Research paperFree to read2021

Comparison of Thermal Loads for a Sample Data Centre Using Different Software

Original title Örnek Bir Veri Merkezi için Isıl Yüklerin Farklı Yazılımlar Kullanılarak Karşılaştırılması

Marmara Üniversitesi, Fen Bilimleri Enstitüsü · Kaan Yılmazkarasu

A 2021 master's thesis at Marmara University comparing thermal load calculations for a data centre designed in Adana using Trace 700, Carrier HAP, Revit and Cype.

On this page

Overview

The thesis is Kaan Yılmazkarasu's master's work in Mechanical Engineering at the Marmara University Institute of Science. It aims to compare heat loss and gain programs widely used in HVAC design and to serve as a reference for later work. A three-dimensional model of a sample data centre building is built and thermal loads are calculated in Trace 700, Carrier hourly analysis (HAP), Revit and Cypetherm Loads.

The study defines data centres, researches the parameters that affect thermal load and looks for cause and effect in the results. The sample building is in Adana. The main finding is that loads from environmental conditions are small compared with equipment loads in data centres; even so, for spaces with large external wall and roof area the calculation method or software affects the results.

Software results differ for external wall and roof loads. The thesis recommends checking Turkish weather data from alternative sources before calculation, since it can vary between programs. Results are specific to the modelled building, and the thesis stresses that calculation accuracy is the first step in mechanical system efficiency work.

Key points

  1. Four programs are compared: Trace 700, Carrier hourly analysis (HAP), Revit and Cypetherm Loads.
  2. The sample building is a data centre designed in Adana and modelled in three dimensions.
  3. Loads from environmental conditions are small compared with equipment loads in data centres.
  4. For spaces with large external wall and roof area, the method or software affects the result.
  5. The programs give different results for external wall and roof loads.
  6. Because Turkish weather data can differ between programs, verification from alternative sources before calculation is recommended.

Using it in design

  • Do not base data hall thermal load on a single program's output; cross-check envelope (wall, roof) load with a second method.
  • Document the weather data source used in the calculation and verify it against an alternative source.
  • Knowing equipment load dominates, treat the software difference in envelope load as a separate uncertainty item when setting capacity margin.
  • For facilities with large roof and wall area (standalone building, containers), take more care in the envelope load calculation.

Who should read it

Mechanical engineers calculating data centre cooling loads and academics comparing load calculation software.

Publication details

Authors
Kaan Yılmazkarasu
Publisher
Marmara Üniversitesi, Fen Bilimleri Enstitüsü
Year
2021
Document number
Makine Mühendisliği yüksek lisans tezi, 2021
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. Üniversite metadata kaydı openAccess ve dil tur gösterir. YÖK tez numarası doğrulanamadı; kayıt üniversite açık tez kaynağı olarak sunulur. Tam metin resmi katalog PDF bağlantısından okundu.

Citation

Kaan Yılmazkarasu (2021). Örnek Bir Veri Merkezi için Isıl Yüklerin Farklı Yazılımlar Kullanılarak Karşılaştırılması. Marmara Üniversitesi, Fen Bilimleri Enstitüsü. Makine Mühendisliği yüksek lisans tezi, 2021. https://openaccess.marmara.edu.tr/entities/publication/0a3d0b2c-1654-4f1e-8751-7a57cff59ca1/full

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.