Technical guideFree to read2025

High-Performance Two-Phase Cooling under Different Cold Plate Orientations (OCP EMEA Summit 2025, Future Technologies Symposium)

Open Compute Project Foundation · Richard Bonner, Qingyang Wang

A short technical talk on pumped two-phase direct-to-chip cooling for very dense AI racks, including a 250 kW rack test and cold plate orientation comparisons.

On this page

Overview

This short technical talk covers pumped two-phase direct-to-chip cooling for very dense AI racks. The motivation is next-generation racks near 600 kW that rotate servers vertically; vendor roadmaps point to such racks around 2027. The source is a conference talk and does not include a thorough method or uncertainty analysis.

The talk reports a 250 kW rack test using a two-phase CDU with 40 C facility water. Two-phase CDU products released in April 2025 cool 250 kW of H100 servers using 40 C facility water. In cold-plate tests with R515B refrigerant at 40 C saturation, 4,500 W was removed from a GPU thermal test vehicle before wall-power limits were reached.

Two-phase cold plates are near-isothermal, so the maximum and average case temperatures coincide. In comparisons of the same cold plate in horizontal and vertical orientations, vertical slightly outperformed at high power and horizontal-up slightly at low power; all orientations performed acceptably.

The results show only small orientation effects. The limit of the document is that the talk reflects one vendor's tests and depends on a particular refrigerant and test setup, so the results should not be generalised directly to other systems. For designers its value is in showing that 40 C facility water can be a valid design point for two-phase CDUs.

Key points

  1. Two-phase CDU products released in April 2025 cool 250 kW of H100 servers using 40 C facility water.
  2. A cold-plate test with R515B at 40 C saturation removed 4,500 W from a GPU thermal test vehicle before wall-power limits were reached.
  3. Two-phase cold plates are near-isothermal, so maximum and average case temperature coincide.
  4. Vertical orientation slightly outperformed at high power and horizontal-up slightly at low power; all orientations performed acceptably.
  5. Vendor roadmaps point to about 600 kW racks with vertically mounted servers around 2027.
  6. Results show only small orientation effects.

Using it in design

  • In CDU catalogue entries, distinguish single-phase and two-phase (refrigerant type, saturation temperature, facility-water supply temperature).
  • Allow 40 C facility water as a valid design point for two-phase CDUs.
  • Record cold plate orientation as a design parameter for high-density racks with vertical server layouts.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling designers evaluating two-phase direct-to-chip cooling for very high-density AI racks.

Publication details

Authors
Richard Bonner; Qingyang Wang
Publisher
Open Compute Project Foundation
Year
2025
Document number
OCP EMEA Summit 2025, FTS Data Center Sustainability
Event
OCP EMEA Summit 2025, Dublin
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Richard Bonner; Qingyang Wang (2025). High-Performance Two-Phase Cooling under Different Cold Plate Orientations (OCP EMEA Summit 2025, Future Technologies Symposium). Open Compute Project Foundation. OCP EMEA Summit 2025, FTS Data Center Sustainability. OCP EMEA Summit 2025, Dublin. https://drive.google.com/file/d/1otzItuoXWWb7eiajvzj4WCNkmuujt20i/view

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.