ABB's reference paper on discrimination between low-voltage protective devices, a practical basis for coordination checks in a data-centre one-line diagram.
On this page
Overview
The paper defines total and partial selectivity per IEC 60947. Total selectivity between a pair of breakers means selectivity up to the lower of the two Icu values; partial selectivity means only up to an ultimate selectivity current Is below that, beyond which the upstream device may also trip. The overload zone runs from In up to about 8-10 x In (thermal / L function) and the short-circuit zone lies above it (magnetic or S, D, I functions). Current through the upstream breaker can exceed the downstream fault current: IA = IB + Iloads for one upstream feeder, IA = (IB + Iloads)/n for n paralleled supplies.
The techniques covered are current, time, energy, time-current and zone (logic-interlock) selectivity. With time selectivity the ultimate limit equals the upstream instantaneous threshold I3 (minus tolerance) or, for an ACB with I3 set OFF, its short-time withstand Icw. For MCCB-MCCB time selectivity, when the upstream S threshold sits above a downstream instantaneous function, set t2A >= 150 ms for I2t=const or >= 100 ms for t=const; for S-over-S with the same curve type, t2A - tolerance >= t2B + tolerance + 50 ms.
Zone selectivity uses lock signals between trip units so only the breaker immediately upstream of the fault trips without long intentional delays; trip times can be below 100 ms but an auxiliary supply is required. Between Emax ACBs (PR122/PR123) it reaches Is = Icw, and between Tmax T4L/T5L/T6L with PR223EF it reaches Is = 100 kA. Directional time and directional zone selectivity for multi-source boards, MV/LV selectivity, residual-current selectivity and a worked LV/LV study are given in appendices.
For MV/LV selectivity the MV relay curve must stay above the transformer inrush curve and below its thermal-withstand point, within the utility's imposed current/time limits. The paper is written around ABB product families, so its settings and thresholds do not transfer directly to other manufacturers.
Key points
- Total selectivity means selectivity up to the lower Icu of the pair; partial means only up to Is, beyond which the upstream device may also trip.
- The overload zone runs from In to about 8-10 x In; the short-circuit zone is above that.
- Upstream current: IA = IB + Iloads for one feeder; (IB + Iloads)/n for n paralleled supplies.
- With time selectivity the ultimate limit is I3 (minus tolerance) or Icw for an ACB with I3 OFF.
- MCCB-MCCB time selectivity: t2A >= 150 ms (I2t=const) or >= 100 ms (t=const); S-over-S: t2A - tol >= t2B + tol + 50 ms.
- Zone selectivity: trip times below 100 ms, auxiliary supply required; Emax ACBs reach Is = Icw, Tmax T4L/T5L/T6L with PR223EF reach 100 kA.
- For MV/LV the MV relay curve must stay above transformer inrush and below its thermal withstand.
Using it in design
- Record Icu, Icw, I1/I2/I3 settings and the t2 curve type for each protective device when assessing selectivity pairs.
- Flag partial selectivity where the prospective Ik at the downstream device exceeds the tabulated Is, and distinguish 'total' from 'partial up to X kA' in reports.
- Include parallel load current and number of paralleled sources when computing upstream current for selectivity.
- Plan auxiliary power and wiring for zone selectivity on main and feeder ACBs; plot transformer inrush and thermal withstand on MV/LV time-current curves.
Who should read it
Electrical designers doing protection coordination and selectivity studies in low-voltage distribution.
Related standards
- IEC 60947-1
- IEC 60947-2
- IEC 60364-5-53
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2008
- Document number
- 1SDC007100G0204 (QT1)
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
ABB (2008). Technical Application Papers No.1: Low voltage selectivity with ABB circuit-breakers. ABB. 1SDC007100G0204 (QT1). https://library.e.abb.com/public/65ddf36f7c3bd0fec1257ac500377a37/1SDC007100G0204.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.