Testing-adjusting-balancing of data centres
Original title Veri Merkezlerinde Test-Ayar-Dengeleme (TAD) (Testing-adjusting-balancing of data centres)
TMMOB Makina Mühendisleri Odası (MMO) · Işık Yücesoy
A TESKON 2025 seminar paper setting out the testing-adjusting-balancing sequence used on data-centre HVAC projects and the reported energy saving.
On this page
Overview
This paper by Işık Yücesoy was presented in the TAB Seminar at the 16th National Installation Engineering Congress (TESKON 2025, Izmir) and published in the proceedings of the Chamber of Mechanical Engineers (TMMOB MMO), p. 1456. It sets out the sequence a Turkish TAB practitioner uses on data-centre HVAC projects: baseline air and water measurements, balancing, determination of BMS set points, and post-TAB energy comparison.
In the introduction, data-centre energy use per 100,000 inhabitants is quoted as about 1 MW in Europe versus about 12 MW in the USA. The method section gives the steps: measure airflow, temperature and pressure per floor before TAB; analyse imbalances; balance air; measure water flow and differential pressure; balance water; set and load BMS set points; and re-measure and compute savings.
The equipment covered includes, on the air side, CRAH/CRAC units, adiabatic AHUs, fresh-air units and fan coils, and on the water side chillers, pumps and balancing valves. Instruments used are an anemometer, manometer, balometer (flow hood), differential-pressure meter, ultrasonic flow meter and humidity and temperature sensors. Both CAV and VAV air systems were treated, and TAB verified operating scenarios and room temperature, humidity and pressure targets.
As a result, the author reports that proper TAB on data centres yields 10-25% HVAC energy savings and that TAB reports become the operating handbook. As a limitation, the paper is short and rests on practitioner experience; it offers no detailed measurement data or independent verification.
Key points
- Data-centre energy use per 100,000 inhabitants is quoted as about 1 MW in Europe versus about 12 MW in the USA.
- TAB steps: measure, analyse imbalances, balance air, measure water flow and differential pressure, balance water, set BMS set points, re-measure and compute savings.
- Instruments used: anemometer, manometer, balometer, differential-pressure meter, ultrasonic flow meter, humidity and temperature sensors.
- Both CAV and VAV air systems were treated.
- TAB verified operating scenarios and room temperature, humidity and pressure targets.
- The reported outcome is a 10-25% energy efficiency improvement.
- TAB reports serve as an O&M handbook.
Using it in design
- Prepare a TAB schedule for each cooling unit and hydronic circuit covering design and measured airflow, water flow, differential pressure and setpoints.
- Flag designs without balancing valves or measurement points.
- In the energy model, allow a 'post-TAB' scenario instead of assuming design airflows are achieved.
Who should read it
Mechanical engineers planning and carrying out data centre HVAC commissioning and TAB work.
Related standards
- NEBB TAB Procedures
- ASHRAE Handbook – HVAC Systems and Equipment
Publication details
- Authors
- Işık Yücesoy
- Publisher
- TMMOB Makina Mühendisleri Odası (MMO)
- Year
- 2025
- Document number
- TESKON 2025 Bildiriler Kitabı, s. 1456
- Event
- 16. Ulusal Tesisat Mühendisliği Kongresi (TESKON 2025), İzmir - TAD Semineri
- Document language
- Turkish
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Document-language evidence reviewed 2026-11-16: https://mmoteskon.org/images/dosya/teskon-2025-bildiriler-kitabi-02.pdf
Citation
Işık Yücesoy (2025). Veri Merkezlerinde Test-Ayar-Dengeleme (TAD) (Testing-adjusting-balancing of data centres). TMMOB Makina Mühendisleri Odası (MMO). TESKON 2025 Bildiriler Kitabı, s. 1456. 16. Ulusal Tesisat Mühendisliği Kongresi (TESKON 2025), İzmir - TAD Semineri. https://mmoteskon.org/images/dosya/teskon-2025-bildiriler-kitabi-02.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.