Technical guideFree to read2025

Vertiv 360AI High Density Reference Design #006: 2x 1.28 MW NVIDIA Blackwell DGX SuperPODs

Vertiv

A three-page datasheet for a 2.56 MW AI hall built from two 1.28 MW SuperPODs, using four-to-make-three UPS redundancy and N+1 cooling.

On this page

Overview

This three-page datasheet (2025) describes a complete 2.56 MW hall built from two 1.28 MW SuperPODs. Total IT load is 2 x 1,280 kW = 2,560 kW. The room holds 32 compute racks at 73 kW, 16 network/storage racks at 14 kW and 4 cabling racks, 52 in all. Heat splits about 78/22 between direct-to-chip liquid and perimeter air, which is 992 kW liquid and 288 kW air per pod.

On the power side it uses a four-to-make-three (distributed redundant, 4N/3) block: 4 IT UPS of 1,200 kVA serve both pods, so three of the four installed modules carry the load. Cooling is N+1 and the cooling equipment (CDUs and CRAHs) has its own 240 kVA 2N UPS. The distribution chain is dual utility and generator feeds, two 4,000 A main switchboards, four 600 kVA PDUs per pod, 400 A overhead busways (8 per pod) and, in the rack, six OCP DC power shelves of 33 kVA each.

The design rests on Vertiv's six principles: co-design power and cooling, align clusters to capacity blocks, weigh TCO against redundancy and blast radius, buffer workload surges, plan hybrid liquid/air, and design for future density. The document expects AI rack density to grow toward 500 kW per rack. It is a vendor datasheet; its values are indicative and should be recomputed.

Key points

  1. Total IT load 2,560 kW = 2 pods x 1,280 kW.
  2. 32 racks at 73 kW + 16 racks at 14 kW + 4 cabling racks (52 racks).
  3. Per pod 992 kW liquid (78%) / 288 kW air (22%).
  4. Power is 4-to-make-3 (4 x 1,200 kVA IT UPS for 2 pods); cooling is N+1.
  5. Cooling UPS is 240 kVA, 2N, feeding both CDUs and CRAHs.
  6. Busways 400 A (8 per pod), tap-off boxes 60 A (2 per rack per busway); 6 x 33 kVA OCP DC power shelves per rack.
  7. CDU rated 1,350 kW (one per half-pod, 4 total); perimeter CRAH in the 150 kW class.
  8. Vertiv expects AI rack density to grow toward 500 kW per rack.

Using it in design

  • Review the reference AI hall with 73 kW compute racks, 14 kW support racks, a 0.78 liquid fraction, 4N/3 power, N+1 cooling and 2N mechanical UPS.
  • Make it a rule that when liquid fraction is above zero, CDUs and pumps sit on UPS; flag designs that put CDUs on generator only.
  • Use the 4-to-make-3 block to show how 3 x 1,200 kVA of usable capacity comes from 4 installed modules, each loaded to at most 75% normally.

Who should read it

Electrical and mechanical engineers designing AI halls in the 1-3 MW range.

Related standards

  • Uptime Tier Standard: Topology
  • TIA-942
  • EN 50600-2-2
  • OCP Open Rack V3
  • ASHRAE TC9.9 Liquid Cooling Guidelines

Publication details

Authors
Vertiv
Publisher
Vertiv
Year
2025
Document number
AI Reference Design #006
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Vertiv (2025). Vertiv 360AI High Density Reference Design #006: 2x 1.28 MW NVIDIA Blackwell DGX SuperPODs. Vertiv. AI Reference Design #006. https://www.vertiv.com/49cfcc/globalassets/documents/ai-hub-reference-design/vertiv-360ai-reference-design-006.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.