White paperFree to read2021

Rack Powering Options for High Density in 230 V AC Countries

Schneider Electric · Paul Lin

This Schneider Electric white paper compares ways to feed high-density racks in 230/400 V IEC markets using 16 A and 32 A single- and three-phase whips. The choice of whip fixes both capacity and protection coordination, so it needs settling early in design.

On this page

Overview

The paper is the IEC-market counterpart of the North American WP 29 and deals with rack power in 230/400 V networks. It considers 16 A and 32 A single-phase and three-phase whips, IEC 60309 connectors and C13/C19 outlets together. The goal is to set a sensible default feed for every rack and add dedicated whips only for unusual loads, rather than engineering each rack individually. That standardisation helps both installation and day-to-day operation of the room.

Its method is to tabulate the whip options and compare the power each can deliver to a rack along with an approximate unit cost. A single 230 V 16 A circuit carries 3.7 kW, and one to four circuits give 3.7, 7.4, 11 and 14.7 kW. The whip options span roughly 2.3 to 44 kW per rack. A 32 A three-phase whip delivers about 22.1 kW, while a 16 A three-phase whip delivers about 11 kW.

Breaker coordination is a key topic. To avoid the mismatch between a 16 A branch circuit and a 25 A feeder, the paper advises preferring 32 A three-phase whips over 25 A ones. It also points out that European 16 A breakers are typically 100%-rated, so the 80% derating familiar from North American practice is not applied in the same way.

On loading, the paper quotes expected rack densities by workload type: 9-22 kW for business workloads and 23-55 kW for scientific ones. According to the survey it cites, 6-10 kW per rack occurs about 48% of the time. The recommended default is a three-phase provision for every rack, with dedicated whips for unusual loads. Cost figures are indicative for 2 kW per rack and range from $270 to $645 per kW depending on whip type.

Key points

  1. A 230 V 16 A branch circuit carries 3.7 kW; one to four circuits give 3.7 / 7.4 / 11 / 14.7 kW.
  2. Whip options deliver about 2.3-44 kW per rack; a 32 A three-phase whip is about 22.1 kW and a 16 A three-phase whip about 11 kW.
  3. Indicative cost at 2 kW per rack is $270-$645 per kW depending on whip type.
  4. Prefer 32 A three-phase whips over 25 A to avoid 16 A branch / 25 A feeder coordination problems.
  5. Expected rack density: business workloads 9-22 kW, scientific workloads 23-55 kW.
  6. In the cited survey, 6-10 kW per rack occurs about 48% of the time.
  7. European 16 A breakers are typically 100%-rated, unlike the 80% derating in NEC practice.
  8. Default to a three-phase provision per rack, with dedicated whips for unusual loads.

Using it in design

  • When the project region is IEC, start rack power from 230/400 V, 16 A or 32 A three-phase IEC 60309 whips.
  • Calculate rack kW without automatically applying the NEC 80% factor; specify the continuous-load factor appropriate to the project.
  • Assess the source’s rack-density bands of 9–22 kW for business workloads and 23–55 kW for HPC/scientific workloads.
  • Check coordination between branch and feeder breakers and recommend 32 A rather than 25 A three-phase whips.

Who should read it

Electrical designers and operations engineers planning rack power distribution on IEC networks.

Related standards

  • IEC 60364
  • IEC 60309
  • IEC 60320
  • EN 50600-2-2

Publication details

Authors
Paul Lin
Publisher
Schneider Electric
Year
2021
Document number
WP 28
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Paul Lin (2021). Rack Powering Options for High Density in 230 V AC Countries. Schneider Electric. WP 28. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-6CYK3V_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.