Switching AVO TTIM60000 60-600 kVA Modular UPS Brochure
Original title Switching AVO TTIM60000 60–600kVA brochure, PDF p.2, image table
Switching AVO
The Switching AVO TTIM60000 series is a 60-600 kVA modular UPS built from 30 kVA/27 kW PM30X power modules, with 0.9 output power factor, 95% normal-mode and 99% ECO-mode efficiency, input PF 0.99 and THDi under 3%.
On this page
Overview
The brochure presents the TTIM60000 series from Switching AVO Electro Power Limited of Kolkata, India, for IT/ITES, medical and railway applications. The system is built from 30 kVA/27 kW PM30X power modules; up to 30 modules can be paralleled, are hot-swappable and give N+X redundancy, with 600 kVA in about 0.5 m2 of floor area. Listed features include an independent charger per module, integrated IGBT design in one module, battery cold start, fully front access, top and bottom cable entry, a touch LCD and maintenance reminders for critical components. A modular version with built-in isolation transformer is also offered.
There are seven models: TTIM60600 (600 kVA/540 kW), TTIM60300 (300 kVA/270 kW), TTIM60180 (180 kVA/162 kW), TTIM60150 (150 kVA/135 kW), TTIM60120 (120 kVA/108 kW), TTIM6090 (90 kVA/81 kW) and TTIM60060 (60 kVA/54 kW). Input is 3-phase + neutral + ground, 400/415 V (line to line); the voltage window is 304-478 Vac at full load, with load decreasing linearly between 228 and 304 Vac according to the minimum phase voltage; frequency 40-70 Hz, power factor above 0.99 and THDi under 3% at 100% linear load.
Output is 380/400/415 V with 1.5% regulation, power factor 0.9, THDu under 1% on linear and under 5.5% on non-linear load, and crest factor 3:1. Overload is 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute and above 150% for 200 ms. Battery is +/-240 VDC, charge power is 20% of system power and charge precision +/-1%. System efficiency is 95% in normal mode, 99% in ECO mode and 95% in battery mode. The display is a 10.4 inch colour touch screen, protection IP20, operation 0-40 C, storage -40 to 70 C, humidity 0-95% and noise 65 dB at 1 m at full load. A power module is 460 x 790 x 134 mm and 30 kg.
Key points
- Seven models: 60, 90, 120, 150, 180, 300 and 600 kVA (54, 81, 108, 135, 162, 270, 540 kW).
- PM30X power module 30 kVA/27 kW; up to 30 modules in parallel; hot-swappable, N+X redundancy.
- Input 400/415 V 3P+N+PE; 304-478 Vac at full load; 40-70 Hz; PF >0.99; THDi <3%.
- Output 380/400/415 V, regulation 1.5%, PF 0.9, THDu <1% (linear) and <5.5% (non-linear).
- Overload: 110% for 1 hour, 125% for 10 min, 150% for 1 min, >150% for 200 ms.
- Battery +/-240 VDC; charge power 20% of system power; independent charger in each module.
- Efficiency: normal mode 95%, ECO 99%, battery mode 95%.
- Power module 460 x 790 x 134 mm, 30 kg; IP20; 0-40 C; noise 65 dB (1 m).
Using it in design
- With a 0.9 output power factor the 600 kVA system gives 540 kW; size critical load on kW.
- Build N+X redundancy by module count: add one or more modules to the number the load needs.
- With charge power at 20%, calculate recharge time and input power for large battery banks.
- The 99% ECO-mode efficiency means bypass operation with reduced conditioning; compare against load sensitivity.
- Feed the overload curve into protection and selectivity studies; plan layout around full front access.
Who should read it
Electrical designers and specification engineers selecting modular UPSs for data centres and critical facilities.
Document contents
- Applications
- Features
- Technical specifications table
Publication details
- Authors
- Switching AVO
- Publisher
- Switching AVO
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Switching AVO Switching AVO TTIM60000 60–600kVA brochure, PDF p.2, image table. Switching AVO. https://switchingavo.com/img/pdf/TTIM60000-60-600KVA.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.