White paperFree to read2020

Supercaps for Uninterruptible Power Supplies

Riello UPS

A 2020 Riello UPS white paper comparing supercapacitors (about 1,000,000 cycles) with batteries and flywheels for UPS bridging; for 200 kW and 15 seconds, 15-year cost is 61,021 euros against 74,867.

On this page

Overview

The white paper introduces electricity storage technologies (electrochemical batteries, hydrogen, electrochemical and electrostatic capacitors) and then covers supercapacitors. A supercapacitor stores electrical energy in an electrostatic field; a cell consists of two porous electrodes with a high surface-to-weight ratio immersed in an electrolyte. Energy density is lower than batteries and power density very high; since no chemical reaction is needed, it charges quickly, is highly efficient and is expected to last about 1,000,000 cycles at 25 degrees C.

Applications named are metro braking energy recovery, short power peaks of hospital imaging equipment, supporting short power peaks in UPS without oversizing batteries, and reducing battery replacement frequency in photovoltaic systems (batteries every 3-7 years, supercapacitors about every 20). For data-centre and medical sites, a generator backed by a short-autonomy supercapacitor UPS is proposed as the most effective continuity solution against generator start problems (fuel blockage, starter battery failure). A data centre can take 3 to 6 hours to move to a mirror site or shut down.

Advantages are high power density, instant charge and discharge, very slow ageing, insensitivity to temperature swings, no toxic or flammable components and a life of up to 15 years or 1,000,000 cycles. Drawbacks are low energy density, which needs frequent recharging, and high cost from carbon and graphene materials. The cost analysis takes 5 kW for 20 seconds (Vmax 300, Vnom 240, Vmin 160): over a 20-year UPS life the supercapacitor solution costs 3,841 euros against 7,782 euros for batteries (saving 3,941 euros); with a 30-year life and supercapacitor prices halving, the supercapacitor total is 4,368 euros and the saving 8,160 euros. UPS cost is excluded.

In a TCO comparison for a 200 kW UPS, 15 seconds of bridging and 15-year life, batteries cost 15,190 euros initially, flywheel 42,891 and supercapacitors 53,613; annual cost (including space, electricity, maintenance and replacement) is 3,976, 1,912 and 491 euros, with totals of 74,867, 71,619 and 61,021 euros; the supercapacitor saving is 13,846 euros (about 18%). This is a manufacturer white paper; the figures are example calculations and not list prices.

Key points

  1. Supercapacitor: electrostatic storage, high power density, low energy density, about 1,000,000 cycles (at 25 degrees C), life up to 15 years, low ESR and cycling efficiency of 95% or more.
  2. Advantages: instant charge and discharge, very slow ageing, insensitivity to temperature swings, no toxic or flammable components.
  3. Drawbacks: low energy density means frequent recharging; cost is high (carbon and graphene).
  4. A data centre can take 3-6 hours to move to a mirror site or shut down; a generator with a short-autonomy supercapacitor UPS is proposed against generator problems.
  5. Cost example: 5 kW for 20 seconds; over 20 years the supercapacitor total is 3,841 euros and the battery 7,782 euros (saving 3,941 euros).
  6. With a 30-year life and half-price supercapacitor replacement, the supercapacitor costs 4,368 euros and the saving is 8,160 euros.
  7. 200 kW, 15 s bridging, 15-year TCO: batteries 15,190 euros initial and 74,867 total; flywheel 42,891 and 71,619; supercapacitor 53,613 and 61,021; supercapacitor saving 13,846 euros (about 18%).
  8. In the TCO example batteries are replaced every 3 years (typical duration 2 years) while the supercapacitor lasts 15 years.
  9. Nanotechnology is expected to raise energy density; some forecasts say supercapacitors could take up to 50% of today's Li-ion applications within 15 years.

Using it in design

  • For UPS and generator applications needing short (seconds) bridging, compare a supercapacitor store with batteries and compute lifecycle cost over 15-30 years.
  • Set an autonomy target that covers generator start time and load acceptance; a supercapacitor solution suits this short time, while long autonomy needs batteries.
  • Reflect battery replacement (3-yearly in the example) and maintenance period against the supercapacitor's 10-yearly maintenance in the maintenance contract cost.
  • Include space, electricity, maintenance, replacement and disposal cost, and the monitoring system cost, in the calculation.
  • Check the voltage range (Vmax, Vnom, Vmin) against the UPS DC bus window; the examples use 300/240/160 V and 600/330 V windows.

Who should read it

Electrical designers comparing UPS energy storage options, engineers designing short-term bridging with generators, and investment decision makers.

Document contents

  1. Introduction
  2. Features
  3. Internal structure and functioning
  4. Application fields
  5. Why choose supercapacitors
  6. Costs
  7. Total cost of ownership
  8. Supercapacitors are eco-friendly devices
  9. Supercapacitors and nanotechnology
  10. Forecasts

Related standards

  • IEC 62040-3
  • IEC 62391-1

Publication details

Authors
Riello UPS
Publisher
Riello UPS
Year
2020
Document number
Whitepaper No. 01-2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Footer '© Riello UPS | All Rights Reserved'; free PDF.

Citation

Riello UPS (2020). Supercaps for Uninterruptible Power Supplies. Riello UPS. Whitepaper No. 01-2020. https://www.riello-ups.com/uploads/file/388/3388/Riello_UPS_WhitePaper_SuperCaps_01-20_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.