Immersion Requirements Rev 2.0, First Amended (Revision 2.10, August 18, 2023)
Open Compute Project Foundation · Rolf Brink, Jessica Gullbrand et al.
OCP's requirements document for single-phase and two-phase immersion cooling solutions (tanks and enclosed chassis) gathers safety, minimum dielectric-fluid properties, specification-sheet metrics and facility-interface rules into one qualification checklist.
CC BY-SA 4.0 — share with attribution under the same licence
On this page
Overview
The document is the checklist used to qualify OCP immersion contributions; it was published as Rev 1.00 (20 May 2019), Rev 2.00 (21 January 2022) and the amended Rev 2.10 (18 August 2023). Requirements are tagged Specification Requirements (SR, for the solution vendor), Customer Requirements (CR, for owners and operators) and optional requirements (OR). The qualification process requires a filled-in checklist and presentation to be shared at least one week before the review, with a quorum of at least 5 votes. Among the Rev 2.10 changes, the minimum auto-ignition point rose from 250 C to 300 C.
The quality and safety chapter requires that horizontal busbars are not load-bearing, that conductors are protected against shorting by dropped conductive objects of at least 6 mm length, that a grounding interface is provided, that electrostatic generation in dielectric fluids is managed and that no aerosol is dispersed. For spills, containment must hold at least 100% of the volume of any single system, open baths need a well-ventilated room, fluid must be kept out of sewers and at least one person must be present during service. Two-phase and volatile systems must contain vapour losses by enclosure and condensation.
The fluids chapter tabulates minimum dielectric limits: lifetime dielectric strength of at least 6 kV/mm at 1 mm, volume resistivity of at least 2.00 GOhm-m unused and 0.20 GOhm-m lifetime, Cleveland closed-cup flash point of at least 150 C, auto-ignition of at least 300 C, sulphur below 10 ppm and acidity of at most 0.01 mg KOH/g for hydrocarbons. Mineral oils are to be avoided in favour of synthetic oils and esters. Suppliers report data-sheet properties such as density, specific heat, thermal conductivity, viscosity and vapour pressure across 20-70 C.
The specification-sheet chapter standardises units and metrics so solutions can be compared: density at ASHRAE facility-water classes W17, W27, W32, W45 and W55, footprint at W32, full-solution static floor load in kN/m2, ceiling clearance, non-IT power per kW of IT and a thermal-loss test. The facility-interface chapter covers flow-direction marking, partial vacuum down to 50 kPa, glycol mixtures up to 50%, a corrosion strategy for galvanic potential differences above 0.15 V and Redfish-based management with Modbus, SNMP or BACnet output for legacy systems.
Three feature classes are defined: thermal optimised, high safety and high availability. High availability allows N+1 to be supplemented with ride-through giving at least 30 minutes of operation without cooling. The ride-through chapter defines dielectric, partial dielectric and facility-water buffering but leaves quantification open. This is a requirements catalogue rather than a design guide and is meant to be read alongside the ACS immersion design guidelines.
Key points
- Requirements are tagged SR (vendor), CR (customer/operator) and OR (optional); the qualification panel quorum is at least 5 votes.
- Rev 2.10 raised the minimum auto-ignition point from 250 C to 300 C and restated dielectric strength in kV/mm.
- Busbar conductors in tanks must be protected so a dropped conductive object of at least 6 mm length cannot short them; horizontal busbars must not be load-bearing.
- Containment must hold at least 100% of the fluid volume of any single system without breach.
- Minimum fluid limits: dielectric strength at least 6 kV/mm at 1 mm, volume resistivity at least 2.00 GOhm-m unused and 0.20 GOhm-m lifetime, flash point at least 150 C, auto-ignition at least 300 C, sulphur below 10 ppm.
- Acidity limits are 0.01 (hydrocarbons), 0.06 (natural esters), 0.03 (synthetic esters) and 0.001 (fluorocarbons) mg KOH/g; mineral oils are to be avoided.
- Specification sheets report density at W17/W27/W32/W45/W55 facility-water classes; the W32 solution footprint is mandatory.
- Public data sheets must include full-solution static floor load (kN/m2), ceiling height clearance and non-IT power per kW of IT.
- The facility-water interface must tolerate partial vacuum down to 50 kPa and glycol mixtures up to 50%, and needs a galvanic corrosion strategy above 0.15 V difference.
- High-availability systems may supplement N+1 with ride-through of at least 30 minutes without cooling; ride-through is not yet quantified in the document.
Using it in design
- Compare vendor offers on the same template: request W32 footprint density (kW/m2), full-solution static floor load, ceiling clearance and non-IT power per kW of IT in writing.
- Check the fluid data sheet against the minimum table (6 kV/mm, 150 C flash, 300 C ignition, sulphur below 10 ppm) and obtain the supplier's monitoring tests and intervals for the lifetime limits.
- Size room containment to at least 100% of the largest connected container; for open baths write ventilation, absorbent, no-sewer and disposal procedures into operating documents.
- At the facility-water connection, check vacuum rating, glycol fraction, galvanic compatibility and flow-direction marking, noting that quick disconnects are not recommended.
- Specify in the technical requirements a Redfish-compliant management system with liquid temperature at two or more locations, two warning levels and Modbus, SNMP or BACnet output for the BMS.
- If high availability is targeted, have the vendor demonstrate any 30-minute no-cooling ride-through claim with measured data.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Immersion solution vendors, facility mechanical designers and operators who qualify or select immersion cooling.
Document contents
- Table of amendments
- Introduction
- Technology definitions (single- and two-phase, enclosed chassis, open bath, hybrid)
- Quality and safety requirements
- Immersion Fluids
- Minimum dielectric fluid requirements
- Dielectric fluid quality management guidelines
- Feature classifications (minimum management, thermal optimized, high safety, high availability)
- General standards and solution specification items
- Required available documentation
- Datacenter interface requirements (FWS compatibility, water quality, galvanic properties)
- DCIM interfaces and Redfish definitions
- Immersion related uptime factors (ride through, thermal design)
- Requirements catalogue
- Glossary
- References
Read the document
ocp-immersion-requirements-rev2-1.pdf
CC BY-SA 4.0 — share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Rolf Brink; Jessica Gullbrand; John Bean; Nigel Gore; Rick Payne; Jimil Shah; Rick Margerison
- Publisher
- Open Compute Project Foundation
- Year
- 2023
- Document language
- English
- Source type
- Industry body
- Access
- Open licence — downloadable
- Licence
- CC BY-SA 4.0 — share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
License section of the document states Creative Commons Attribution-ShareAlike 4.0. Attribution required; derivatives/adaptations must stay CC-BY-SA.
Citation
Rolf Brink; Jessica Gullbrand; John Bean; Nigel Gore; Rick Payne; Jimil Shah; Rick Margerison (2023). Immersion Requirements Rev 2.0, First Amended (Revision 2.10, August 18, 2023). Open Compute Project Foundation. https://www.opencompute.org/documents/ocp-acs-immersion-requirements-rev-2-1-pdf
Events on this subject
- NVIDIA GTC
- ISK-SODEX Istanbul 2027
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.