Technical guideFree to read2018

High-voltage DC distribution is key to increased system efficiency and renewable energy opportunities

Vicor

This 7-page Vicor white paper (Rev 1.2, October 2018) argues for moving data-centre and telecom facilities to 380 V nominal (400 V peak) DC distribution. The four conversion stages of the conventional AC architecture fall to two, and the paper cites France Telecom and China Mobile work estimating savings of 8 to 10%.

On this page

Overview

The paper frames the pressure for energy efficiency with the EU 20-20-20 targets and demand growth of 5 to 10% a year in data centres. It argues that local improvements within the existing AC-DC chain yield only a few percentage points at system scale, so a different structure deserves attention: high-voltage DC distribution inside the building. The advantages of DC are listed: no source synchronisation, no phase balancing or harmonic issues, backup sources such as batteries and flywheels are inherently DC, and server and telecom loads already run on DC.

The topology comparison is the core of the paper. In a typical data centre the incoming AC is converted to DC inside the UPS, back to AC, to DC again in the power supply and finally to the processor rails: four major stages. A 48 V DC telecom system has two stages but carries high current at low voltage. The 380 V DC architecture also has two: the mains is rectified to 380 V DC, the battery connects directly to that bus, and local DC-DC converters produce the final voltages. Lower current means less copper, and longer feasible distances give flexibility in placing equipment.

On the conversion side, Vicor describes two building blocks. The Sine Amplitude Converter (BCM bus converter) is isolated, unregulated and fixed-ratio: with K = 1/8 it produces 50 V from a 400 V input and 47.5 V from 380 V, and soft switching above 1 MHz gives it more than 96% efficiency and a power density of 70 W/cm³. The second block is a zero-voltage-switching buck-boost regulator with 97% efficiency. Together they hold a 48 V ± 5% output across the 260 to 400 V normal service range defined by ETSI, with the regulator bypassed around 380 V.

The paper sketches the migration in three steps: today's rectification from AC to 48 V DC, a transition phase in which a 380 V DC PDU serves 380 V, 48 V and AC outputs side by side, and a final state in which 380 V goes straight to the loads. A working 400 V DC demonstration built by Emerson, Vicor, Anderson and Fujitsu powered an Intel VR12 processor, a LAN switch, a 1U server, a PC and a monitor, and converting 48 V directly to 1 V without an intermediate step gave about 5% higher efficiency than the traditional route. The document is written from a manufacturer's standpoint and does not go into protection, fault-current interruption or earthing.

Key points

  1. The proposed distribution voltage is 380 V DC nominal, 400 V peak; the battery connects directly to the bus at the same voltage.
  2. A typical AC data-centre chain has four major conversion stages; the 380 V DC architecture has two.
  3. Work by France Telecom and China Mobile estimates savings of 8 to 10% from moving to DC distribution.
  4. Per ETSI, the normal service range is 260 to 400 V; 400 to 410 V and 0 to 260 V are abnormal ranges.
  5. A bus converter with K = 1/8 produces 50 V from 400 V and 47.5 V from 380 V, at more than 96% efficiency and 70 W/cm³ power density.
  6. A bus converter measuring 3.25 × 2.2 × 0.67 cm delivers up to 330 W; the buck-boost regulator is 97% efficient.
  7. Standards and specification work: ITU L.1200, ETSI EN 300 132-3-1, IEC, IEEE, NTT and the DCG+C consortium.
  8. In the 400 V DC demonstration, direct conversion from 48 V to 1 V was about 5% more efficient than the traditional approach.

Using it in design

  • When assessing 380 V DC distribution, compare the multiplied efficiency of the four AC stages with the two-stage DC chain and test the 8 to 10% savings claim against your own load profile.
  • Size the battery string for direct connection to the 380 V bus and keep the end-of-discharge voltage above 260 V, the lower limit of the ETSI normal service range.
  • Specify the input range of IT equipment power supplies against the 260 to 400 V normal band and the 400 to 410 V abnormal band.
  • Plan a transition architecture to keep existing 48 V or AC-input equipment: a 380 V DC PDU, 380 V to 48 V bus converters and, where needed, DC-AC modules.
  • Calculate cable and busbar cross-sections by comparing the 48 V and 380 V currents for the same power, and base DC protection, connector and fuse selection on ETSI EN 300 132-3-1 and ITU L.1200.

Who should read it

Data-centre and telecom electrical designers assessing DC distribution architectures, power-electronics engineers and managers deciding on energy-efficiency investments.

Document contents

  1. Introduction: a transition to 400VDC
  2. Why use DC at all?
  3. Topology makes a difference
  4. Getting down to single volts
  5. A tangible demonstration
  6. The challenges and opportunities ahead

Publication details

Authors
Vicor
Publisher
Vicor
Year
2018
Document number
Rev 1.2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.

Citation

Vicor (2018). High-voltage DC distribution is key to increased system efficiency and renewable energy opportunities. Vicor. Rev 1.2. https://www.vicorpower.com/files/live/sites/vicor/files/documents/whitepapers/wp-High-voltage-DC-Distribution.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.