Technical Application Papers No.14: Faults in LVDC microgrids with front-end converters
ABB
A 2021 ABB paper that analyses short circuits and ground faults on the DC and AC sides of an IGBT front-end converter (FEC) feeding a low-voltage DC microgrid, for different grounding schemes, by simulation, and covers DC protective device selection.
On this page
Overview
The paper explains that, with distributed generation and storage spreading, DC microgrids are an alternative to AC systems with advantages in applications such as data centres and marine installations. Against conventional wisdom, it argues that converters do not limit current in every condition, depending on converter type, connection and grounding scheme. Chapter 1 lists DC distribution advantages: sensitive electronic loads, distributed generation, cables and transmissible power, DC in data centres, the hazard of DC versus AC and the elimination of synchronisation.
The data-centre section notes that conventional AC distribution has five to seven conversion steps, each adding losses, heat and a reliability penalty. 380 VDC distribution is said to save about 28 percent energy against a typical AC system and about 7 percent against best-in-class AC, with about 33 percent less space. For the same line, DC can carry about 2.2-3.9 times the power of AC depending on configuration (assuming 400 V AC, 400 V and 800 V DC, cables loaded to thermal limit, power factor 0.9).
The fault analysis covers four cases: short circuit and ground fault on the DC side of the FEC, and short circuit and ground fault on the AC side. For high-resistance DC faults the FEC control holds Vdc and limits fault current near converter rating. For low-impedance faults the DC capacitors discharge into the fault and, once the IGBTs block, the freewheeling diodes conduct as an uncontrolled rectifier, so the converter cannot limit current. The analysis first neglects IGBT self-protection (DESAT), so that architectures relying on external protective devices are examined.
Chapter 4 presents ABB's DC protection offer (air circuit breakers, moulded-case breakers, miniature breakers, fuse-disconnectors, fuse-holders, GE Rapid). The annexes describe power-electronic switches, switch-mode three-phase converters and the DC fault contribution of other converter types (DC/AC interface for loads, AC/DC interface for gensets or wind). It is a manufacturer reference paper, and the product section addresses ABB ranges.
Key points
- A typical AC data-centre chain has five to seven conversion steps.
- 380 VDC distribution saves about 28 percent energy against a typical AC system and about 7 percent against best-in-class AC; about 33 percent less space.
- On the same line DC can carry about 2.2-3.9 times the power of AC depending on configuration; 1.28 times in the first comparison for 3-wire or 2-wire DC.
- Online UPS losses in conventional AC schemes are given as roughly 5-10 percent.
- For high-resistance DC faults the FEC control holds Vdc and limits current near converter rating.
- For low-impedance faults the DC capacitors discharge into the fault; once IGBTs block, freewheeling diodes conduct as an uncontrolled rectifier.
- It cannot be assumed that converters always limit fault current; behaviour depends on type, connection and grounding scheme.
- On an AC-side short circuit the IGBT converter can limit current.
- A ground fault in the LVDC microgrid is seen by each converter as a short circuit at its DC terminals (without a separation transformer).
Using it in design
- In DC microgrid design, do not base fault current on converter rating alone; compute capacitor discharge and diode rectification contributions separately.
- Choose the grounding scheme by fault type and verify tripping on ground faults by simulation.
- Select external DC protective devices (breakers, fuses) without relying on the FEC's DESAT protection, and check DC breaking capacity.
- When evaluating 380 VDC, weigh energy saving, space and reliability gains against protection cost.
- Account separately for the DC fault contribution of ESS, PV and generator interface converters.
Who should read it
Electrical engineers designing DC distribution, data-centre power architecture and energy storage protection.
Document contents
- Introduction
- 1. Advantages of Low Voltage DC distribution systems
- 2. System configuration
- 3. Fault analysis
- 4. DC fault protection: the ABB offer
- Annex A: Description of the main power-electronic switches
- Annex B: Switch-mode three-phase converters
- Annex C: DC fault contribution of other types of converters
Related standards
- IEC 60947-2
- IEC 60364-1
- IEC 61660-1
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2021
- Document number
- 1SDC007113G0201
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
ABB technical application paper, free download from ABB library; copyright ABB, no open licence.
Citation
ABB (2021). Technical Application Papers No.14: Faults in LVDC microgrids with front-end converters. ABB. 1SDC007113G0201. https://library.e.abb.com/public/d772a7b5e0d0428fbc66ea24fe04be65/1SDC007113G0201_QT14%202021_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
