A Bidirectional Gated Recurrent Unit Model for PUE Prediction in Data Centers
arXiv preprint (National University of Singapore) · Dhivya Dharshini Kannan, Anupam Trivedi et al.
A preprint developing a BiGRU neural network to predict data centre PUE and comparing it with a standard GRU; because the data are simulated, the very high accuracy is not field validation.
On this page
Overview
The study develops a BiGRU neural network to predict data centre PUE and compares it with a standard GRU. Training data come from a one-year EnergyPlus simulation of the example data centre model with Singapore weather at 10-minute steps: 52,560 samples with 117 features. The data are therefore simulator output, not metered field data.
Feature selection uses recursive feature elimination with cross-validation (RFECV) with XGBoost, choosing subsets of 21-43 variables covering outdoor conditions, IT power, UPS and CRAC/cooling-coil variables, with hyperparameters tuned for each set. RFECV selected sets of {21, 28, 29, 32, 33, 43} features with the minimum MSE. The 21 features include outdoor dry-bulb, dew-point and wet-bulb temperature, ITE CPU, fan and UPS electric power, air volume flow, CRAC total power, net sensible capacity and SCOP, and cooling-coil power and outlet temperature.
The BiGRU with 21 features gave the lowest error: MAE 0.00038 (MSE 5.6342e-7, R2 0.99673), while the GRU performed best with 28 features (MAE 0.0004181). The paper recalls that Google's neural-network PUE model achieved an MAE of 0.004 +/- 0.005 for a PUE of 1.1, and that Singapore guidance requires new data centres to have a PUE of 1.3 or below at 100 percent IT load.
The key limit is that the data are simulated: the very high accuracy reflects the regularity of the simulator, not field validation. The model is a surrogate of the simulator and should be validated against metered data before being used for guarantees. The document is a preprint, not a peer-reviewed publication. ISO/IEC 30134-2 is named as the related standard.
Key points
- Dataset: one-year EnergyPlus simulation with 2009 Singapore weather at 10-minute intervals, giving 52,560 samples with 117 features.
- RFECV selected feature sets of {21, 28, 29, 32, 33, 43} features with the minimum MSE.
- The 21 features include outdoor dry-bulb, dew-point and wet-bulb temperature, IT CPU, fan and UPS power, air flow, CRAC power, net sensible capacity and SCOP, and coil power and outlet temperature.
- BiGRU with 21 features achieved the lowest MAE of 0.00038 (MSE 5.6342e-7, R2 0.99673); GRU did best with 28 features (MAE 0.0004181).
- Cited Singapore guidance requires new data centres to have a PUE of 1.3 or below at 100 percent IT load.
- Prior work cited: Google's neural-network PUE model achieved an MAE of 0.004 +/- 0.005 for a PUE of 1.1.
Using it in design
- For an operations or digital-twin module, use the feature list as a practical minimum sensor set for PUE prediction: outdoor dry/wet-bulb, IT power, UPS power, CRAC power/capacity/SCOP, coil temperatures and airflow.
- Treat ML PUE models trained on simulation as surrogates of the simulator and validate against metered data before using them for guarantees.
- Keep regional PUE limits (e.g. Singapore 1.3 at full IT load) in the metrics/compliance catalogue.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Operations engineers and data scientists building digital twins and energy forecasting.
Related standards
- ISO/IEC 30134-2
Publication details
- Authors
- Dhivya Dharshini Kannan; Anupam Trivedi; Dipti Srinivasan
- Publisher
- arXiv preprint (National University of Singapore)
- Year
- 2025
- Document number
- arXiv:2512.20161
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- arXiv distribution permission — reuse conditions remain with the rights holder
Original licence note
arXiv default non-exclusive distribution licence; citation only
Citation
Dhivya Dharshini Kannan; Anupam Trivedi; Dipti Srinivasan (2025). A Bidirectional Gated Recurrent Unit Model for PUE Prediction in Data Centers. arXiv preprint (National University of Singapore). arXiv:2512.20161. https://doi.org/10.48550/arXiv.2512.20161
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.