add battery weight to the weight without batteries for floor loading.
Who should read it
Electrical designers selecting a 10-80 kVA three-phase UPS and engineers running selectivity and heat load calculations for server rooms and small data centres.
Document contents
- Series introduction
- Principles of Working
- Features
- Control Panel
- Interfaces
- N+X Power Scalable Parallel Redundancy
- Emergency Power Off
- Generating Set Connection
- Technical table: Input, Output, Battery, Efficiency, Miscellaneous, Standards
Publication details
- Authors
- ELIT
- Publisher
- ELIT
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ELIT ELIT TPH KING technical specification table. ELIT. http://www.elit-ups.eu/eng/ups_tph_king.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
