Technical guideFree to read2026

High-Performance Computing Data Center Warm-Water Liquid Cooling (ESIF)

National Laboratory of the Rockies (formerly NREL) · National Laboratory of the Rockies

A description of warm-water liquid cooling at the ESIF HPC data centre: high rack densities, warm supply water that cooling towers can produce year-round in a semi-arid climate, and return water warm enough to heat the building.

On this page

Overview

This page presents the warm-water liquid cooling used in the ESIF high-performance computing (HPC) data centre of the National Laboratory of the Rockies (formerly NREL). It stresses three features of the approach: high rack densities, warm supply water that cooling towers can produce year-round in a semi-arid climate, and return water warm enough to heat the building. The page was last updated on February 17, 2026.

The figures on the page are as follows: rack densities of 60 kW per rack or more are achievable with warm-water liquid cooling. Supply water can be up to 75 F and the design wet-bulb is 60 F. HPC systems heat the water to around 100 F for building heating; the building needs at least 95 F. This is a concrete example of waste-heat reuse.

As a limit, this is the showcase page of a single facility; it provides no detailed measurement data, cost or general design method. The results are specific to ESIF's semi-arid climate and HPC load profile, and the same conditions may not apply directly elsewhere. It remains valuable as a reference case showing that warm-water cooling can combine with chiller-free operation and heat recovery.

Key points

  1. Rack densities of 60 kW per rack or more are achievable with warm-water liquid cooling.
  2. Supply water up to 75 F; design wet-bulb is 60 F.
  3. HPC systems heat the water to around 100 F for building heating; the building needs at least 95 F.
  4. Cooling towers can produce the warm supply water year-round in a semi-arid climate.
  5. Page last updated February 17, 2026.

Using it in design

  • Use as a reference case for warm-water DLC presets (supply about 24 C, return about 38 C).
  • Check chiller-free operation against design wet-bulb plus tower approach.
  • Model reuse of the return water for building heating as a waste-heat recovery option.
  • Verify the supply temperature against the ASHRAE W classes.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling engineers designing liquid cooling and waste-heat recovery, and decision makers planning HPC facilities.

Related standards

  • ASHRAE W-classes (Liquid Cooling Guidelines)

Publication details

Authors
National Laboratory of the Rockies
Publisher
National Laboratory of the Rockies (formerly NREL)
Year
2026
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document
Original licence note

NREL/NLR (contractor-operated DOE laboratory) web page; not US-Gov public domain. Cited only.

Citation

National Laboratory of the Rockies (2026). High-Performance Computing Data Center Warm-Water Liquid Cooling (ESIF). National Laboratory of the Rockies (formerly NREL). https://www.nlr.gov/computational-science/warm-water-liquid-cooling

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.