A 2020 Riello UPS white paper on choosing a data-centre UPS: VFI class, Tier architecture, modular type, battery technology, external bypass, generator compatibility and efficiency.
On this page
Overview
The white paper describes the role of static UPS in protecting a data centre against voltage drops, waveform distortion, interruptions and frequency changes. It states that critical applications and the power levels involved call for double-conversion (VFI, voltage and frequency independent) technology. In electrical sizing one must consider the apparent and active power of the critical load, its nature, whether service loads such as air conditioning are added, the nature of those service loads (motors, compressors) and future growth margin.
The architecture section gives example configurations by Uptime Institute class. For 200 kVA total: Tier I a single 200 kVA UPS, Tier II and III 2 x 200 kVA in N+1, Tier IV one 200 kVA UPS per radial; for 1000 kVA: Tier I two paralleled 500 kVA, Tier II and III 3 x 500 kVA in N+1, Tier IV a separate system per radial. Monolithic (single power module) and modular (hot-addable, scalable, N+1 inside) types are compared, with modular presented as best for data centres because of pay-as-you-grow and efficiency optimisation.
The battery section covers VRLA (life classes from 5 to 10/12 years and up to 15-20, ventilation per EN 50272-2), open-vessel lead-acid, open-vessel nickel-cadmium and lithium-ion (about 10 times faster charge, with BMS, no ventilation needed). Installation decisions cover modularity, parallel operation, radiality (synchronisation for dual radial), single or dual input (an alarm contact for static-bypass back-feed risk), external maintenance bypass switches (mandatory with more than two paralleled UPS), earth-leakage devices (type A for single-phase input and type B for three-phase input per EN 62040-1), additional transformers, generator compatibility (input current, rectifier inrush, harmonics, alternator sub-transient reactance, rectifier ramp, high power factor 0.9-1) and interfaces.
The energy-efficiency section defines PUE and lists UPS-side improvements: 3-level NPC2 IGBTs, short-connection power modules, controlled fixed losses (fan speed), efficiency optimisation at 50-75% load, feeding the load from the mains (VI and VFD, Eco and Smart modes, up to 3 points more efficient than VFI) and parallel energy saving that disables surplus UPS at low load. This is a manufacturer white paper; it gives selection criteria in a general frame and does not replace a product data sheet.
Key points
- Critical data-centre applications need double-conversion VFI (voltage and frequency independent) UPS.
- Sizing inputs: apparent and active power of the critical load, load nature, service loads to add (air conditioning), type of service load (motor, compressor) and growth margin.
- 200 kVA example: Tier I a single 200 kVA, Tier II/III 2 x 200 kVA N+1, Tier IV one 200 kVA per radial; 1000 kVA example: Tier I 2 x 500 kVA parallel, Tier II/III 3 x 500 kVA N+1, Tier IV a separate system per radial.
- Modular UPS: hot-addable, N+1 inside, pay-as-you-grow, automatic load management and efficiency optimisation.
- VRLA batteries come in life classes from 5 years to 10/12 and to 15-20 years; hydrogen requires ventilation per EN 50272-2.
- Li-ion batteries charge about 10 times faster than VRLA, come with BMS and can sit in a cabinet without ventilation.
- With more than two paralleled UPS the internal maintenance bypass switch cannot be used; an external bypass switch is mandatory and must be protected from unauthorised access by lock and procedure.
- Earth-leakage protection: per EN 62040-1 type A for single-phase input and type B for three-phase input; only delayed or selective devices are used; in a TN-S system UPS generally need no upstream residual-current device.
- With the UPS downstream of a generator, assess maximum input current, inrush, harmonics, rectifier power factor, sub-transient reactance, inhibiting battery charging and rectifier ramp.
- Efficiency: optimisation at 50-75% load, up to 3 points gain with VI and VFD modes against VFI, and disabling surplus UPS at low load.
Using it in design
- Set the UPS count and configuration by target Tier (N, N+1, dual radial) and compute total power including growth margin and service loads.
- Compare monolithic and modular options on scalability, internal N+1 and efficiency optimisation; draw up a pay-as-you-grow installation plan for modular.
- Choose battery technology (VRLA, open vessel, Li-ion) on cost, life, charge time, ventilation and EN 50272-2 requirements; do the ventilation calculation for hydrogen-emitting batteries.
- In systems with more than two paralleled UPS, add the external maintenance bypass switch, an output isolator for each UPS and the lock and procedure scheme to the single-line diagram.
- If dual input is used, wire the alarm contact to the trip coil of the bypass line protective switch or to a contactor against the static bypass back-feed risk.
- When placing the UPS downstream of a generator, check input current, inrush, harmonics and alternator sub-transient reactance together; write rectifier ramp and delayed start into the specification.
- Define the interfaces (dry contacts, SNMP, MIB, web, Modbus, BACnet) at design stage.
Who should read it
Electrical engineers, consultants and facility managers designing data-centre UPS systems.
Document contents
- Introduction
- Evaluation criteria for choosing the right UPS for the data center (UPS classification, electrical sizing)
- Typology of architecture (Uptime Institute Tier examples)
- Type of UPS (monolithic and modular)
- Type of batteries
- The installation of the UPS (modularity, parallel, radiality, power supply, external bypass, differential switches, transformers, generator, high power factors, interfaces)
- The role of UPS in energy efficiency of data centers
Related standards
- IEC 62040-1
- IEC 62040-3
- EN 50272-2
Publication details
- Authors
- Riello UPS
- Publisher
- Riello UPS
- Year
- 2020
- Document number
- Whitepaper No. 06-2020
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Each page footer: '© Riello UPS | All Rights Reserved'; free PDF download.
Citation
Riello UPS (2020). UPS to Protect Power Supply of Data Center. Riello UPS. Whitepaper No. 06-2020. https://www.riello-ups.com/uploads/file/30/3030/Riello_UPS_WhitePaper_UPS_for_DataCenter_06-20_EN_.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.