Renutron Technical Specifications: Online UPS 10-50 kVA 3ph/3ph

Original title Renutron technical specifications Online UPS 10–50 kVA 3ph/3ph, p.1

Renutron Power Solutions India

Table for seven models of Renutron Power Solutions India's 10-50 kVA three-phase online UPS: 415 Vac input, 400 Vac ±1 percent output, THD below 3 percent, inverter efficiency above 92 percent.

On this page

Overview

The document is the specification sheet for the 10 to 50 kVA three-phase-in, three-phase-out online UPS range of Renutron Power Solutions India. Seven models are rated 10, 15, 20, 25, 30, 40 and 50 kVA; on unbalanced load the capacities are given as 8, 12, 16, 20, 24, 32 and 40 kW, so a power factor of 0.8 is the basis. A balanced-load option is available.

Input is 415 Vac +15/-20 percent, 50 Hz ±6 percent, with power factor above 0.8. The rectifier is 6-pulse (ATM technique, CVLC). Battery voltage is 240 to 360 V, 360 V on the larger models. Output is 400 Vac line-to-line ±1 percent (200 Vac optional), 50 Hz ±0.5 percent, PWM sine wave, with output power factor of 0.8 to 1 lagging. The inverter is microcontroller-controlled IGBT double conversion with an inbuilt galvanic isolation transformer. THD is below 3 percent on linear load and inverter efficiency is above 92 percent.

Protections include output overload and short circuit, low battery, DC overvoltage, output and input under/over voltage, and input phase loss and phase reversal. Options are manual or static bypass, GSM SMS alerts, an SNMP interface and an input auto phase corrector. Ambient range is 0 to 50 °C, humidity up to 95 percent, and noise is below 60 dB at 1 metre. Dimensions come in two cabinet groups, 950 × 450 × 800 mm and 1200 × 570 × 1000 mm.

The document is a data sheet and gives no per-model mass, efficiency curve or standards compliance. A 6-pulse rectifier calls for attention to input harmonic current, and the sheet does not state input THDi.

Key points

  1. Seven models: 10, 15, 20, 25, 30, 40, 50 kVA; 8, 12, 16, 20, 24, 32, 40 kW on unbalanced load.
  2. Input 415 Vac +15/-20 percent, 50 Hz ±6 percent, power factor above 0.8; 6-pulse rectifier.
  3. Battery voltage 240 to 360 V, 360 V on larger models.
  4. Output 400 Vac line-to-line ±1 percent (200 Vac optional), 50 Hz ±0.5 percent, PWM sine, output power factor 0.8 to 1 lagging.
  5. THD below 3 percent on linear load; inverter efficiency above 92 percent.
  6. Transient recovery: ±4 percent from no load to full load, corrected within 60 ms.
  7. Input single-phasing and phase-reversal indication and protection; optional auto phase corrector.
  8. Noise below 60 dB at 1 m; cabinets 950 × 450 × 800 and 1200 × 570 × 1000 mm.

Using it in design

  • Allocate load to the three-phase system in kW, not kVA: the 50 kVA model delivers 40 kW.
  • Include the 6-pulse rectifier's input harmonic current in generator and transformer sizing; input THDi is not in the sheet, so request it from the manufacturer.
  • Compare the wide input window (+15/-20 percent) with the supply quality.
  • Because battery voltage runs 240 to 360 V, match the string cell count to the UPS DC window.
  • State the bypass, SNMP and phase corrector options explicitly in the specification.

Who should read it

Electrical designers and specification engineers selecting small and medium three-phase UPS.

Document contents

  1. Model and capacity
  2. AC input
  3. DC charger
  4. AC output
  5. Indications and alarms
  6. Metering
  7. Protections
  8. Additional features
  9. General (bypass, noise, ambient, dimensions)

Publication details

Authors
Renutron Power Solutions India
Publisher
Renutron Power Solutions India
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Renutron Power Solutions India Renutron technical specifications Online UPS 10–50 kVA 3ph/3ph, p.1. Renutron Power Solutions India. https://www.renutron.com/images/online-ups/10-50kva-3ph-3ph-6pulse-technical-specification.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.