Whitepaper - The Cooling Technology of the RiMatrix S Data Centre
Rittal
The paper explains how Rittal's standardised, modular RiMatrix S data centre pairs server modules (Single 6/9, Double 6/9) with cooling modules that blow cold air directly in front of the racks. A worked 60 kW example converts the PUE improvement into kWh and CO2.
On this page
Overview
Cooling modules come in 70 kW (Single 6 server module) and 100 kW (Single 9) classes. The air temperature difference over rack height is only about 1 K from U1 to U42. The paper also notes that battery service life benefits from about 20 C storage temperature.
Free cooling uses a dry cooler, and its share depends on water temperatures and climate. In the example climate, ambient exceeds 22 C for only 343 h, so free cooling is usable 96.1 % of the year. Differential-pressure (cross-section) control with closed-loop fans keeps cold-aisle overpressure at only 1-2 Pa, supplying just the air the servers draw.
Server fan energy rises sharply above about 27 C inlet when fans go to 100 % speed, which ties the inlet setpoint to fan power. For a 60 kW centre at 30 kW average load, PUE falls from 1.3 to 1.1 with optimised control, saving 50,510 kWh and 29,801 kg CO2 per year. It is a manufacturer paper and the calculation rests on a single example climate and load profile.
Key points
- Cooling modules come in 70 kW (Single 6) and 100 kW (Single 9) classes.
- Air temperature difference from U1 to U42 is only about 1 K.
- Delta-P control keeps cold-aisle overpressure at only 1-2 Pa.
- In the example climate ambient exceeds 22 C for only 343 h, so free cooling is usable 96.1 % of the year.
- Server fan energy rises sharply above about 27 C inlet as fans reach 100 % speed.
- 60 kW centre at 30 kW average load: PUE 1.3 to 1.1 saves 50,510 kWh and 29,801 kg CO2 per year.
- Battery life benefits from about 20 C storage temperature.
Using it in design
- In the free-cooling estimator compute economiser hours from hourly climate data against the required water supply temperature and report the percentage of the year.
- Show the relationship between inlet setpoint and server fan power and warn above 27 C.
- Support delta-P based fan control as an option with a 1-2 Pa target.
- In the prefab module catalogue tie cooling module capacity to server module type.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers evaluating modular data-centre cooling and free-cooling hours.
Related standards
- ASHRAE TC 9.9
- The Green Grid PUE
Publication details
- Authors
- Rittal
- Publisher
- Rittal
- Year
- 2015
- Document number
- 5_4358
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Rittal (2015). Whitepaper - The Cooling Technology of the RiMatrix S Data Centre. Rittal. 5_4358. https://www.rittal.com/imf/none/5_4358/Rittal_Whitepaper_The_Cooling_Technology_of_the_RiMatrix__5_4358/
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.