The paper explains how Rittal's standardised, modular RiMatrix S data centre pairs server modules (Single 6/9, Double 6/9) with cooling modules that blow cold air directly in front of the racks. A worked 60 kW example converts the PUE improvement into kWh and CO2.

On this page

Overview

Cooling modules come in 70 kW (Single 6 server module) and 100 kW (Single 9) classes. The air temperature difference over rack height is only about 1 K from U1 to U42. The paper also notes that battery service life benefits from about 20 C storage temperature.

Free cooling uses a dry cooler, and its share depends on water temperatures and climate. In the example climate, ambient exceeds 22 C for only 343 h, so free cooling is usable 96.1 % of the year. Differential-pressure (cross-section) control with closed-loop fans keeps cold-aisle overpressure at only 1-2 Pa, supplying just the air the servers draw.

Server fan energy rises sharply above about 27 C inlet when fans go to 100 % speed, which ties the inlet setpoint to fan power. For a 60 kW centre at 30 kW average load, PUE falls from 1.3 to 1.1 with optimised control, saving 50,510 kWh and 29,801 kg CO2 per year. It is a manufacturer paper and the calculation rests on a single example climate and load profile.

Key points

  1. Cooling modules come in 70 kW (Single 6) and 100 kW (Single 9) classes.
  2. Air temperature difference from U1 to U42 is only about 1 K.
  3. Delta-P control keeps cold-aisle overpressure at only 1-2 Pa.
  4. In the example climate ambient exceeds 22 C for only 343 h, so free cooling is usable 96.1 % of the year.
  5. Server fan energy rises sharply above about 27 C inlet as fans reach 100 % speed.
  6. 60 kW centre at 30 kW average load: PUE 1.3 to 1.1 saves 50,510 kWh and 29,801 kg CO2 per year.
  7. Battery life benefits from about 20 C storage temperature.

Using it in design

  • In the free-cooling estimator compute economiser hours from hourly climate data against the required water supply temperature and report the percentage of the year.
  • Show the relationship between inlet setpoint and server fan power and warn above 27 C.
  • Support delta-P based fan control as an option with a 1-2 Pa target.
  • In the prefab module catalogue tie cooling module capacity to server module type.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Designers evaluating modular data-centre cooling and free-cooling hours.

Related standards

  • ASHRAE TC 9.9
  • The Green Grid PUE

Publication details

Authors
Rittal
Publisher
Rittal
Year
2015
Document number
5_4358
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Rittal (2015). Whitepaper - The Cooling Technology of the RiMatrix S Data Centre. Rittal. 5_4358. https://www.rittal.com/imf/none/5_4358/Rittal_Whitepaper_The_Cooling_Technology_of_the_RiMatrix__5_4358/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.