Two-Stage Power Delivery Architecture Using Hybrid Converters for Data Centers and Telecommunication Systems
Electronics (MDPI AG) · Ratul Das, Hanh-Phuc Le
A hardware study that proposes cutting the usual four conversion stages between UPS output and processor to two: a switched-capacitor step-down PFC rectifier and a GaN multi-phase hybrid point-of-load converter.
CC BY 4.0 — share with attribution
On this page
Overview
The study asks whether the power chain from AC distribution voltage to processor core voltage can be done in two stages instead of four. The conventional chain after an online UPS has four stages: PFC rectifier to a high-voltage DC link, DC link to a nominal 48 V bus, 48 V to 12 V, and 12 V to 0.8-3.3 V core voltages. The proposed architecture replaces it with a switched-capacitor (SC) step-down PFC rectifier producing a 48-60 V bus and a GaN multi-phase hybrid point-of-load converter producing about 1 V.
Prototypes of both stages were built and tested separately and together. The first-stage SC PFC rectifier (90-110 VAC to 48-60 VDC) reached 96.1% peak efficiency at 0-4.5 A output, with 73 W/in³ peak power density. The second-stage hybrid PoL converter reached 90.7% peak efficiency over 0-220 A at 1 V, with 2020 W/in³ peak power density. For the multi-phase multi-inductor hybrid (MP-MIH) converter a new phase sequence giving a wider output voltage range was proposed and verified experimentally.
End to end, direct conversion from about 110 VAC to 1 VDC peaked at 84.1% efficiency at 50 A and fell to 73.5% at 160 A. This shows the two-stage structure works as a concept, but efficiency may lag production-grade multi-stage chains.
Limits: it is a converter-level hardware paper, efficiency falls at high current and the input is a low 90-110 VAC range; facility-scale use, thermal management and reliability are not assessed. Its relevance to facility design is the efficiency of the 48 V rack-to-chip chain and the argument for fewer stages.
Key points
- The conventional rack chain after an online UPS has four stages: PFC rectifier to a high-voltage DC link, DC link to a nominal 48 V bus, 48 V to 12 V, and 12 V to 0.8-3.3 V core voltages.
- The first-stage SC PFC rectifier (90-110 VAC to 48-60 VDC) reached 96.1% peak efficiency at 0-4.5 A output, with 73 W/in³ peak power density.
- The second-stage hybrid PoL converter reached 90.7% peak efficiency over 0-220 A at 1 V, with 2020 W/in³ peak power density.
- End to end, direct conversion from about 110 VAC to 1 VDC peaked at 84.1% efficiency at 50 A and fell to 73.5% at 160 A.
- A new phase sequence for an extended output voltage range was proposed and verified experimentally.
Using it in design
- In rack power-chain efficiency calculations, treat the number of stages and each stage's efficiency as separate inputs, and show the benefit of fewer stages at load points (low and high current).
- Account for the efficiency fall at high current (73.5% at 160 A) in rack heat-load calculations; do not use peak efficiency as typical operating efficiency.
- Label such two-stage architectures as prototype-maturity options and do not compare them with production-grade solutions as if at the same maturity.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Power-electronics engineers evaluating the number of stages and efficiency in in-rack power conversion and the 48 V chain.
Document contents
- 1. Introduction
- 2. Step-Down PFC Converter (2.1 Topology and Operation, 2.2 Modified Operation for Capacitor Balancing, 2.5 Control and Sensing Circuits)
- 3. Multi-Phase, Multi-Inductor Hybrid Converter
- 4. Experimental Results (4.1 Step-Down PFC Converter, 4.2 MP-MIH Converter, 4.3 Full System Verification)
- 5. Conclusions
Read the document
two-stage-48v-hybrid-converter-pdn-2025.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Ratul Das; Hanh-Phuc Le
- Publisher
- Electronics (MDPI AG)
- Year
- 2025
- Volume
- 14
- Issue
- 16
- Pages
- 3169
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
Page 1 states the article is distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Ratul Das; Hanh-Phuc Le (2025). Two-Stage Power Delivery Architecture Using Hybrid Converters for Data Centers and Telecommunication Systems. Electronics (MDPI AG). 14(16), 3169. https://doi.org/10.3390/electronics14163169
Events on this subject
- Electricity Eurasia 2027
- ELECO 2026 Elektrik-Elektronik ve Biyomedikal Mühendisliği Konferansı
- The smarter E Europe (Intersolar Europe, ees Europe, Power2Drive, EM-Power)
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.