Protections for Data Centers Powered by Direct Current (Technical Paper)
Siemens / NVIDIA · Guang Yang, Mike Tu
This 2025 Siemens/NVIDIA paper examines how to protect 800 V DC distribution for megawatt AI racks. It compares grounding schemes and protection devices through simulations of a 1 MW block.
On this page
Overview
The paper compares floating, high-resistance and solid grounding, each at +/-400 V and 800 V. On the device side it simulates fuses, mechanical breakers, solid-state and hybrid breakers. Interruption speeds are laid out together: solid-state breakers act in under 0.5 ms, hybrids in 1-3 ms, while a fuse reached its melting I2t in about 1 ms and needed about 20 ms to recover. In the 1 MW floating 800 VDC case study, a solid-state circuit breaker (SSCB) held peak fault current below 800 A and healthy loads saw only about 1 V of variation.
Because the fault current is limited, neighbouring racks keep running unaffected. The result shows concretely why AC-style selectivity logic has to be rebuilt for DC. Personnel protection and arcing expose gaps in the standards. UL 943C Class E ground-fault interruption is about 850 us at 400 VDC and about 300 us at 800 VDC, while UL 2367 covers e-fuses only up to 60 VDC. Arc mitigation shorted an initiated arc in about 3 ms.
For ride-through, holding voltage within 10% for 10 ms at 1 MW needs about 80 mF of capacitance. The work is simulation-based, covers one block size and selected topologies, and is neither field measurement nor a full standard proposal. It is still a core reference for anyone planning 800 VDC because it shows that DC arc-flash cannot reuse the IEEE 1584 results used for AC and that protection choice is tied to the grounding decision.
Key points
- Solid-state breakers interrupt in under 0.5 ms; hybrid 1-3 ms; fuse reached melting I2t in about 1 ms with about 20 ms recovery.
- With SSCB, peak fault current under 800 A and about 1 V variation on healthy loads (1 MW floating 800 VDC simulation).
- Keeping voltage within 10% for 10 ms at 1 MW needs about 80 mF.
- UL 943C Class E ground-fault interruption: about 850 us at 400 VDC, about 300 us at 800 VDC.
- UL 2367 covers e-fuses only up to 60 VDC.
- Arc mitigation shorted an initiated arc in about 3 ms.
- Grounding schemes compared: floating, high-resistance, solid; +/-400 V and 800 V.
Using it in design
- If 800 VDC is selected, require SSCB/hybrid breakers in the protection catalog.
- Require an explicit grounding-scheme decision (floating, high-resistance, solid).
- Add a DC arc-flash study as a mandatory task; do not reuse AC IEEE 1584 results for DC.
- Size load-side ride-through capacitance against the 10 ms / 10% criterion (about 80 mF at 1 MW).
- Record the UL gaps (the UL 2367 60 VDC limit) in the personnel-protection risk register.
Who should read it
Electrical engineers designing 800 VDC distribution and protection for megawatt-class AI racks.
Related standards
- UL 943C
- UL 2367
- IEC 60364-4-41
- NFPA 70E (DC arc flash)
- IEC 60947-2
Publication details
- Authors
- Guang Yang; Mike Tu
- Publisher
- Siemens / NVIDIA
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Guang Yang; Mike Tu (2025). Protections for Data Centers Powered by Direct Current (Technical Paper). Siemens / NVIDIA. https://assets.new.siemens.com/siemens/assets/api/uuid:cacbc29b-5d0d-4b12-9053-696eb0b43e74/Protections-for-Data-Centers-Powered-by-Direct-Current-Technical-Paper_original.pdf