Technical guideFree to read2025

ROHM's 800VDC Architecture Solutions for AI Servers

Original title ROHM’s 800VDC Architecture Solutions for AI Servers

ROHM

A manufacturer white paper that compares the power-conversion stages of an 800 V DC rack distribution (side power rack and in-rack DC-DC) with SiC and GaN device choices, including simulation and board-size estimates.

On this page

Overview

The paper explains that AI accelerator power has risen from 100 W to over 1000 W and rack power from 20-30 kW to over 100 kW, which pushes 48 V and 12 V distribution to its limits. Carrying the same power at low voltage means large currents, I²R loss, thick copper cable and restricted airflow. As the answer it presents 800 VDC distribution, pioneered by NVIDIA; according to the cited source, converting 13.8 kV AC grid power directly to 800 VDC can raise efficiency by up to 5%, and doubling the voltage halves the current and can cut copper use by up to 45%.

In the architecture AC-DC conversion moves out of the rack into a side (sidecar) power rack, where efficiency is critical; the DC-DC stage stays inside the IT rack, where power density decides. For the power source a Vienna rectifier PFC with a three-phase isolated LLC converter is recommended: 400 VAC input, 800 VDC output. In simulation the Vienna rectifier exceeds 99% efficiency up to 50 kW, and the three-phase LLC reaches about 99.5% at 33 kW; turn-off losses are about 60% of total LLC loss.

On the IT rack side, a three-phase LLC converts 800 VDC to 50 VDC. At 10 kW, efficiency exceeds 99% at switching frequencies of 125 kHz and below; efficiency falls as frequency rises, so raising frequency alone does not raise power density. A design study of a 20 kW IT rack gives 40 x 91 x 700 mm and 7.8 W/cc with SiC, and 40 x 55 x 605 mm and 15 W/cc with GaN (cascade three-phase LLC); GaN keeps 99% efficiency up to 500 kHz.

Limits: the figures rest on ROHM's PLECS simulations and board-size estimates; the simulations include power-device losses but exclude peripheral components such as reactors and capacitors. The paper is a component and topology selection guide; it does not cover site-level protection, earthing, battery integration or maintenance.

Key points

  1. AI accelerator power has risen from 100 W to over 1000 W and rack power from 20-30 kW to over 100 kW (up to 500 kW projected).
  2. Per the cited NVIDIA source, 800 VDC raises efficiency by up to 5% and cuts copper use by up to 45%; doubling the voltage halves the current.
  3. AC-DC conversion sits in a side power rack, DC-DC conversion inside the IT rack.
  4. Side power rack: Vienna rectifier PFC (400 VAC input, 800 V) with a three-phase isolated LLC; existing AC-DC units are in the 20-33 kW range.
  5. Simulation: Vienna rectifier above 99% efficiency up to 50 kW; LLC about 99.5% at 33 kW.
  6. In the LLC, turn-off losses are about 60% of total circuit loss; a large magnetising inductance degrades load response and line regulation.
  7. IT rack DC-DC: 800 VDC to 50 VDC; above 99% efficiency at 125 kHz and below at 10 kW; 20 kW SiC rack 40x91x700 mm, 7.8 W/cc; GaN rack 40x55x605 mm, 15 W/cc.
  8. The reported PLECS loss simulations exclude peripheral components such as reactors and capacitors.
  9. 5th-generation SiC MOSFETs cut normalised on-resistance by about 30% against 4th generation; total loss falls about 33% at 33 kW and 100 °C.

Using it in design

  • When comparing 800 VDC architectures, note the efficiency and copper-saving claims together with the source's conditions (13.8 kV AC direct conversion); do not apply them unchanged to your own site topology.
  • When planning the side power rack's location, cable route and cooling, allow for the 20-33 kW AC-DC module scale and the 800 VDC bus length.
  • Do not use simulated efficiencies as system efficiency; add reactor, capacitor, busbar and cable losses separately.
  • For the in-rack DC-DC, confirm the trade-off between power density (W/cc) and efficiency, and the switching-frequency limits, with the supplier.
  • Specify protection, fault-current limiting and battery interface for DC distribution separately; the paper does not address them.

Who should read it

Electrical designers evaluating high-density AI rack power architectures, and power-electronics engineers.

Document contents

  1. Abstract
  2. Introduction and market trends
  3. The need for 800VDC architecture
  4. Recommended topologies: device selection, system overview, side power rack, IT rack, components, SiC modules
  5. Advantages of ROHM's 800VDC solutions: EcoSiC and EcoGaN
  6. Appendix: DC link capacitor selection, simulation support

Publication details

Authors
ROHM
Publisher
ROHM
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.

Citation

ROHM (2025). ROHM’s 800VDC Architecture Solutions for AI Servers. ROHM. https://fscdn.rohm.com/en/products/databook/white_paper/common/800vdc_architecture_solution_for_ai_server_wp-e.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.