Comparison of Neutral Wire Distribution Options for Data Centers
Schneider Electric · Malik Megdiche, Avelino De Oliveira et al.
This paper examines what happens when a 4-pole transfer switch at the main LV switchgear changes the UPS and downstream loads from a TN earthing system to an ungrounded system during generator changeover. It compares eight neutral distribution solutions.
On this page
Overview
The paper examines what happens when a 4-pole transfer switch at the main LV switchgear changes the UPS and downstream loads from a TN earthing system to an ungrounded system during generator changeover. It describes the resulting power-quality disturbances. The introduction also compares the typical 400/230 V global architecture with the 480/208/120 V North American one. One example of the disturbances is given: 25 µH x 100 A / 5 µs on a PEN conductor induces about 500 V. Transients of this kind show that the handling of the neutral conductor during changeover matters in design.
It then compares eight neutral distribution solutions, including isolation and PDU transformers, tabulating losses, footprint and cost trade-offs. Losses for transformer-based options are quantified: the PDU transformer option adds about 3% losses, and neutral conductor losses are about 1.1%. An isolation transformer on the UPS input adds about 1.98% at 100% load and about 0.7% in eco mode. These transients matter for power quality at sensitive IT equipment, and the choice of solution has a lasting effect on both initial investment and operating losses.
A limit is that the paper is a comparison of options rather than a design procedure, so the choice has to be made together with local regulations and site details. Even so, the figures show that earthing and neutral decisions feed directly into the efficiency calculation. Selecting among them therefore means weighing power quality, efficiency and cost together, instead of treating the neutral as a purely wiring detail.
Key points
- PEN conductor transient example: 25 µH x 100 A / 5 µs is about 500 V induced.
- The PDU transformer option adds about 3% losses; neutral conductor losses are about 1.1%.
- An isolation transformer on the UPS input adds about 1.98% losses at 100% load and about 0.7% in eco mode.
- Eight neutral distribution solutions are compared on losses, footprint and cost.
- The typical 400/230 V global architecture is compared with the 480/208/120 V North American one.
Using it in design
- In the one-line design, check a four-pole transfer switch against a UPS neutral that is not separately derived.
- Show the options: a 3-pole switch with solid neutral, or an isolation transformer.
- When a transformer is chosen, add its 1-3% losses to the efficiency model.
Who should read it
Electrical engineers designing generator changeover, earthing and neutral distribution.
Related standards
- IEC 60364-1
- IEC 60364-4-44
- IEC 62040-3
- NEC 250
Publication details
- Authors
- Malik Megdiche; Avelino De Oliveira; Eric Brun
- Publisher
- Schneider Electric
- Year
- 2022
- Document number
- WP 41
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Malik Megdiche; Avelino De Oliveira; Eric Brun (2022). Comparison of Neutral Wire Distribution Options for Data Centers. Schneider Electric. WP 41. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP41_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
