NOARK quick selection guide: ExATSNH
NOARK
A selection guide, published on CHINT's domain, for the NOARK ExATS series of automatic transfer switches, giving current steps, controller types and the order-code structure of the PC-class ExATSNH family.
On this page
Overview
The guide (in Chinese) covers the ExATS series. The ExATSNH section introduces a transfer switch for switching between two sources in distribution systems rated 400 V AC and below, utilisation category AC-33A, with a neutral overlap function (4N). Stated applications include rail transit, data centres, commercial buildings and hospitals.
The technical parameter table separates the family into frame codes: ExATSN1H (16, 20, 25, 32, 40, 50, 63, 80, 100 A), ExATSN2H (125, 160, 180, 200, 225, 250 A), ExATSN3H (315, 350, 400 A) and larger frames (500, 630 A, then columns for 800, 1000, 1250, 1600 A and 3200, 4000 A). The table gives 3, 4 or 4N poles, PC class, two- or three-position contacts, 800 or 1000 V insulation voltage and 8 or 12 kV impulse withstand.
Contact transfer time is 80 ms or less for the two-position type and 200 ms or less for the three-position type; larger frames show values down to 30 ms. Mechanical life is 20000, 15000 and 3000 operations and electrical life 8000, 6000 and 1000 operations depending on frame. Operating temperature is -20 to +75 °C for A and C controllers and -10 to +50 °C for B.
The order code has the form Ex-ATS-frame-H-poles-position-controller-communication; for example ExATSN1H463IIAT is a high-performance PC-class ATS of 100 A frame, four-pole, two-position, advanced controller, 63 A, with communication. The controller code is part of the complete ExATSNH order structure. Controllers come in A, B and C types; all detect voltage, frequency, phase loss and phase sequence, and offer fire-system linkage and operating modes; type B adds an LCD and load shedding.
Key points
- ExATSNH: 400 V AC and below, AC-33A, PC class, 3/4/4N poles, neutral overlap transfer (4N).
- Frame codes N1H, N2H, N3H and larger; 16-100 A for ExATSN1H, 125-250 A for N2H, 315-400 A for N3H.
- The selection scheme covers 16-630 A; the table also includes the upper frames (800 A and above, up to 4000 A).
- Contact transfer time at most 80 ms (two-position) and 200 ms (three-position).
- Mechanical life 20000, 15000, 3000 operations; electrical life 8000, 6000, 1000 operations (by frame).
- Operating temperature -20 to +75 °C for A/C controllers, -10 to +50 °C for B.
- The controller code (A, B) and communication code (T) are part of the complete ExATSNH order structure.
- Controller functions: over/under voltage and frequency, phase loss, phase sequence, fire linkage, adjustable delays; type B adds LCD and load shedding.
Using it in design
- Record the order code in its parts: frame, poles, two/three position, controller type and communication; do not treat the controller code as a separate item.
- On three-phase four-wire distribution, decide on 4N (neutral overlap) according to the neutral earthing arrangement of the mains-generator system.
- Compare the transfer time of up to 80 ms (two-position) or 200 ms (three-position) with load and UPS hold-up time.
- In generator-connected systems choose a type B or C controller (mains-generator mode, load shedding).
- The selection scheme is limited to 16-630 A; for larger currents use the table rows separately.
Who should read it
Electrical engineers designing mains-generator changeover and teams building ATS product data.
Document contents
- ExATSNH product overview
- ExATSNH parameter table
- Selection description and order code
- Controller functions and technical parameters
Publication details
- Authors
- NOARK
- Publisher
- NOARK
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document