Industrial Products Catalogue (static transfer switch section)

Original title Endüstriyel Ürünler Kataloğu

Tunçmatik

The static transfer switch section of Tunçmatik's 2025 catalogue: 16-150 A single phase and 50-800 A three phase, under 4 ms synchronous transfer, over 99% efficiency and discrete cabinet size groups.

On this page

Overview

The Tunçmatik Industrial Energy Solutions catalogue covers frequency converters, UPS, rectifiers, inverters, static transfer switches (STS) and automatic and servo voltage regulators. This summary rests on the STS section (pp.13-16), which has two product groups: 16-150 A single phase and 50-800 A three phase. Single-phase models are 16, 32, 50, 63, 100 and 150 A; three-phase models are 50, 63, 100, 150, 200, 300, 400, 600 and 800 A.

Common technical data: input and output voltage is 110/127/208/220/230/240/265 VAC single phase and 200/227/380/400/415/440/460 VAC three phase; voltage range is +/-20% (transfer outside range); frequency is 50/60 Hz with a 45-65 Hz window; transfer time is under 4 ms with synchronous sources and 10 ms asynchronous; crest factor is 3:1 and efficiency over 99%. The transfer type is break before make, selectable as automatic, manual or remote, and the thyristor-controlled design lists back-feed protection, SCR failure alarm and a bypass interlock as internal protections.

The overload curve is 100-110% continuous, 110-125% for 10 minutes, 125-150% for 1 minute, 150-200% for 10 seconds and above 200% for 250 ms. General features include DSP control, a 2x16 or 4x20 LCD panel, RS232 and RS485 ModBus communication, adjustable dry-contact outputs, a 200-event history, a hot-swappable power module (1U and 2U models) and a 20-year design life. Options include SNMP, ModBus TCP/IP, a TFT touch panel, protection up to IP54 and thyristor fault detection (extra 4 relays).

Size and weight data fall into groups: single phase is 19 inch 1U for 16 and 32 A, 19 inch 2U for 50 and 63 A and 500 x 450 x 1000 mm for 100 and 150 A, with weights of 3, 6 and 8 kg. Three-phase freestanding cabinets are 500 x 450 x 1000, 600 x 600 x 1300, 750 x 700 x 1600 and 800 x 800 x 2100 mm with weights on request. Operation is 0-50 C, storage -10 to 70 C, humidity below 90%, with a 1% reduction per 100 m above 1000 m.

Key points

  1. Single-phase STS: 16, 32, 50, 63, 100, 150 A; three-phase STS: 50, 63, 100, 150, 200, 300, 400, 600, 800 A.
  2. Transfer time is under 4 ms with synchronous sources and 10 ms asynchronous; transfer type is break before make.
  3. Efficiency is over 99%; crest factor 3:1; voltage range +/-20%; frequency 45-65 Hz (adjustable).
  4. Overload: 100-110% continuous, 110-125% 10 min, 125-150% 1 min, 150-200% 10 s, above 200% 250 ms.
  5. Single-phase sizes: 19 inch 1U (16, 32 A), 19 inch 2U (50, 63 A), 500 x 450 x 1000 mm (100, 150 A); weights 3, 6, 8 kg.
  6. Three-phase freestanding cabinets: 500x450x1000, 600x600x1300, 750x700x1600, 800x800x2100 mm; weights on request.
  7. Operation 0-50 C; storage -10 to 70 C; humidity below 90%; 1% reduction per 100 m above 1000 m; noise 50-73 dBA.
  8. Communication RS232, RS485 ModBus, dry contacts; SNMP and ModBus TCP/IP optional; 200-event log; 20-year design life.

Using it in design

  • Tie the load current to one of the discrete single-phase (16-150 A) or three-phase (50-800 A) current classes; these are discrete models, not a continuous range.
  • Compare transfer time with load tolerance: under 4 ms applies to synchronous sources only, allow 10 ms for asynchronous sources, and account for the short gap of a break-before-make switch.
  • Match the overload curve (10 s at 150-200%, 250 ms above 200%) to the fault current and protection selectivity study.
  • For three-phase, add the freestanding cabinet size groups (500x450 to 800x800 mm footprints) to the electrical room layout and obtain drawings from the manufacturer for weight and cable entry.
  • Specify ModBus TCP/IP or SNMP and the dry-contact outputs for monitoring.

Who should read it

Electrical engineers designing dual-feed critical loads, teams writing STS specifications and buyers evaluating Turkish-market supply.

Document contents

  1. Introduction to Tunçmatik
  2. Frequency converter, UPS, rectifier, inverter
  3. Static transfer switch general features
  4. Options
  5. 16-150 A single-phase table
  6. 50-800 A three-phase table
  7. Voltage regulators (AVR, SVR)

Publication details

Authors
Tunçmatik
Publisher
Tunçmatik
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Tunçmatik Endüstriyel Ürünler Kataloğu. Tunçmatik. https://tuncmatik.com/wp-content/uploads/2025/04/Tuncmatik-Endustriyel-Urunler-Katalogu-TR.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.