Research paperPDF2026

From Servers to Sites: Compositional Power Trace Generation of LLM Inference for Infrastructure Planning

arXiv preprint (Stanford University / Microsoft Azure Research) · Grant Wilkins, Fiodar Kazhamiaka et al.

A framework that generates LLM-inference power traces by separating workload-driven transitions among GPU operating states (prefill, decode, idle, mixed batches) from configuration-specific power distributions within each state, aggregated to rack, row and facility level.

CC BY 4.0 — share with attribution

On this page

Overview

Datacenter operators and electrical utilities rely on power traces at different spatiotemporal scales: operators use fine-grained traces for provisioning, facility management and scheduling, while utilities use site-level load profiles for capacity and interconnection planning. Existing datacentre power models do not capture LLM inference workloads, in which GPUs shift rapidly among compute-intensive prefill, lower-power decode and idle states. The paper shows LLM inference power can be represented compositionally through workload-driven transitions among operating states and configuration-specific power distributions within those states.

Prefill drives GPU power to 80-90% of TDP while memory-bound decode runs at 40-60% of TDP; under continuous batching both coexist in the same batch. Classifiers trained on measured vLLM server traces turn request-arrival streams into state trajectories and power traces, which are then aggregated to rack, row and facility level. The generated traces achieve median absolute energy error below 5% for most configurations, while a flat TDP assumption overestimates energy by more than 3.5×.

In the facility case study, TDP sizing gives 1.19 MW peak versus 0.75 MW from generated traces, so nameplate provisioning overstates required interconnection capacity by roughly 60%. Generated facility traces show a peak-to-average ratio of 1.19, a load factor of 0.84 and a maximum 15-minute ramp of 0.11 MW. With a 600 kW row limit, TDP provisioning allows 23 racks, whereas the trace-based P95 criterion allows 57 racks (observed peak about 580 kW), more than double the rack density. Oversubscription headroom depends on temporal decorrelation of rack peaks; more strongly synchronised arrivals would reduce the safe oversubscription limit.

Limits: the models are trained on measured vLLM server traces and need configuration-specific distributions; the case study rests on a single production Azure inference trace. It is a preprint.

Key points

  1. Prefill drives GPU power to 80-90% of TDP while memory-bound decode runs at 40-60% of TDP; under continuous batching both coexist in the same batch.
  2. The generated traces achieve median absolute energy error below 5% for most configurations, while a flat TDP assumption overestimates energy by more than 3.5×.
  3. For the facility case study, TDP sizing gives 1.19 MW peak versus 0.75 MW from generated traces, so nameplate provisioning overstates required interconnection capacity by roughly 60%.
  4. Generated facility traces show a peak-to-average ratio of 1.19, a load factor of 0.84 and a maximum 15-minute ramp of 0.11 MW.
  5. With a 600 kW row limit, TDP provisioning allows 23 racks, whereas the trace-based P95 criterion allows 57 racks (observed peak about 580 kW), more than double the rack density.
  6. Oversubscription headroom depends on temporal decorrelation of rack peaks; more strongly synchronised arrivals would reduce the safe limit.

Using it in design

  • For an AI inference facility, set interconnection capacity from traces generated from the workload, not nameplate TDP or mean power; TDP sizing gave 1.19 MW against 0.75 MW trace-based (about 60% too much).
  • Assess row limits (for example 600 kW) for rack density and oversubscription with a trace-based P95 criterion instead of TDP (57 racks instead of 23), and state the temporal-decorrelation assumption of rack peaks (synchronised arrivals lower the limit) as an explicit risk.
  • Take into account in the power model that prefill (80-90% of TDP) and decode (40-60%) states coexist in the same batch.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Designers and grid planners planning the electrical load, interconnection capacity and rack oversubscription of AI inference facilities.

Document contents

  1. 1 Introduction
  2. 2 Motivation and Observations (2.1 Power States in Continuous-Batch Inference)
  3. 3 Methods (3.1 Planner-Facing Interface, state-transition classifiers, within-state power distributions, rack, row and facility aggregation)
  4. 4 Evaluation and Case Studies (energy error, temporal autocorrelation, facility case study, row oversubscription)
  5. 7 Conclusion

Read the document

llm-inference-power-trace-generation-2026.pdf

PDF · 6.0 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Grant Wilkins; Fiodar Kazhamiaka; Ram Rajagopal
Publisher
arXiv preprint (Stanford University / Microsoft Azure Research)
Year
2026
Document number
arXiv:2603.18383
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
arxiv.org
Original licence note

arXiv record licence is http://creativecommons.org/licenses/by/4.0/ (checked via arXiv OAI-PMH)

Citation

Grant Wilkins; Fiodar Kazhamiaka; Ram Rajagopal (2026). From Servers to Sites: Compositional Power Trace Generation of LLM Inference for Infrastructure Planning. arXiv preprint (Stanford University / Microsoft Azure Research). arXiv:2603.18383. https://doi.org/10.48550/arXiv.2603.18383

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.