POLCA: Power Oversubscription in LLM Cloud Providers

arXiv preprint (Microsoft Azure) · Pratyush Patel, Esha Choukse et al.

A paper from Microsoft Azure characterising LLM training and inference power and proposing the POLCA framework to enable power oversubscription.

On this page

Overview

This 2023 arXiv preprint from Microsoft Azure by Pratyush Patel and colleagues characterises the power use of LLM training and inference on DGX A100 servers and in production clusters, and uses it to motivate power oversubscription. Inference clusters show a diurnal pattern but stay well below provisioned power, while training clusters produce large, synchronised swings.

The numbers show the difference: LLM inference clusters use only up to 80% of provisioned power, whereas training clusters offer a smaller headroom of about 10% because of massive coordinated power peaks. In production clusters, training incurs power swings of up to 37.5% of provisioned power capacity, whereas inference changes by only up to 9%. GPU power constitutes on average 60% of server-level power, and peak GPU power can exceed the server's GPU TDP by up to 500 W.

At training iteration boundaries GPU power drops to 75% of TDP (RoBERTa), 50% (GPT-NeoX) or 20% (Flan-T5, roughly idle); the authors stress that the swings, not the peak, are the main challenge. GPU frequency locking and power capping are evaluated as control knobs, noting that power caps are reactive and let prompt-phase spikes through, and that out-of-band controls via the BMC are slow. For Flan-T5 and GPT-NeoX training, frequency capping reduced peak server power by 22% while impacting performance by 10%.

The proposed POLCA framework uses phase-aware frequency and power thresholds with a power-brake backstop. Simulation on production-like traces allows 30% more inference servers in the same power budget with minimal performance loss, maintaining SLOs. As a limitation, the results are specific to Azure's workloads and hardware, and the paper is a preprint.

Key points

  1. LLM inference clusters use only up to 80% of provisioned power; training clusters offer about 10% headroom because of coordinated peaks.
  2. In production clusters training incurs power swings of up to 37.5% of provisioned power capacity; inference changes by only up to 9%.
  3. GPU power is on average 60% of server power, and peak GPU power can exceed the server's GPU TDP by up to 500 W.
  4. At training iteration boundaries GPU power drops to 75% of TDP (RoBERTa), 50% (GPT-NeoX) or 20% (Flan-T5); the swings are the main challenge.
  5. For Flan-T5 and GPT-NeoX training, frequency capping reduced peak server power by 22% while impacting performance by 10%.
  6. Power caps are reactive and let prompt-phase spikes through; out-of-band controls via the BMC are slow.
  7. POLCA allows 30% more servers in the same inference GPU cluster while maintaining SLOs.

Using it in design

  • In the power planner, apply different diversity and oversubscription factors by workload: inference rows can be provisioned below sum-of-nameplate (for example peak about 80% of provisioned), while training rows should assume near-coincident peaks with only about 10% headroom.
  • Expose a 'power oversubscription' option that requires a capping or brake mechanism and telemetry, and report the extra servers deployable.
  • Account for GPU peaks above TDP when sizing PSUs and rack PDUs, and flag mixed training and inference rows as a risk.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers, capacity planners and operators setting power allocation and oversubscription strategy for AI clusters.

Publication details

Authors
Pratyush Patel; Esha Choukse; Chaojie Zhang; Íñigo Goiri; Brijesh Warrier; Nithish Mahalingam; Ricardo Bianchini
Publisher
arXiv preprint (Microsoft Azure)
Year
2023
Document number
arXiv:2308.12908
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY-NC-ND 4.0 — share unaltered with attribution for noncommercial purposes
Original licence note

arXiv CC BY-NC-ND 4.0 - citation only

Citation

Pratyush Patel; Esha Choukse; Chaojie Zhang; Íñigo Goiri; Brijesh Warrier; Nithish Mahalingam; Ricardo Bianchini (2023). POLCA: Power Oversubscription in LLM Cloud Providers. arXiv preprint (Microsoft Azure). arXiv:2308.12908. https://doi.org/10.48550/arXiv.2308.12908

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.