Schneider Electric 2011
Mitigating Fire Risks in Mission Critical Facilities
Default to aspirating detection for rooms above 15 ACH and spot photoelectric otherwise; compute detector count as floor area divided by the area per detector for the ACH band.
- Industry default in high-airflow rooms is one spot detector per 250 ft2 (23 m2).