Wide-Area Power System Oscillations from Large-Scale AI Workloads
arXiv preprint (University of Texas at Austin; formatted for IEEE Transactions on Power Systems) · Min-Seung Ko, Hao Zhu
A stochastic power-profile model for AI-centric datacenters represents training and fine-tuning jobs as periodic compute/communicate cycles with random cycle length and phase power; aggregated profiles are injected into WECC 179-bus and NPCC 140-bus dynamic models to study forced and wide-area oscillations.
CC BY 4.0 — share with attribution
On this page
Overview
The work develops a new dynamic power-profiling approach for AI-centric datacenter loads and analyses their impact on grid operations, particularly their potential to induce wide-area oscillations. It characterises the periodic stochastic power fluctuations inherent to large-scale AI workloads during training and fine-tuning, driven by GPU architecture. These sustained, large power fluctuations, unlike conventional load ramping, act as persistent forcing inputs capable of interacting with and amplifying local and inter-area oscillation modes.
Training model parameters: baseline fluctuation frequency U(0.5, 1.5) Hz, cycle-duration sigma 0.1, compute-phase share 55%-80% of each cycle, and an average 30% demand reduction in synchronisation phases (mu_Delta = 0.3). The fine-tuning model uses a dominant frequency U(0.3, 0.7) Hz and compute fraction 0.7-0.9. Baseline WECC case: 60.8 GW base load, system inertia 2.7, 7 datacenters of 1 GW each (11.5% penetration), fluctuation band 0.5-1.5 Hz, with 80% of each site's capacity modelled as steady load and 20% as fluctuating AI load.
Eigen-analysis of the WECC system found unstable modes at 0.852, 1.06 and 1.44 Hz; higher-penetration scenarios of 23% and 34.5% were also simulated. Across 20 stochastic runs the response consistently shows a dominant oscillation around 1 Hz, and narrower workload frequency ranges give stronger, more repeatable oscillations. Direct suppression of datacenter load fluctuation is substantially more effective than indirect system-level measures such as added damping.
The finding is that AI datacenters behave as persistent, frequency-selective forcing sources rather than ramping loads, and oscillation severity depends on fluctuation frequency band, single-site size, siting, system inertia and penetration. Limits: the stochastic model parameters are assumptions, not from a measured single-facility profile; the simulation is on two test systems. It is a preprint.
Key points
- Non-computational datacenter components (cooling, networking, storage) are cited as typically 40-50% of total consumption, and AI workloads as roughly 10-20% of datacenter electricity today.
- Training model parameters: baseline fluctuation frequency U(0.5, 1.5) Hz, cycle-duration sigma 0.1, compute-phase share 55%-80% of each cycle, and an average 30% demand reduction in synchronisation phases (mu_Delta = 0.3).
- The fine-tuning model uses a dominant frequency U(0.3, 0.7) Hz and compute fraction 0.7-0.9.
- Baseline WECC case: 60.8 GW base load, system inertia 2.7, 7 datacenters of 1 GW each (11.5% penetration), fluctuation band 0.5-1.5 Hz; 80% of each site as steady load and 20% as fluctuating AI load.
- Eigen-analysis of the WECC system found unstable modes at 0.852, 1.06 and 1.44 Hz; higher-penetration scenarios of 23% and 34.5% were also simulated.
- Across 20 stochastic runs the response consistently shows a dominant oscillation around 1 Hz; narrower workload frequency ranges give stronger, more repeatable oscillations.
- Direct suppression of datacenter load fluctuation is substantially more effective than indirect system-level measures such as added damping.
Using it in design
- Model AI data-centre load as a persistent periodic forcing (0.3-1.5 Hz band, about 20% of peak fluctuating) rather than a ramp, and add oscillation analysis to the grid-interconnection study.
- Suppress fluctuation on site (UPS, battery, workload smoothing); direct suppression is far more effective than system-level damping.
- Treat single-site size, siting and penetration (11.5% to 34.5%) as limiting factors at the point of connection.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Grid planners and data-centre designers assessing the grid-stability impact and interconnection conditions of large AI data centres.
Document contents
- Introduction
- AI Workload Power Profile Modeling (A. Training Workload Modeling, B. Fine-tuning Workload Modeling, C. Aggregated AI Workloads for Datacenter Power Profiling)
- Simulation Results (A. Simulation Settings, WECC 179-bus and NPCC 140-bus systems, eigen-analysis, penetration and siting sensitivity)
- Oscillation Implications of AI Datacenter Deployment
- Conclusion
Read the document
ai-workload-wide-area-oscillations-2025.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Min-Seung Ko; Hao Zhu
- Publisher
- arXiv preprint (University of Texas at Austin; formatted for IEEE Transactions on Power Systems)
- Year
- 2025
- Document number
- arXiv:2508.16457
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- arxiv.org
Original licence note
arXiv record licence is http://creativecommons.org/licenses/by/4.0/ (checked via arXiv OAI-PMH, v2)
Citation
Min-Seung Ko; Hao Zhu (2025). Wide-Area Power System Oscillations from Large-Scale AI Workloads. arXiv preprint (University of Texas at Austin; formatted for IEEE Transactions on Power Systems). arXiv:2508.16457. https://doi.org/10.48550/arXiv.2508.16457
Events on this subject
- Electricity Eurasia 2027
- ELECO 2026 Elektrik-Elektronik ve Biyomedikal Mühendisliği Konferansı
- 7x24 Exchange Spring Conference
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.