XVII TTMD International HVAC&R Technologies Symposium Proceedings: Artificial Intelligence in Buildings (2026)
Original title TTMD 2026 Symposium Proceedings: data-centre thermal AI papers
Türk Tesisat Mühendisleri Derneği · Koray Ömercan Saçlı, Ömer Yiğit Türkarslan et al.
The 132-page 2026 TTMD proceedings include two data centre papers: PCNN reconstruction of temperature fields from sparse sensors (mean absolute error 0.75 degrees C, about 1 ms inference) and a guide to AI methods.
On this page
Overview
The proceedings of the XVII International HVAC&R Technologies Symposium (ISBN 978-625-97915-3-1), published by the Turkish Society of HVAC and Sanitary Engineers (TTMD), have the theme Artificial Intelligence in Buildings. The book holds papers on natural ventilation opening layout optimisation, TPMS heat exchangers, bus HVAC, sensor-free AI-driven HVAC control, climate change and urban heat island, thermal energy storage, heat pump hot water and photovoltaic generation forecasting. The two papers relevant to a data centre designer come from Istanbul Technical University.
The first paper (Saçlı, Türkarslan, Onbaşıoğlu) addresses reconstructing high-resolution temperature fields in air-cooled data centres from sparse sensor measurements. A physics-constrained neural network (PCNN) builds heat transfer and conservation constraints into learning and is trained on CFD data. On unseen conditions the mean absolute error is 0.75 degrees C, while an unconstrained network underestimates peak temperature by 3.60 to 5.08 degrees C. Inference takes about 1 ms per field against about 60 minutes for CFD.
The second paper (Türkarslan, Saçlı, Onbaşıoğlu) is a tutorial guide for engineers wishing to integrate AI into data centre thermal management. It compares data-driven surrogates, physics-informed neural networks (PINNs) and PCNNs on data need, accuracy, physical consistency and implementation complexity, and gives practical guidance on data generation, model selection, training and validation. The limits are stated in the papers: the PCNN study is restricted to a single rack, steady state, a single horizontal plane and CFD-only validation, and needs retraining for different layouts. The guide paper is a review and presents no new measurement data.
Key points
- The PCNN study gives 0.75 degrees C mean absolute error on unseen conditions; the unconstrained neural network underestimates peak temperature by 3.60 to 5.08 degrees C.
- PCNN inference takes about 1 ms per field; CFD takes about 60 minutes.
- PCNN study conditions: velocity 0.5-1.5 m/s, inlet temperature 18-27 degrees C, single rack, 20 m x 5 m domain, steady state.
- Cooling accounts for 30-40% of data centre energy; the guide paper gives an average of 38%, mean PUE 2.13 (range 1.33-3.85).
- In Ni and Bai's review of 100 data centres, cooling reaches up to 61% in poorly optimised facilities.
- Data-driven surrogates offer inference of about 9 ms but have no physical guarantee.
- About 500 CFD cases are needed for a high-accuracy surrogate while 50 cases capture the general trend.
- Model selection: MLP or CNN with abundant data, PINN with sparse data and known equations, PCNN with partly known physics, hybrid where a first-principles model exists, reinforcement learning for continuous control.
- Genetic algorithm optimisation of CRAC settings is cited with 21-52% cooling energy savings.
Using it in design
- In temperature monitoring design, consider virtual sensing with sparse sensors, noting that physics-constrained models give a safer, slightly conservative estimate of peak temperature.
- For AI-assisted cooling control, generate CFD cases for training by factorial or Latin hypercube sampling and validate interpolation and extrapolation separately.
- Plan for retraining of models such as the PCNN whenever the layout changes.
- Apply a safety margin to critical predictions and retrain the model regularly with operational data.
- In liquid cooling and digital twin work, design the control strategy together with model predictive control.
Who should read it
Mechanical engineers and researchers who want to use AI for data centre thermal monitoring and cooling control.
Document contents
- Natural ventilation opening layout optimisation
- Transient thermal response of a TPMS heat exchanger
- CFD analysis of bus HVAC
- Sensor-free AI-driven HVAC control
- Climate change and urban heat island
- AI in thermal energy storage
- Heat pump hot water system
- Physics-constrained deep learning for data centre thermal management
- AI for data centre thermal management: methods and guidelines
- Photovoltaic generation forecasting
Publication details
- Authors
- Koray Ömercan Saçlı; Ömer Yiğit Türkarslan; Seyhan Onbaşıoğlu
- Publisher
- Türk Tesisat Mühendisleri Derneği
- Year
- 2026
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
132-page publisher PDF downloaded normally and selected source pages read; this closes the earlier fetch-size failure. One proceedings record covers both related papers to avoid duplicate URLs. No ASHRAE source text or translated ASHRAE presentation was summarized.
Citation
Koray Ömercan Saçlı; Ömer Yiğit Türkarslan; Seyhan Onbaşıoğlu (2026). TTMD 2026 Symposium Proceedings: data-centre thermal AI papers. Türk Tesisat Mühendisleri Derneği. https://www.ttmd.org.tr/upload/TTMD-2026-Symposium-Proceedings-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.