White paperFree to read2016

Comparing UPS System Design Configurations

Schneider Electric · Kevin McCarthy, Victor Avelar

Compares capacity (N), isolated redundant, parallel redundant, distributed redundant and system-plus-system UPS architectures on availability, cost and efficiency.

On this page

Overview

The paper covers five principal UPS architectures: capacity (N), isolated redundant, parallel redundant (N+1), distributed redundant (catcher, with and without STS, tri-redundant) and system-plus-system 2N/2(N+1). Each gets a one-line description and pros and cons, backed by a Markov/RBD availability comparison.

Each architecture is related to Uptime Tier classes and to an indicative first cost per rack. The paper also shows how module size in N+1 systems sets per-module load and therefore efficiency: for a 240 kW load, 2 x 240 kW modules run at 50% and 5 x 60 kW modules at 80%.

Modelled availability is 99.92% for N, 99.93% for N+1, 99.9994% for distributed redundant and 99.99997% for 2(N+1). In the analysis, isolated redundant and N systems showed the same unreliability (about 1.8% per year). N systems need 2-4 hours a year of full shutdown for system-level maintenance unless a wrap-around bypass exists.

The conclusion is that 2(N+1) feeding dual-corded loads directly gives the highest availability. The selection guide points N+1 or isolated redundant at IT loads typically under 500 kW, distributed redundant above 1 MW, and 2N/2(N+1) at large multi-MW sites. The figures are comparative and should not be read as absolute values.

Key points

  1. Modelled availability: N 99.92%; isolated redundant 99.93%; N+1 99.93%; distributed redundant catcher 99.9989%; distributed redundant 99.9994%; 2(N+1) 99.99997%.
  2. Indicative capex: Tier I $13.5-18k/rack; Tier II $18-24k; Tier III $24-30k; Tier IV $36-42k (30 ft²/rack, 2.3-3.8 kW/rack basis).
  3. N+1 module loading for a 240 kW load: 2x240 kW 50%; 3x120 66%; 4x80 75%; 5x60 80%.
  4. Typical 3-phase module overload rating: 125% for 10 minutes before transfer to static bypass.
  5. Isolated redundant and N systems had the same unreliability (about 1.8% per year) in the analysis.
  6. N systems need 2-4 h/yr full shutdown for system-level maintenance unless a wrap-around bypass exists.
  7. Selection guide: N+1 / isolated redundant typically under 500 kW IT; distributed redundant above 1 MW; 2N/2(N+1) for large multi-MW.

Using it in design

  • Assess N, isolated redundant, N+1, distributed redundant (catcher/STS), tri-redundant, 2N and 2(N+1) in the topology library, and label availability values as comparative rather than absolute.
  • Compute per-module load as load / (number of modules x module kW) and feed it to the UPS efficiency curve.
  • Map each topology to a Tier hint and scale the per-Tier cost ranges to the current year in estimates.
  • Show a warning that N systems need a full shutdown for maintenance unless a wrap-around bypass is provided.

Who should read it

Electrical designers choosing a UPS architecture and decision makers weighing redundancy against cost.

Related standards

  • Uptime Tier Standard: Topology
  • TIA-942
  • EN 50600-2-2
  • IEEE 3006.7

Publication details

Authors
Kevin McCarthy; Victor Avelar
Publisher
Schneider Electric
Year
2016
Document number
WP 75
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Kevin McCarthy; Victor Avelar (2016). Comparing UPS System Design Configurations. Schneider Electric. WP 75. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_SADE-5TPL8X_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.