MAXGE MCCB and ATS catalogue, 202509 V5

MAXGE

MAXGE's catalogue of moulded-case circuit breakers (MCCB) and automatic transfer switches (ATS), giving current options and control-unit scope for the ATS1, ATS3 and ATS4-GA series.

On this page

Overview

The catalogue (September 2025, V5) covers MCCB products and four ATS series; ATS1, ATS3 and ATS4-GA are covered here. The series switch automatically between two sources, and each rests on a different current range and breaker class: ATS1 is a CB-class unit built from miniature breakers, ATS3 a CB-class unit built from two moulded-case breakers, and ATS4-GA a PC-class switch driven by an electromagnetic coil.

The ATS1 series (63M model) consists of two 3P or 4P miniature circuit breakers, a mechanical chain mechanism and a controller. It is defined by 400 V AC, 50/60 Hz, 220 V control voltage, currents of 6, 10, 16, 20, 25, 32, 40, 50 and 63 A, a transfer time of 1.5 to 3 s and a mechanical life of 10000 operations. In the model code, X means economical, Y fire type and M mini type.

The ATS3 series is 3P and 4P, three-position, motor-driven, with an integral or split controller. Current options are 16, 32, 63 A for ATS3-63; 80, 100 A for ATS3-100; 125, 160, 200, 225 A for ATS3-225; 315, 400 A for ATS3-400; 500, 630 A for ATS3-630; 800 A for ATS3-800; and 1000, 1250 A for ATS3-1250. In the split type the controller is mounted in the panel and connected with about 2 m of cable.

The ATS4-GA series offers discrete current options from 16 A to 3200 A (frames of 100, 250, 630, 1600 and 3200 A). The integral GA type has three positions and includes over-voltage, under-voltage and phase-loss detection, plus a generator start/stop signal output with a 3 s delay when the main supply fails. The technical table gives utilisation categories AC-33B/AC-33iB, 8 kV impulse voltage, 400 V working voltage, short-circuit withstand values and transfer times.

Key points

  1. Discrete current selections are given for ATS1-63M, ATS3 and ATS4-GA: ATS1 6-63 A, ATS3 16-1250 A, ATS4-GA 16-3200 A.
  2. ATS1: 400 V AC, 50/60 Hz, 220 V control, transfer time 1.5-3 s, mechanical life 10000 operations.
  3. ATS3: 3P/4P, three positions, motor-driven, integral or split controller (about 2 m cable in the split type).
  4. ATS4-GA: frames 100, 250, 630, 1600, 3200 A; AC-33B for the 100 A frame, AC-33iB for larger frames.
  5. ATS4-GA rated limited short-circuit current 8 kA, 26 kA and 67 kA (by frame); transfer I-II or II-I 0.6 to 2.5 s.
  6. ATS4-GA control power DC 24, 48, 110 V or AC 220 V; 4-pole weight from 3.4 kg to 67 kg.
  7. The GA integral control covers three positions and source-failure monitoring; it gives a generator start signal after a 3 s delay when the main fails.
  8. In the ATS1 model code, X means economical, Y fire type, M mini type.

Using it in design

  • Record each ATS current rating with the frame and discrete step (for example 200 A on ATS3-225), not only the series name.
  • For data-centre critical loads, decide whether transfer times of 1.5-3 s (ATS1) or 0.6-2.5 s (ATS4-GA) will sit behind a UPS or on mechanical loads.
  • Compare the ATS4-GA utilisation category and limited short-circuit current with the site short-circuit current.
  • For the split controller type, add the in-panel controller position and the 2 m cable limit to the panel layout.
  • Include the 3 s generator start signal delay in the generator start-up and UPS battery time calculation.

Who should read it

Electrical engineers designing mains and generator changeover, and teams writing ATS specifications.

Document contents

  1. ATS1 Series Automatic Transfer Switch
  2. ATS2 and ATS3 Series
  3. ATS4-GA Series
  4. Technical parameter tables

Publication details

Authors
MAXGE
Publisher
MAXGE
Year
2025
Document number
202509 V5
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

MAXGE (2025). MAXGE MCCB and ATS catalogue, 202509 V5. MAXGE. 202509 V5. https://exhibitorsearch.messefrankfurt.com/images/original/document_downloads/10000016202601/508185/1769581292799_3176172053.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.