Model-based analysis of data center tiers: a reliability and availability perspective
Journal of Reliable Intelligent Environments (Springer Science and Business Media LLC) · Lubnnia Souza, Kádna Camboim et al.
An open-access 2026 paper in the Journal of Reliable Intelligent Environments models Tier I-IV data centres with RBD and stochastic Petri nets; annual downtime falls from 86.74 h to 0.81 h and cooling is the most influential subsystem.
On this page
Overview
The paper presents a hierarchical and heterogeneous modelling approach that represents the IT, electrical and cooling infrastructures of a data centre according to Tier I to Tier IV redundancy specifications. The cooling and electrical infrastructures are modelled with reliability block diagrams (RBD) and overall system behaviour with stochastic Petri nets (SPN). Four SPN models, one per Tier, are built, with places, transitions and guard expressions tabulated.
The evaluation focuses on availability, reliability, uptime and downtime over a year of 8760 hours. The model results are compared with Uptime Institute reference values (Tier I 99.67%, Tier II 99.74%, Tier III 99.98%, Tier IV 99.99%). As redundancy is added step by step, downtime falls markedly, and from Tier II onward each level gives a measurable gain.
In the sensitivity analysis MTTF values are varied from -50% to +50% and MTTR separately, with each subsystem (electrical, cooling, IT) examined on its own. The result shows that system robustness is directly proportional to redundancy and that Tier IV is the least sensitive to MTTF and MTTR changes. The subsystem that most affects availability is cooling. The authors state the limits plainly: common-cause failures (natural disaster, human error) and cost are not considered, and although Tier IV is the most reliable, its economic viability may not suit every application. Future work will address sustainability and energy source costs.
Key points
- Uptime Institute reference availabilities: Tier I 99.67%, Tier II 99.74%, Tier III 99.98%, Tier IV 99.99%.
- Tier I model results: availability 99.00%, reliability 79.72%, uptime 8673 h/year, downtime 86.74 h/year.
- Tier II: availability 99.92%, reliability 98.07% (up 18.35 points), uptime 8754 h/year, downtime 5.89 h/year.
- Tier III: availability 99.98%, reliability 99.71%, uptime 8758 h/year, downtime 1.22 h/year.
- Tier IV: availability 99.99%, reliability 99.72%, uptime 8759 h/year, downtime 0.81 h/year.
- In the sensitivity analysis MTTF is varied from -50% to +50% over a 3000 h period.
- The subsystem with the greatest effect on availability is cooling.
- Tier IV shows the lowest sensitivity to MTTF and MTTR changes thanks to its 2N hot-standby architecture.
- Common-cause failures and cost are not included in the model.
Using it in design
- When setting a Tier target, model the redundancy of the cooling infrastructure as well as the electrical one; in the paper cooling is the subsystem with most effect on availability.
- Run a sensitivity analysis on MTTF and MTTR of critical equipment to find which repair-time or failure-rate improvement cuts downtime most.
- Use the comparison of Tier II to III (annual downtime from 5.89 h to 1.22 h) in the investment case, but assess cost and common-cause failures separately.
- Use the mixed RBD and SPN model in availability calculations so that standby switch-in delay and repair order are not neglected.
- When taking model results to site, treat the common-cause failures that the authors left out in a separate risk analysis.
Who should read it
Reliability engineers calculating data centre availability, designers choosing a Tier level, and researchers.
Document contents
- Introduction
- Background
- Related works
- Methodology
- Proposed models
- Result analysis
- Conclusion
Related standards
- Uptime Institute Tier Standard
- ANSI/TIA-942
- IEEE 3006.8
Publication details
- Authors
- Lubnnia Souza; Kádna Camboim; Gustavo Callou; Jean Araujo
- Publisher
- Journal of Reliable Intelligent Environments (Springer Science and Business Media LLC)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Landing page states open access; publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Lubnnia Souza; Kádna Camboim; Gustavo Callou; Jean Araujo (2026). Model-based analysis of data center tiers: a reliability and availability perspective. Journal of Reliable Intelligent Environments (Springer Science and Business Media LLC). https://doi.org/10.1007/s40860-026-00275-5
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
