Technical guideFree to readYear not stated

ELIT NS 5–12 kVA Rev.7 datasheet

ELIT

A five-page Rev. 7 datasheet from Italian manufacturer ELIT Srl describing four models of the NS series single-phase online double-conversion UPS: NS5000 (5 kVA / 4.5 kW), NS6000 (6 / 5.4), NS10000 (10 / 9) and NS12000 (12 kVA / 9.6 kW), with input power factor 0.99, 0 ms transfer time and N+X parallel operation of up to 4 units.

On this page

Overview

The sheet is an extract from the single-phase UPS section of the ELIT product catalogue and covers the NS series. The series is an online double-conversion UPS under full-time DSP control, built from a rectifier, inverter, static switch, manual bypass and battery. The load is normally fed through the rectifier and inverter line, the battery feeds the inverter during an outage, and the static bypass moves the load to the emergency line on a short circuit or overload. Online or offline (ECO) operation can be set. A galvanic isolation transformer, dual input and a 60 Hz output converter are optional.

The technical table gives four models in VA/W: 5000/4500, 6000/5400, 10000/9000 and 12000/9600. Input is 160-280 VAC single phase at 45-65 Hz; power factor at full load is 0.99 and current distortion is below 6%. Output is 220/230/240 V ±2%, adjustable, with voltage distortion below 3% and a 3:1 crest factor. The battery is maintenance-free VRLA; standard backup time is 15 minutes for NS5000, NS6000 and NS12000 and 10 minutes for NS10000. Weights are 60, 90, 100 and 135 kg respectively.

Parallel operation has its own section. Standard units connect in groups of up to 4 through CAN-bus RJ45 cables on the rear panel with no additional components, either to add capacity or to build N+1 redundancy. Parallel distribution boxes are available up to 200 A (40 kVA) and external maintenance bypass boxes up to 400 A. According to the table, NS5000, NS6000 and NS10000 can be paralleled and NS12000 cannot. Additional battery cabinets extend backup time to several hours; the 1000 W external charger can be paralleled up to 4 units.

Efficiency is given as up to 90% in online mode for the smaller models, up to 93.5% for the larger ones and up to 95% in offline mode; these are upper bounds. Heat dissipation is below 450 W or 600 W depending on model group. RS232 and EPO are standard; a dry contact card, second RS232, RS485, USB and SNMP are options. The sheet names Windows 98 through Windows 7 for the monitoring software, which dates the document to an older product generation. Standards cited are IEC/EN 62040-1-1, 62040-2 and EN 62040-3.

Key points

  1. Models: NS5000 5 kVA / 4.5 kW, NS6000 6 kVA / 5.4 kW, NS10000 10 kVA / 9 kW, NS12000 12 kVA / 9.6 kW.
  2. Input: 160-280 VAC single phase, 45-65 Hz, power factor 0.99 at full load, THDi < 6%.
  3. Output: 220/230/240 V ±2%, THD < 3%, transfer time 0 ms, crest factor 3:1, DC start available.
  4. Standard backup time: 15 minutes for NS5000, NS6000 and NS12000, 10 minutes for NS10000.
  5. Efficiency: up to 90% or up to 93.5% in online mode depending on model, up to 95% in offline mode.
  6. Parallel: N+X up to 4 units over CAN-bus; NS12000 cannot be paralleled. Parallel distribution box to 200 A (40 kVA), external bypass box to 400 A.
  7. Weight: 60, 90, 100 and 135 kg; noise below 50 dBA at 1 m.
  8. Environment: 0-40 °C, humidity below 90% non-condensing; leakage current below 3 mA at full load.
  9. Standards: IEC/EN 62040-1-1, IEC/EN 60950-1, IEC/EN 62040-2, IEC/EN 61000-3-2, IEC/EN 61000-6-2, EN 62040-3.

Using it in design

  • For edge rooms and small IT rooms, work from the kW column: NS12000 has a 0.8 power factor (9.6 kW), the other models 0.9.
  • Where N+1 redundancy is required, choose NS10000 or a smaller model that can be paralleled instead of NS12000, and apply the 4-unit limit.
  • Use the heat dissipation ceilings in the sheet (450 W or 600 W) for the room heat load, and leave margin for part-load losses since online efficiency is given as an upper bound.
  • If the standard 10 or 15 minutes of autonomy is not enough, calculate recharge time together with the additional battery cabinet and the 1000 W external charger.
  • On parallel systems, add the 200 A parallel distribution box and the external maintenance bypass box (up to 400 A) to the single-line diagram.
  • Check the imbalance a 10-12 kVA single-phase load creates on three-phase distribution, and move to a three-phase input series if needed.

Who should read it

Electrical designers selecting a 5-12 kVA single-phase UPS, engineers planning edge and branch IT rooms and maintenance teams operating existing ELIT installations.

Document contents

  1. Features
  2. Principles of Working
  3. Control Panel
  4. N+X Power Scalable Parallel Redundancy
  5. Interfaces
  6. Accessories
  7. Rear Panel Explanation
  8. Block Diagram
  9. Technical table: Input, Output, Battery, Protection, Efficiency, Miscellaneous, Standards

Publication details

Authors
ELIT
Publisher
ELIT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ELIT ELIT NS 5–12 kVA Rev.7 datasheet. ELIT. http://elit-ups.eu/download/elitups_ns5_12eng.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.