Renutron Technical Specifications: Online UPS 1-10 kVA 1ph/1ph
Original title Renutron technical specifications Online UPS 1–10 kVA 1ph/1ph, p.1
Renutron Power Solutions India
Specification table for eight models of Renutron Power Solutions India's 1-10 kVA single-phase double-conversion online UPS: 230 Vac, ±1 percent output regulation, THD below 3 percent, 800 to 8000 W.
On this page
Overview
The document is a one-page technical specification table for the 1 to 10 kVA single-phase-in, single-phase-out online UPS range of India-based Renutron Power Solutions. Eight models (ON-01, 02, 03, 04, 05, 06, 075 and 10) are rated 1, 2, 3, 4, 5, 6, 7.5 and 10 kVA, with capacities from 800 W to 8000 W, which implies an output power factor of 0.8.
Input is 230 Vac +20 percent and 50 Hz ±6 percent, with input power factor of 0.85 to unity from an IGBT-based PFC rectifier. Battery voltage is customizable and runs from 36 V to 192 V depending on the model. Output is 230 Vac ±1 percent, 50 Hz ±0.5 percent, PWM sine wave, with output power factor of 0.8 to 1 lagging, and total harmonic distortion below 3 percent on linear load. Smaller models use a MOSFET-based and larger ones an IGBT-based double conversion. An inbuilt galvanic isolation transformer is fitted at the output.
Other figures: transient recovery of ±4 percent from no load to full load is corrected within 60 ms, inverter efficiency is 85 to 90 percent depending on DC voltage, and a low-battery pre-alarm sounds at 80 percent battery discharge. Options include manual or static bypass, SMS alerts through a GSM modem, an SNMP interface and digital metering. Ambient range is 0 to 50 °C with up to 95 percent non-condensing humidity, and noise is below 50 dB at 1 metre.
The document is a product data sheet; it carries no test report, efficiency curve or standards compliance statement. At 1 to 10 kVA it is small for data-centre scale and suits edge and office loads more than white-space power.
Key points
- Eight models: 1, 2, 3, 4, 5, 6, 7.5 and 10 kVA, with capacity from 800 W to 8000 W (output power factor 0.8).
- Input 230 Vac +20 percent, 50 Hz ±6 percent, input power factor 0.85 to unity.
- Output 230 Vac ±1 percent, 50 Hz ±0.5 percent, PWM sine, THD below 3 percent on linear load.
- Battery voltage is 36 V (1 kVA), 48 V, 72 V, 96 V, 120-144 V, 144-180 V and 180-192 V (10 kVA); customizable.
- Inverter efficiency is 85 to 90 percent, depending on DC voltage.
- Transient recovery: ±4 percent from no load to full load, corrected within 60 ms.
- Low-battery pre-alarm at 80 percent battery discharge; intermittent beep for 30 s on mains failure.
- Dimensions are 600 × 280 × 550 mm, 650 × 370 × 650 mm and 770 × 420 × 750 mm; noise below 50 dB at 1 m.
Using it in design
- Size on kW, not the nameplate kVA: with a 0.8 power factor in this series, the 10 kVA model delivers 8 kW.
- Because battery voltage is customer-defined, verify the battery string against the UPS DC voltage window.
- Compare the +20 percent input window and 6 percent frequency tolerance with supply quality; frequency tolerance matters on generator supply.
- State in the specification that bypass, SNMP and GSM are options.
- For critical data-centre loads, assess redundancy and parallel operation separately rather than relying on a single unit at this scale.
Who should read it
Designers and buyers selecting single-phase UPS for small critical loads, offices and edge sites.
Document contents
- Model and capacity
- AC input
- DC charger
- AC output
- Indications and alarms
- Metering
- Protections
- Additional features
- General (bypass, noise, ambient, dimensions)
Publication details
- Authors
- Renutron Power Solutions India
- Publisher
- Renutron Power Solutions India
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Renutron Power Solutions India Renutron technical specifications Online UPS 1–10 kVA 1ph/1ph, p.1. Renutron Power Solutions India. https://www.renutron.com/images/online-ups/1-10-kva-1ph-1ph-pfc-technical-specification.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.