Liebert FDC User Manual
Vertiv
Vertiv's Liebert FDC is a UPS sub-distribution cabinet with up to four panelboards and 720 A continuous on a single input; the manual covers installation, operation and maintenance.
On this page
Overview
The Liebert FDC is a sub-distribution cabinet designed to provide additional distribution capacity downstream of a UPS. The unit can be furnished with one, two, three or four panelboards, and most units carry four. Two panelboards are accessed from the front and two from the rear. Panelboards are Square-D or GE with bolt-in or plug-in branch breakers. Each panelboard has 42 single-pole branch breaker positions, and the neutral busbar is sized for at least 1.73 times the panelboard full-load rating to carry the high harmonic neutral currents of single-phase non-linear loads.
The manual covers safety, unpacking and inspection, location, power and control wiring, operation, startup, maintenance and specifications. Input is three-phase four-wire plus ground within ±10% of nominal voltage, and output voltage equals input. Nominal voltages are 208/120 V, 380/220 V, 400/230 V and 415/240 V, plus 480/277 V at 60 Hz. Frequency is 50 or 60 Hz (±0.5 Hz). Current ratings are 100% continuous at all voltages and frequencies: 720 A on one input, 360 A per input on two inputs and 180 A per input on four.
Each panelboard is protected by a main breaker of 225 A (208 V, 380-415 V at 50 Hz) or 400 A (380-480 V, 60 Hz) with a short-circuit rating of 22 kA (208-240 V) or 35 kA (380-480 V, 60 Hz); an optional 65 kA main breaker exists for 380-480 V, 60 Hz. Monitoring is not standard; Current Monitoring Panel, Current Plus Monitoring and Liebert LDMF options are available. The document is a user manual and gives no sizing method.
Key points
- One to four panelboards; each has 42 single-pole branch breaker positions.
- Panelboards rated 225 A (208 V and 380-415 V, 50 Hz) or 400 A (380-480 V, 60 Hz).
- Short-circuit rating 22 kA (208-240 V), 35 kA (380-480 V, 60 Hz); optional 65 kA main breaker (not at 380-415 V, 50 Hz).
- Neutral busbar and wiring sized for at least 1.73 times the panelboard full-load rating.
- Continuous current: 720 A on one input, 360 A on two, 180 A on four; 100% continuous.
- Voltages: 208/120, 380/220, 400/230, 415/240 V; 480/277 V at 60 Hz; input ±10%, frequency ±0.5 Hz.
- Maximum heat output 3412 BTU/hr (1 kW); operation 0 to 40 °C, humidity 0 to 95%, altitude to 2000 m; noise below 45 dBA.
- Cabinet 597 x 1994 x 965 mm, NEMA 1 (IP10); floor loading under 1225 kg/m2; convection-cooled.
Using it in design
- Select the cabinet's current configuration (720 A single input or 2 x 360 A, 4 x 180 A) to match the UPS output breaker and cable size.
- Compare the panelboard short-circuit rating (22, 35 or 65 kA) with the expected fault current at the point of installation.
- With many single-phase non-linear loads, rely on the 1.73 times neutral busbar sizing.
- Include 1 kW of heat per unit in the room cooling load and keep the front, rear and (with the tie-breaker option) right-side service clearances.
- In seismic areas, specify the optional seismic floor stand and floor bolting.
Who should read it
Electrical engineers and site teams designing or operating distribution downstream of a UPS.
Document contents
- Important safety instructions
- Safety precautions
- Unpacking and inspections
- Locating the Liebert FDC
- Power and control wiring
- Introduction to Liebert FDC operation
- Equipment inspection and startup
- Operating instructions
- Maintenance
- Specifications
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Vertiv Liebert FDC User Manual. Vertiv. https://www.vertiv.com/4914f8/globalassets/products/critical-power/power-distribution/liebert-fdc-user-manual.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.