PESS Enerji Teknolojileri

A 2023 Russian-language brochure from PESS Enerji Teknolojileri presenting its industrial static transfer switch (STS) family for two or three sources, single or three phase, with block diagrams, operating modes and technical data.

On this page

Overview

The brochure defines an STS as an electronic switch that moves a load automatically to another source when one fails or its voltage sags, and says it serves critical systems. The family has four models: STS-112 (two single-phase sources), STS-113 (three single-phase sources), STS-332 (two three-phase sources) and STS-333 (three three-phase sources). The units are designed for industrial environments and can be adapted to customer requirements.

Block diagrams show two- and three-source layouts with example applications: mains and UPS, two separate UPSs, mains and generator, or a solar inverter, mains and generator. A generator or renewable line can serve as the third source. Each source line has an input switch, a bypass switch and a fuse-failure alarm, and the control panel offers a 4-line by 20-column LCD, 24 or 27 indication LEDs and an optional 7-inch touchscreen.

Operating modes are described in detail. With a priority source selected, the load runs from it and returns automatically when its parameters recover. In manual transfer the other source's voltage, current and frequency are checked, and the command is cancelled if values are out of tolerance. If there is a phase difference, the command waits until it reaches the set value. On an output short circuit the STS opens quickly so the fault is not passed to other sources.

Service bypass, synchronisation failure and thyristor failure are also covered. In service bypass each line has a mechanical interlock that prevents both lines being opened at once. On thyristor failure the load is disconnected from the source feeding through the faulty thyristors and moved to the most suitable other source. The brochure is a product introduction: it does not list discrete current models, and 60 to 1250 A is given as a continuous range.

The technical table gives common values for the family. The brochure carries a 2023 copyright date, and project-specific configurations and operating conditions need the manufacturer's detailed documents.

Key points

  1. Four models: STS-112 and STS-113 (single phase, two and three sources), STS-332 and STS-333 (three phase, two and three sources).
  2. Rated current runs from 60 to 1250 A; rated voltage is 220/230/240 V single phase and 380/400/415 V three phase.
  3. Input voltage tolerance is +30 and -40 percent, frequency is selectable 50/60 Hz, and frequency tolerance is user-set at ±5 percent.
  4. Efficiency at full load is at least 99 percent.
  5. Overload capability: 125 percent for 10 minutes, 150 percent for 1 minute, 200 percent for 10 seconds, 300 percent for 1 second.
  6. Transfer time is 4 ms or less typical and 5 ms or less worst case.
  7. Operating temperature is -10 to +40 C, noise below 60 dBA, enclosure IP20, with natural or forced ventilation depending on rating.
  8. User-adjustable parameters include voltage range, synchronisation range, phase difference, over- and undervoltage thresholds, instantaneous short-circuit threshold and asynchronous transfer delay.
  9. Modbus RS485 and TCP/IP communication, a 1000-event history and redundant control-board supplies are listed features.

Using it in design

  • For dual-mains, UPS and generator combinations, decide whether a two- or three-source switch is needed; the three-source model makes a generator or renewable line a direct third source.
  • Compare the transfer time (4 ms typical, 5 ms worst case) with the load power supplies' hold-up time.
  • Set the inter-source frequency tolerance (±5 percent) and phase-difference threshold together with generator and UPS bypass synchronisation behaviour.
  • Pick the current rating from the 60 to 1250 A range and check the overload curve (125 percent for 10 min, 300 percent for 1 s) against the load profile; confirm discrete model ratings with the manufacturer.
  • Include the service bypass and mechanical interlock arrangement in the maintenance procedure.

Who should read it

Electrical designers and tender engineers selecting static transfer switches for dual-fed critical loads.

Document contents

  1. STS family
  2. Single-phase and three-phase models
  3. Special features
  4. Block diagrams (two and three sources)
  5. Control panel
  6. Benefits
  7. Operating modes
  8. Technical specifications

Publication details

Authors
PESS Enerji Teknolojileri
Publisher
PESS Enerji Teknolojileri
Year
2023
Document number
PR_PESS_STS_REV01_RU
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

PESS Enerji Teknolojileri (2023). PESS STS static transfer switch brochure, Russian edition. PESS Enerji Teknolojileri. PR_PESS_STS_REV01_RU. https://www.pesspower.com/wp-content/uploads/2024/01/PR_PESS_STS_REV01_RU.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.