White paperFree to read2020

Distributed vs Centralized Bypass Architectures in Parallel UPS Systems of Capacity N

Riello UPS

Riello UPS's May 2020 white paper: it compares centralized and distributed static bypass in capacity-N parallel UPS systems on reliability, power balance (cable length difference at most 2-5%), cost and footprint.

On this page

Overview

The white paper explains that an N system (parallel UPS sized to the load) has no built-in redundancy but offers lower installation and operating cost and higher asset utilisation, while an N+1 system adds one unit to give resilience to momentary overloads and faults. On an overload, short circuit or internal component failure the UPS switches automatically to its internal static bypass and transfers the critical load to the mains; this transfer should be a last resort and, apart from maintenance, used only for external factors such as overload, over-temperature or short circuit.

Two main architectures are compared. In centralized bypass, a single common static switch in a separate cabinet is rated for the total capacity needed in the N configuration and is controlled by a master UPS module; for example, a single 600 kVA bypass module for three 200 kVA UPS. In distributed bypass each UPS contains its own bypass switch; for three 200 kVA UPS, three 200 kVA static switches operate in parallel. In a planned transfer the command is passed to all units over a parallel CANBUS line; in an emergency each unit detects the fault independently and a simultaneous transfer is started.

The selection factors are reliability, maintenance resilience, power balance, cost and footprint with future planning. Centralized bypass has a single point of failure and loses its function when the static bypass is serviced; distributed bypass also loses function in maintenance because there is no redundancy. Power balance favours centralized bypass: in distributed bypass, differences in input and output cable length (impedance) of each UPS can unbalance bypass currents, and reasonable balance needs the difference in total cable length to be no more than about 2-5%; otherwise adding input line reactors raises cost considerably.

In conclusion there is no single right answer. Distributed bypass, with scalability and low first cost, suits small and medium sites with modules up to 200 kVA; centralized bypass suits larger data centres with multiple units of 300-400 kVA and above. This is a manufacturer white paper, the comparison rests on general principles, and it gives no numerical investment figures.

Key points

  1. An N system equals the load capacity and has no built-in redundancy; an N+1 system has one extra unit so that one unit may be offline.
  2. On overload, short circuit or internal component failure the UPS goes to internal static bypass; the transfer is treated as a last resort.
  3. Centralized bypass: one common static switch in a separate cabinet rated for total capacity (600 kVA for 3 x 200 kVA), controlled by a master UPS.
  4. Distributed bypass: each UPS contains its own static switch (3 x 200 kVA for 3 x 200 kVA); the command travels over parallel CANBUS and in a fault each unit detects independently.
  5. Centralized bypass has a single point of failure and loses bypass function in maintenance; distributed also loses function in maintenance as it has no redundancy.
  6. Power balance: with distributed bypass the total cable length difference must be at most about 2-5%; otherwise a static switch can be overloaded or protection can nuisance-trip; line reactors add cost.
  7. Centralized bypass is usually slightly more expensive (extra cabinet, cabling and switchgear); the gap is largest in small systems and shrinks as capacity grows.
  8. Distributed design offers pay-as-you-grow scalability; centralized bypass needs correct sizing on day one or must be replaced or oversized.
  9. Recommendation: distributed bypass for small and medium sites with modules up to 200 kVA; centralized for large data centres with multiple units of 300-400 kVA and above.

Using it in design

  • In parallel UPS design choose the bypass architecture by unit size and growth plan: distributed for modules up to 200 kVA, centralized for 300-400 kVA and above.
  • If distributed bypass is chosen, equalise input and output cable lengths to each UPS (difference at most 2-5%) and state it on the design drawings; if not possible, include line reactor cost in the budget.
  • With centralized bypass, prepare a maintenance bypass cabinet and operating procedure for the single point of failure and loss of redundancy during bypass maintenance.
  • Size the centralized bypass module for future total capacity; compare day-one value with the expansion scenario.
  • If dual input is required, add to switchgear cost that a distributed architecture needs double the number of input breakers per UPS.
  • Write into the operating policy that bypass transfer is a last resort used only for external factors such as overload, over-temperature and short circuit, and for maintenance.

Who should read it

Electrical engineers, consultants and data-centre facility managers designing parallel UPS systems.

Document contents

  1. Parallel UPS systems of capacity N and bypass architectures
  2. What are the main UPS bypass architectures (centralized, distributed)
  3. Factors impacting bypass architecture choice (reliability, maintenance resilience, power balancing, cost, footprint and future planning)
  4. Summary

Related standards

  • IEC 62040-3
  • IEC 62040-1

Publication details

Authors
Riello UPS
Publisher
Riello UPS
Year
2020
Document number
Whitepaper No. 05-2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Footer '© Riello UPS | All Rights Reserved'; free PDF from riello-ups.com downloads.

Citation

Riello UPS (2020). Distributed vs Centralized Bypass Architectures in Parallel UPS Systems of Capacity N. Riello UPS. Whitepaper No. 05-2020. https://www.riello-ups.com/uploads/file/392/3392/Riello_UPS_WhitePaper_05-20_Distributed_vs_Centralized_bypass_N_Capacity_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.