A Review of Lithium-Ion Battery Fire Suppression
Energies (MDPI AG) · Mohammadmahdi Ghiji, Vasily Novozhilov et al.
This review covers lithium-ion cell construction, the abuse modes that trigger thermal runaway, safety measures at cell, module, pack and compartment level, and extinguishing agents; its central argument is that many agents can knock down flames but only sustained cooling stops runaway.
CC BY 4.0 — share with attribution
On this page
Overview
The review asks how the fire risk of Li-ion batteries (LiBs) can be reduced and which agent is actually effective against these fires. The method is a literature survey: cathode, anode, separator and electrolyte components, battery systems, thermal runaway and fire, safety at cell, module/pack and compartment level, fire detection and extinguishing agents (water, foam, powder, CO2, halon-based) and LiB suppression studies are covered in turn, followed by detail on water-mist characterisation, nozzle characteristics and extinguishing mechanisms.
In thermal abuse, internal temperatures of 90-120 °C cause exothermic SEI decomposition, and above 200 °C the hydrocarbon electrolyte can decompose and release heat. Heat detectors are reported as the slowest way to detect LiB fires and are not recommended; combined smoke-heat detectors are reported as the fastest and are recommended. LiB fires straddle classes A, B and E, and the authors stress that cooling cells in a large pack to stop propagation matters more than extinguishing a single cell's flames.
On agents: halon-based agents can extinguish a LiB fire but cannot stop the internal temperature rise or prevent re-ignition. HFC-227ea outperformed CO2 and powder in cited tests, and Novec 1230 was also found effective. In DNV-GL tests, F500, FireIce, PyroCool foam, Stat-X aerosol and sprinklers all extinguished the fires, but the water-based systems cooled better over time. When water mist vaporises its volume grows by more than three orders of magnitude, diluting oxygen and fuel vapour, and a cited study found mist cut radiant heat flux to enclosure walls by 70%.
The conclusion is that water mist with additives and surfactants, or combined with a gaseous agent, is the most promising extinguishing and cooling method for LiBs. Limits: as a review it has no new measurements, and the cited tests used different cell types, scales and set-ups and cannot be compared directly.
Key points
- Thermal abuse: internal temperatures of 90-120 °C cause exothermic SEI decomposition, and above 200 °C the hydrocarbon electrolyte can decompose and release heat.
- Heat detectors are reported as the slowest way to detect LiB fires and are not recommended; combined smoke-heat detectors are reported as the fastest and are recommended.
- LiB fires straddle classes A, B and E; cooling cells in a large pack to stop propagation matters more than extinguishing a single cell's flames.
- Halon-based agents can extinguish a LiB fire but cannot stop the internal temperature rise or prevent re-ignition; HFC-227ea outperformed CO2 and powder in cited tests and Novec 1230 was also effective.
- In DNV-GL tests, F500, FireIce, PyroCool foam, Stat-X aerosol and sprinklers all extinguished the fires, but the water-based systems cooled better over time.
- When water mist vaporises, its volume grows by more than three orders of magnitude, diluting oxygen and fuel vapour; a cited study found mist cut radiant heat flux to enclosure walls by 70%.
- The authors conclude that water mist with additives and surfactants, or combined with a gaseous agent, is the most promising extinguishing and cooling method for LiBs.
Using it in design
- In Li-ion UPS and BESS areas, set up detection with combined smoke-heat detectors; do not rely on heat detectors alone.
- Define the suppression design goal as cooling neighbouring cells (stopping propagation and re-ignition) as well as knocking down flames; do not treat a gaseous agent alone as sufficient.
- Evaluate water mist, or water mist plus a gaseous agent, with its nozzle and droplet-size characteristics among the suppression alternatives for BESS and battery rooms.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Bring standards pre-checks into your project
Review model-based TS EN 50600 and Tier pre-checks, missing inputs and items requiring engineering review in SoSo CAD.
Request a demo
Who should read it
Fire-safety engineers designing fire detection and suppression for Li-ion battery rooms, UPS and BESS.
Document contents
- 1. Introduction
- 2. Lithium-Ion Battery Components (cathode, anode, separator, electrolyte)
- 3. Lithium-Ion Battery Systems
- 4. Thermal Runaway and Fire
- 5. Fire Protection Techniques (safety at cell, module and pack, and compartment level)
- 6. Lithium-Ion Battery Fire Detection and Suppression (types of extinguishants: water, foam, powder, CO2, halon-based; LiB suppression studies; water mist characterisation: droplet size distribution, spray cone angle, velocity, mass flow rate, momentum; nozzle characteristics; mechanisms of extinguishment; water mist system characteristics)
- 7. Summary and Outlook
Related standards
- NFPA 855
- NFPA 750
- NFPA 2001
- UL 9540A
Read the document
li-ion-battery-fire-suppression-review-2020.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Mohammadmahdi Ghiji; Vasily Novozhilov; Khalid Moinuddin; Paul Joseph; Ian Burch; Brigitta Suendermann; Grant Gamble
- Publisher
- Energies (MDPI AG)
- Year
- 2020
- Volume
- 13
- Issue
- 19
- Pages
- 5117
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.30 states the article is distributed under the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Citation
Mohammadmahdi Ghiji; Vasily Novozhilov; Khalid Moinuddin; Paul Joseph; Ian Burch; Brigitta Suendermann; Grant Gamble (2020). A Review of Lithium-Ion Battery Fire Suppression. Energies (MDPI AG). 13(19), 5117. https://doi.org/10.3390/en13195117
Events on this subject
- Electricity Eurasia 2027
- The smarter E Europe (Intersolar Europe, ees Europe, Power2Drive, EM-Power)
- ISAF International 2027
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.