Gama Sonic UPS6KL official product technical specifications

Gama Sonic Argentina

Gama Sonic Argentina's UPS6KL product page gives the electrical and mechanical data of a 6 kVA / 6 kW single-phase double-conversion on-line UPS with a 192 Vdc internal battery: 220 Vac output, a 460 x 191 x 720 mm cabinet and 54 kg weight.

On this page

Overview

The page presents the UPS6KL, a model in Gama Sonic Argentina's on-line UPS family. The unit is a double-conversion design rated 6 kVA / 6 kW and carries a 192 Vdc 7 Ah internal battery string. The manufacturer states a transfer time of zero from mains to battery and a typical 5 ms from inverter to bypass. In battery mode the output is a pure sine wave and voltage regulation is given as ±1%.

The technical table describes the input side in detail: 220 Vac nominal, an input voltage window of 110-300 Vac and an auto-sensing frequency range of 40-70 Hz. The feature list quotes the same window as 110-286 Vac, so both figures appear on the page. The bypass voltage window is adjustable, 230-264 Vac at the upper limit and 176-220 Vac at the lower limit. Input power factor is 0.99 with PFC, and the output voltage is selectable among 208, 220, 230 and 240 Vac.

Overload behaviour is stepped: the unit carries up to 105% continuously, up to 125% for 10 minutes and up to 130% for 30 seconds, and above 130% it switches to bypass at once. In bypass mode protection is a 40 A thermal breaker. The page also lists a maintenance switch, EPO, ECO mode, generator compatibility, cold start, and RS232, USB and RS485 interfaces. Efficiency, runtime tables and short-circuit current are not published on the page; a downloadable datasheet and manual are offered for those.

Key points

  1. Rating 6 kVA / 6 kW; double-conversion on-line topology.
  2. Input: 220 Vac nominal, 110-300 Vac window in the table (110-286 Vac in the feature list), 40-70 Hz auto-sensing, input power factor 0.99.
  3. Output voltage selectable 208/220/230/240 Vac; battery-mode regulation ±1%, frequency 50 or 60 Hz ±1 Hz.
  4. Overload: continuous up to 105%, 10 minutes up to 125%, 30 seconds up to 130%, immediate bypass above that.
  5. Transfer time: 0 ms mains to battery, typically 5 ms inverter to bypass.
  6. Battery: 192 Vdc 7 Ah internal string.
  7. Operating environment 0-40 °C, 0-90% RH non-condensing; noise below 45 dB.
  8. Dimensions 460 x 191 x 720 mm, weight 54 kg; the cabinet is on castors.

Using it in design

  • For single-phase edge-room or network-cabinet loads up to 6 kW, store 6 kVA / 6 kW, 220 Vac and the 192 Vdc battery together on the model entry.
  • Bypass protection is a 40 A thermal breaker, so check selectivity against the upstream protective device.
  • Compare the overload steps (10 minutes at 125%, 30 seconds at 130%) with the inrush profile of the load.
  • Carry the 54 kg weight and 460 x 191 x 720 mm footprint into floor loading and layout; the unit is a tower.
  • Base autonomy calculations on the 192 Vdc 7 Ah string and request the discharge table from the manufacturer datasheet.

Who should read it

Electrical designers selecting small single-phase UPSs and teams cataloguing products sold in the Latin American market.

Document contents

  1. Especificaciones técnicas
  2. Características
  3. Archivos descargables

Publication details

Authors
Gama Sonic Argentina
Publisher
Gama Sonic Argentina
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Gama Sonic Argentina Gama Sonic UPS6KL official product technical specifications. Gama Sonic Argentina. https://gamasonic.com.ar/producto/ups6kl/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.