Data Center Busway Guide: Choosing the Right Busway for Your Application
Starline
Starline selection guide comparing its T5 open-channel (250-1200 A) and Series HP enclosed (630-6000 A) busway families by amperage, layout change, power density and growth.
On this page
Overview
Starline's guide opens by noting that AI and high-performance computing have more than doubled rack densities in recent years and that data centres are expected to scale faster and more flexibly. Starline says it has supplied data-centre busway for over 30 years, with a UL857-listed portfolio from 100 to 6000 A.
The comparison sets two families side by side. T5 is open-channel, covering 250-1200 A (UL) and 250-1250 A (IEC); it suits rack-level distribution and fast-changing enterprise and colocation sites. Plug-in units can be added, moved or removed without downtime, and compression joints need no re-torquing. Series HP is enclosed, covering 630-6000 A (UL) and 630-6300 A (IEC); it is for high-capacity bulk power in hyperscale or AI data centres and is custom-engineered.
Protection and monitoring differ: T5 offers standard indoor and IP54, with Series-S for liquid-cooled environments, and the M70 Critical Power Monitor at feed and branch level. Series HP has IP42, IP54 and IP55 as standard, IP65 outdoor on request, with real-time temperature sensing and power monitoring. Certifications are listed as UL857, IEC 61439-6, ETL, CCC, NOM, VDE and CE for T5, and ANSI/UL857, NEMA BU 1.1, IEC 61439-6, ISO 9001 and cUL for HP.
The guide asks four selection questions: target amperage range, how often the layout will change, the power density being designed for and future growth. T5 scales at the rack level with plug-in units, Series HP at the infrastructure level with larger backbone deployments. Some projects need both: Series HP can serve as the trunk feeding open-channel busway over the racks. The document is a product selection guide; it contains no cost or electrical sizing calculation.
Key points
- T5 open-channel: 250-1200 A (UL), 250-1250 A (IEC); plug-in units added or moved without downtime.
- Series HP enclosed: 630-6000 A (UL), 630-6300 A (IEC); custom-engineered bulk distribution.
- T5: M70 Critical Power Monitor at feed and branch-circuit level.
- Series HP: real-time temperature sensor and power monitoring.
- T5: standard indoor and IP54; Series-S for liquid-cooled environments.
- Series HP: IP42, IP54, IP55 standard; IP65 outdoor on request.
- T5 compression joints need no re-torquing.
- Series HP can trunk open-channel busway over the racks.
- Portfolio 100-6000 A, UL857 listed.
Using it in design
- Fix the amperage range first: T5 for rack distribution up to 1200 A, Series HP for bulk power up to 6000 A.
- Prefer open-channel where the layout will change often, because plug-in units move without downtime.
- In hyperscale or AI halls evaluate an HP backbone with T5 rack-level runs.
- Pick the IP rating by environment (indoor, IP54/55, outdoor IP65) and review Series-S for liquid-cooled areas.
- Carry the monitoring level (feed, branch circuit, temperature) into the DCIM and power metering architecture.
Who should read it
Electrical designers and project managers selecting data-centre power distribution and busway.
Document contents
- Introduction
- Open-channel T5 vs enclosed Series HP
- Where each solution fits
- Questions to ask before selecting a busway system
- Why data centers choose Starline
Publication details
- Authors
- Starline
- Publisher
- Starline
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.
Citation
Starline Data Center Busway Guide: Choosing the Right Busway for Your Application. Starline. https://starlinepower.com/sites/default/files/files/Starline_Data_Center_Busway_Selection_Guide.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.