Vertiv 360AI High Density Reference Designs #028/#030: 5 MW and 10 MW at up to 142 kW per rack

Vertiv

Two companion datasheets define a repeatable 2,496 kW "large pod" of 142 kW racks and build 5 MW and 10 MW AI facilities by multiplying it. They give a ready numerical template for planning AI campus capacity in building blocks rather than whole buildings.

On this page

Overview

Designs #028 and #030 are not two separate buildings but two scales of one unit. The large pod carries 2,496 kW of IT load: 16 compute racks at 142 kW plus 16 support racks at 14 kW. Design #028 stacks two pods for 4,992 kW across 64 racks, and #030 stacks four for 9,984 kW across 128 racks. The 10 MW design is therefore exactly double the 5 MW one, and adding capacity means adding pods rather than doing new engineering.

The cooling split per pod is stated explicitly: 1,936 kW (78%) goes to liquid and 560 kW (22%) to air. The liquid side is served by 2,300 kW-class CDUs (XDU2300), the air fraction by CRAHs, and heat rejection by free-cooling chillers. Cooling redundancy is N+1, while power uses a 4-to-make-3 arrangement: four units where three carry the load and one stands spare. That needs far less installed equipment than a 2N scheme.

On the electrical side the IT UPS modules are 2,000 kVA. The facility UPS, which backs the mechanical plant, is 300 kVA in #028 and 540 kVA in #030. Divided by IT load these come to roughly 6.0% (300/4,992) and 5.4% (540/9,984), a useful reference showing that at a 78% liquid fraction the mechanical UPS stays near one twentieth of the IT UPS capacity.

Being a vendor datasheet, the document gives configuration and counts rather than calculation rationale or cost, and it is copyright, so it can only be cited. Its value is a concrete example of which CDU, UPS and chiller classes work together at 142 kW per rack. It does not directly apply to densities above 142 kW per rack or to different redundancy targets.

Key points

  1. Large pod = 2,496 kW IT: 16 x 142 kW compute + 16 x 14 kW support racks
  2. Per-pod heat split: 1,936 kW liquid (78%), 560 kW air (22%)
  3. #030: 9,984 kW IT, 128 racks; #028: 4,992 kW IT, 64 racks
  4. IT UPS modules 2,000 kVA; facility UPS 300 kVA (#028) and 540 kVA (#030)
  5. CDU class 2,300 kW (XDU2300); power 4-to-make-3, cooling N+1
  6. Air fraction by CRAHs, heat rejection by free-cooling chillers
  7. Facility UPS is about 5.4-6.0% of IT load (300/4,992 and 540/9,984)

Using it in design

  • When phasing campus capacity in 2,496 kW pod blocks, scale UPS, CDU and chiller quantities with the number of blocks.
  • Use roughly 5-6% of IT load as a first check on mechanical (facility) UPS sizing: 300 kVA at 5 MW, 540 kVA at 10 MW.
  • For 142 kW rack designs take the liquid/air split as 78/22 and size room air cooling for the 560 kW air share.
  • Compare the four-to-make-three power arrangement with 2N and calculate the equipment-count difference.

Who should read it

Design engineers and investment decision makers planning electrical and cooling capacity for AI campuses in modular blocks.

Related standards

  • Uptime Tier Standard: Topology
  • ASHRAE TC9.9 Liquid Cooling Guidelines

Publication details

Authors
Vertiv
Publisher
Vertiv
Year
2025
Document number
AI Reference Design #030 (with #028)
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Vertiv (2025). Vertiv 360AI High Density Reference Designs #028/#030: 5 MW and 10 MW at up to 142 kW per rack. Vertiv. AI Reference Design #030 (with #028). https://www.vertiv.com/4939b8/globalassets/campaigns/ai-hub/vertiv-reference-design-030-ds-en-na-sl-80248-web.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.