ABM Technology and Battery Testing in Eaton UPS Products
Eaton
Describes an opportunistic charging scheme for VRLA UPS batteries as an alternative to continuous float charging, which accelerates positive-grid corrosion.
On this page
Overview
VRLA batteries marketed with a 10-year design life are replaced every 4-5 years on average in UPS service and can be about 30% of UPS cost. ABM addresses this with a three-stage cycle: charge, float with an automatic battery test, and a long rest with the charger off and open-circuit voltage monitored.
Charge mode uses constant voltage at float level with current above 0.1C, up to a 100-hour limit, then 48 h of float with an automatic battery test after 24 h. Rest mode turns the charger off for about 28 days; charging restarts after an outage longer than 15 s, low open-circuit voltage, timer expiry or battery replacement.
The battery test discharges at about 15% load for up to 6 minutes then at 50% load for 45 s, and compares voltage to a load-dependent end-of-life threshold. On day 27 of rest, a 15-minute battery still provides all but about 30 seconds of its runtime. Calculated service life at 25 C increases by about six years versus float charging.
The paper presents accelerated-life and long-term test evidence, and states when to disable the scheme: with wet-cell batteries.
Key points
- VRLA batteries marketed with a 10-year design life are replaced every 4-5 years on average in UPS service and can be about 30% of UPS cost.
- Charge mode: constant voltage at float level, current above 0.1C, up to 100 hours; then 48 h float with an automatic test after 24 h.
- Rest mode turns the charger off for about 28 days; an outage over 15 s, low open-circuit voltage, timer expiry or battery replacement restarts charging.
- The test discharges at ~15% load for up to 6 minutes then 50% load for 45 s against a load-dependent end-of-life threshold.
- On day 27 of rest a 15-minute battery still gives all but about 30 seconds of runtime.
- Calculated service life at 25 C rises by about six years versus float charging.
Using it in design
- Add charging method (float, opportunistic/ABM, Li-ion BMS) and automatic battery test capability to the battery/UPS catalogue.
- Default the VRLA replacement interval to 4-5 years unless managed charging is specified.
- Warn if opportunistic charging is applied to flooded or wet-cell batteries.
- Include a 2-3% runtime derating at the end of the rest period in the autonomy margin.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
UPS designers and facility operators planning VRLA battery life and maintenance.
Related standards
- IEEE 1188
- IEC 60896-21
Publication details
- Authors
- Eaton
- Publisher
- Eaton
- Year
- 2018
- Document number
- WP09-18 (AP162001EN)
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Eaton (2018). ABM Technology and Battery Testing in Eaton UPS Products. Eaton. WP09-18 (AP162001EN). https://itpccit.com/wp-content/uploads/2022/02/Eaton-ABM-White-Paper-AP162001EN.pdf
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.