White paperFree to read2020

Lifespan of UPS Batteries

Riello UPS

Riello UPS's February 2020 white paper: it explains the gap between VRLA battery design life and service life, the ageing factors (life halves for every 10 degrees C above 20-25) and the practice of replacing 10-year batteries in year 7-8.

On this page

Overview

The white paper says battery failure is as serious for a UPS as a mains outage and that batteries are a significant share of UPS cost. Sealed lead-acid (VRLA) batteries, still used in most UPS, have low energy-to-weight and energy-to-volume ratios but give high surge current. Under EUROBAT guidance a battery has reached the end of service life when capacity falls below 80% of original; a 10-year design life battery falls below 100% capacity in year 6 even in ideal conditions and to 80% over the remaining 4 years. Replacing 10-year batteries in year 7 or 8 and 5-year batteries in year 3 or 4 is therefore accepted best practice.

Early failure is explained by the bathtub curve: infant mortality, random and wear-out failures; in wear-out, battery problems can account for over 98% of UPS failures. The factors affecting life are temperature (rated capacity is for 20-25 degrees C; a constant 10 degrees C rise halves service life), frequency and depth of discharge, time left discharged, incorrect application (such as telecom batteries in a UPS), operating voltage (overcharge causes dry-out and thermal runaway, undercharge causes sulphation), AC ripple current, poor storage and UPS topology. One battery's failure can shorten neighbouring batteries' lives.

Common problems are grid corrosion, sulphation (charging at a higher current for about 12 hours can sometimes recover), short circuits, dry-out, thermal runaway and top mossing. The prevention section recommends annual cell-level monitoring, terminal and connection checks, monitoring parameters covered by IEEE 1491 (cell and string voltages, AC ripple voltage and current, charge and discharge current, temperature, internal resistance, cycles), annual impedance testing, discharge (load bank) testing at installation and ideally yearly, and partial discharge testing of up to 80%. Most UPS test their batteries every 24 hours but this gives only a general indication.

Operating advice includes holding temperature at 20-25 degrees C, using a separate air-conditioned battery room where possible, not packing blocks too tightly, not letting batteries drain to 0% in long outages, and managing charge with battery care systems (floating, two-level, cyclical, commissioning). This is a manufacturer white paper; it stresses that accurate failure prediction is impossible and that safety margins must be used.

Key points

  1. Under EUROBAT a battery's service life ends when capacity falls to 80% of the initial value.
  2. A 10-year design life battery falls below 100% capacity in year 6 and to 80% over the remaining 4 years; 10-year batteries are replaced in year 7-8 and 5-year batteries in year 3-4.
  3. In the wear-out period battery problems can account for over 98% of UPS failures.
  4. Rated capacity applies at 20-25 degrees C; a constant 10 degrees C rise above the recommendation halves service life; short-term fluctuations have little effect.
  5. Unused batteries stored at 10 degrees C or below last longer; stored batteries need periodic top-up charging per the manufacturer's guidance.
  6. Most UPS test batteries every 24 hours but this is only a general indication; cell-level monitoring and annual impedance testing are recommended.
  7. IEEE 1491 monitoring parameters: string and cell voltages, AC ripple voltage and current, charge and discharge current, ambient and cell temperature, internal resistance and cycles.
  8. Discharge (load bank) testing is the only test that determines actual capacity; done at installation and ideally yearly; batteries are usually back within 24 hours, worst case several days.
  9. Partial discharge testing discharges by up to 80% and the batteries are available again within 8 hours; meanwhile capacity is only 20%.
  10. UPS are generally designed for 0-40 degrees C; 20-25 degrees C prolongs battery life; a separate air-conditioned battery room is an option.

Using it in design

  • Plan battery replacement with a safety margin, not on design life: year 7-8 for 10-year batteries and year 3-4 for 5-year batteries.
  • Target 20-25 degrees C in the battery or UPS room; where possible provide a separate air-conditioned, humidity-controlled battery room and space blocks for heat dissipation and case expansion.
  • Write a battery monitoring system covering IEEE 1491 parameters into the specification (cell voltage, internal resistance, temperature, ripple current).
  • Plan impedance and discharge testing at commissioning and in annual maintenance, and include the battery's out-of-service time during a discharge test in the operating scenario.
  • Ask the UPS supplier for charge and ripple current values; compare temperature-compensated charging and battery care system features.
  • State the battery application type (short-duration high-rate battery designed for UPS) in the procurement specification; telecom batteries do not give the same performance in a UPS.

Who should read it

Electrical engineers and operations managers designing, running and contracting maintenance for UPS battery systems.

Document contents

  1. Introduction
  2. Battery design life versus service life
  3. Premature battery failure: the bathtub curve
  4. Factors affecting the length of battery life
  5. The most common problems that impact battery life
  6. How to prevent premature battery failure (maintenance, monitoring, testing, temperature, correct use)
  7. Conclusion

Related standards

  • IEC 60896-21
  • IEC 62485-2
  • EUROBAT guide

Publication details

Authors
Riello UPS
Publisher
Riello UPS
Year
2020
Document number
Whitepaper No. 02-2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Footer '© Riello UPS | All Rights Reserved'; free PDF.

Citation

Riello UPS (2020). Lifespan of UPS Batteries. Riello UPS. Whitepaper No. 02-2020. https://www.riello-ups.com/uploads/file/389/3389/Riello_UPS_WhitePaper_02-20_Lifespan_of_UPS_Batteries_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.