Research paperPDF2026

Experimental Study on Fire Suppression of Lithium-Ion Battery Module with Different Extinguishing Agents in Confined Space

Batteries (MDPI AG) · Yanbo Jia, Chaohui Shi et al.

Packs of three 314 Ah LFP cells were driven into thermal runaway by an 800 W heater inside a confined battery pack on a full-scale platform with a 10 MW calorimeter, with no agent, condensed aerosol, heptafluoropropane (HFC-227ea) and perfluorohexanone (FK-5-1-12).

CC BY 4.0 — share with attribution

On this page

Overview

The study asks how different extinguishing agents perform against Li-ion battery fires in real confined spaces. Three 3.2 V/314 Ah LFP storage cells were driven into thermal runaway with an 800 W heater (per GB 36276, switched off at safety venting), with vent gas ignited. Four cases were compared: no agent, condensed aerosol (30 g, rated to protect 0.3 m³), heptafluoropropane (3 kg) and perfluorohexanone (3 kg), all delivered through pipe-fed nozzles with a coefficient of 2.0 on 12 mm pipe.

Without suppression, peak HRR reached 69.09 kW and total heat release was 8.05 MJ, with multiple deflagrations after venting in the confined space. Heptafluoropropane extinguished the flames in 12 s and perfluorohexanone in 20 s; the aerosol caused rapid flame contraction but could not prevent re-ignition. Front-surface battery temperature dropped by 147 °C with heptafluoropropane and by 230 °C with perfluorohexanone, whose liquid adhesion gave sustained cooling.

Voltage response lagged behind gas and smoke release, so the authors judge characteristic-gas monitoring more time-sensitive than voltage monitoring for early warning. All three agents showed limited ability to block heat transfer between adjacent cells, so combining fast flame knock-down with long-lasting cooling, coordinated with ventilation and explosion venting, is recommended.

Limits: one three-cell pack, one agent quantity and one configuration; results are not validated for larger modules or other confined volumes. Perfluorohexanone stands out for flame extinguishment, cooling and suppression of thermal propagation, while heptafluoropropane suits a fast-response role.

Key points

  1. Test cells were three 3.2 V/314 Ah LFP storage cells; thermal runaway was triggered with an 800 W heater (per GB 36276) switched off at safety venting.
  2. Agent quantities: aerosol 30 g (rated to protect 0.3 m³), heptafluoropropane 3 kg and perfluorohexanone 3 kg, through nozzles with a coefficient of 2.0 on 12 mm pipe.
  3. Without suppression, peak HRR reached 69.09 kW and total heat release was 8.05 MJ, with multiple deflagrations after venting in the confined space.
  4. Heptafluoropropane extinguished the flames in 12 s and perfluorohexanone in 20 s; the aerosol caused rapid flame contraction but could not prevent re-ignition.
  5. Front-surface battery temperature dropped by 147 °C with heptafluoropropane and by 230 °C with perfluorohexanone, whose liquid adhesion gave sustained cooling.
  6. Voltage response lagged behind gas and smoke release, so the authors judge characteristic-gas monitoring more time-sensitive for early warning.
  7. All three agents showed limited ability to block heat transfer between adjacent cells.

Using it in design

  • For confined battery packs and cabinets, evaluate a fast flame-knockdown agent (such as heptafluoropropane) together with an agent or approach giving long-lasting cooling (such as perfluorohexanone); no single agent stopped heat transfer to neighbouring cells.
  • Make characteristic (vent) gas detection the primary early-warning trigger rather than voltage; voltage response lagged gas and smoke release.
  • Coordinate agent design with ventilation and explosion venting; multiple deflagrations were seen after venting in the confined space.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Bring standards pre-checks into your project

Review model-based TS EN 50600 and Tier pre-checks, missing inputs and items requiring engineering review in SoSo CAD.

Request a demo
Selected rule packs and findings in the SoSo CAD standards panel

Who should read it

Fire-safety engineers choosing extinguishing agents for confined battery packs, cabinets and BESS.

Document contents

  1. 1. Introduction
  2. 2. Experiment (2.1 Experimental Platform, 2.2 Experimental Setup, 2.3 Thermocouple Placement)
  3. 3. Results (3.1 Open Flame Suppression Capability, 3.2 Cooling Capacity, 3.3 Suppression Capability for Thermal Diffusion)
  4. 4. Conclusions

Related standards

  • NFPA 2001
  • NFPA 855
  • GB 36276
  • UL 9540A

Read the document

li-ion-module-suppression-agents-confined-space-2026.pdf

PDF · 4.2 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Yanbo Jia; Chaohui Shi; Lei Zhang; An Tao; Sen Hu; Huang Li
Publisher
Batteries (MDPI AG)
Year
2026
Volume
12
Issue
7
Pages
229
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

Citation

Yanbo Jia; Chaohui Shi; Lei Zhang; An Tao; Sen Hu; Huang Li (2026). Experimental Study on Fire Suppression of Lithium-Ion Battery Module with Different Extinguishing Agents in Confined Space. Batteries (MDPI AG). 12(7), 229. https://doi.org/10.3390/batteries12070229

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.