Economizers in Tier Certified Data Centers (Keith Klesner)
Uptime Institute Journal · Keith Klesner
An Uptime Institute Journal article reviewing economizer types and how to apply them without breaking Tier III/IV objectives.
On this page
Overview
Keith Klesner's 2016 Uptime Institute Journal article reviews economizer types: direct air, direct air plus evaporative, indirect evaporative, pumped-refrigerant dry coolers and water-side economizers. It explains how to apply them without breaking Tier III/IV objectives. Uptime consultants observed that roughly one-third of new data centre designs include an economizer function.
Citing The Green Grid's 2011 survey, the article notes that 49% of large data centres used economizers and 24% were considering them. Direct-air rooftop economizer units report PUE around 1.30-1.60 and consume very little water. Outside-air units for mission-critical spaces must be able to run 100% recirculation during pollution or wildfire smoke events.
Commercial rooftop units adapted for 24x7 use need adequate filtration, full recirculation capability and well-tested control sequences across every operating mode. A DX unit with an air-side economizer can go from no power to full cooling in 120 seconds or less, with four operating modes; a chilled-water unit with wetted media may have nine modes, all of which must be tested.
Worst-case design conditions, not typical weather, govern Tier compliance. Most commercial HVAC ratings are at 95 F (35 C), and designs must be checked against the site's worst-case conditions. As a limitation, this is a journal article and offers no detailed calculation. Copyright belongs to Uptime Institute.
Key points
- Uptime consultants observed roughly one-third of new data centre designs include an economizer function.
- The Green Grid 2011 survey: 49% of large data centres used economizers and 24% were considering them.
- Direct-air rooftop economizer units report PUE around 1.30-1.60 and consume very little water.
- Outside-air units for mission-critical spaces must run 100% recirculation during pollution or wildfire smoke events.
- A DX unit with an air-side economizer can go from no power to full cooling in 120 s or less, with four operating modes.
- A chilled-water unit with wetted media may have nine modes, all of which must be tested.
- Most commercial HVAC ratings are at 35 C (95 F); designs must be checked against the site's worst-case conditions.
Using it in design
- Catalogue economizer units with operating modes, restart time and recirculation capability.
- For outside-air economizers, require filtration and a 100% recirculation mode.
- Check cooling capacity at the site's extreme design temperatures, not at the 35 C rating.
- Generate a commissioning test list covering every mode.
Who should read it
Mechanical designers selecting free cooling and economizers for Tier-targeted data centres.
Related standards
- ASHRAE 90.4
- Uptime Institute Tier Standard: Topology
Publication details
- Authors
- Keith Klesner
- Publisher
- Uptime Institute Journal
- Year
- 2016
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Keith Klesner (2016). Economizers in Tier Certified Data Centers (Keith Klesner). Uptime Institute Journal. https://journal.uptimeinstitute.com/implications-of-economizers-in-tier-certified-data-centers/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.