WTI PTS automatic power transfer switch PTS250105

WTI (Western Telematic)

Datasheet of a family of 1U horizontal automatic transfer switches, in 120 V and 240 V models, that give single-corded rack devices a second power source.

On this page

Overview

The PTS family is an automatic transfer switch for legacy or single-corded rackmount devices that have no second power inlet. The unit has two AC inlets, one for the primary and one for a backup source. When the primary fails, the load moves to the backup, and it can switch back once the primary returns. Transfer is asynchronous, and the unit is stated to switch between out-of-phase sources.

Typical switching time is 8 to 12 ms and 16 ms at most at 60 Hz. No configuration is needed for installation and the active source is shown by LED. The chassis is a 1U horizontal 19 in rackmount unit (48.3 cm wide, 16.5 cm deep, 4.5 cm high).

The model table separates five product codes: PTS-8NE15-1R (2 x 15 A inlets, C14, 100-120 VAC, 8 NEMA 5-15R outlets), PTS-9CM20-1R and -2R (2 x 20 A inlets, C20, 100-120 and 200-240 VAC respectively, 8 x C13 and 1 x C19) and PTS-4MM20-1R and -2R (2 x 20 A inlets, 4 x C19). In line with UL requirements the permitted load values are de-rated to 80%: 12 A total on a 15 A feed and 16 A on a 20 A feed.

Other data: operating temperature 0 to 60 °C, humidity 10 to 90% RH, approvals UL 62368-1, cUL, EN 62368-1, IEC 62368-1 and FCC Class A. The 2.73 kg (PTS-8/9/4M) and 5.44 kg (PTS-14 models) values are shipping weights, not net unit weights.

Key points

  1. Typical transfer time 8-12 ms, 16 ms maximum at 60 Hz; asynchronous, including out-of-phase sources.
  2. Five models: PTS-8NE15-1R, PTS-9CM20-1R, PTS-9CM20-2R, PTS-4MM20-1R, PTS-4MM20-2R.
  3. Permitted total load against 15/20 A input feeds is 12/16 A (UL 80% de-rating).
  4. PTS-9CM20 models rate 10/16 A per outlet: 8 x C13 and 1 x C19.
  5. Voltage ranges 100-120 VAC and 200-240 VAC; 1U horizontal, 48.3 x 16.5 x 4.5 cm.
  6. Operating temperature 0 to 60 °C, humidity 10-90% RH.
  7. 2.73 kg and 5.44 kg are shipping weights, not net weights.
  8. Approvals: UL 62368-1, cUL, EN 62368-1, IEC 62368-1, FCC Class A.

Using it in design

  • Size the load against the de-rated totals in the table (12 A or 16 A), not the feed current.
  • In racks with single-corded devices, connect the A and B feeds to the PTS inlets from separate sources and check the transfer time against the device hold-up time.
  • Show the PTS itself as a single point of failure in the redundancy analysis; prefer dual-corded devices where possible.
  • Reserve 1U and 16.5 cm depth in the rack layout and compare the 0-60 °C operating limit with hot-aisle conditions.

Who should read it

Electrical and network infrastructure engineers designing in-rack power distribution and redundancy.

Document contents

  1. Features and operation
  2. The need for power redundancy
  3. Model table
  4. Weight, temperature, approvals

Publication details

Authors
WTI (Western Telematic)
Publisher
WTI (Western Telematic)
Year
2025
Document number
PTS250105
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

WTI (Western Telematic) (2025). WTI PTS automatic power transfer switch PTS250105. WTI (Western Telematic). PTS250105. https://ftp.wti.com/download/datasheets/specs_pts-automatic-transfer-switch.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.