Technical Application Papers No.6: Arc-proof low voltage switchgear and controlgear assemblies
ABB
ABB's Technical Application Paper No. 6 explains the physics of internal arcing faults in low-voltage switchboards, their effects on people and the three approaches to arc-proof design: arc temperature is about 7000 to 8000 °C, a person 60 cm from a 20 kA arc can be subject to a force of 225 kg, and the IEC 61641 test is judged against seven acceptance criteria.
On this page
Overview
The first chapter gathers the basic concepts for low-voltage assemblies: standards and their applicability, electrical characteristics, types of assembly (primary distribution switchgear, secondary distribution switchgear, motor control centres, control and measurement boards, construction site assemblies), IP and IK degrees of protection, forms of internal separation and temperature rise inside the assembly. Forms 1 to 4, with a and b variants, define how far busbars, functional units and terminals are separated. Internal arc testing, seismic qualification and shock-proof execution are noted as special executions.
The second chapter deals with the electric arc. Inside an assembly an arc produces a pressure wave, a rapid temperature rise, ejection of molten metal and hot gas, and intense radiation. Effects on people fall under four headings: burns, injuries from ejected material, hearing damage and inhalation of toxic gases. The paper puts numbers on the hazard: arc temperature of about 7000 to 8000 °C, sound levels up to 160 dB, and a force of 225 kg at 60 cm from a 20 kA arcing fault. In a bolted short circuit the stresses are mainly electrodynamic, whereas in an arc fault they are thermal.
The third chapter compares three design philosophies for arc-proof assemblies. Passive protection means a reinforced mechanical structure that withstands the pressure plus a preferential discharge path for the hot gases; instruments on doors must withstand about 1 bar of overpressure. Active protection detects the arc with light sensors (often paired with a current sensor to avoid unwanted trips) or with overpressure sensors and opens the incoming breaker; light detectors signal within a few milliseconds, pressure sensors with a delay of 10 to 15 ms. The third approach reduces arc energy with current-limiting circuit-breakers.
The fourth chapter presents the ABB SACE PC3.0/MNS R switchgear as an example, offered with internal arc withstand up to 100 kA for 0.3 s and forms of separation 3a, 3b and 4b. Annex A documents an internal arc test under IEC 61641 with its recordings: a 65 kA test current was applied for 0.3 s at 462 V (440 V + 5%), and for an arc on the load side of a current-limiting breaker the current lasted only 7.7 ms. IEC 61641 is a technical report and not a standard, applied by agreement between manufacturer and user. The paper dates from 2008 and cites the standard editions of that time.
Key points
- Arc data: temperature about 7000 to 8000 °C; a force of 225 kg at 60 cm from a 20 kA arcing fault; sound up to 160 dB (a shotgun blast is 130 dB).
- Stress in a bolted short circuit is electrodynamic; in an arc fault it is thermal.
- Three design approaches: assemblies that mechanically withstand the arc (passive), assemblies with devices limiting arc effects (active), and assemblies with current-limiting circuit-breakers.
- Arc monitoring with light detectors issues a trip signal within a few milliseconds without waiting for an overcurrent relay delayed for selectivity; pressure sensors signal with a 10 to 15 ms delay.
- In a passively protected assembly, instruments on doors must withstand about 1 bar of overpressure without being ejected.
- The seven IEC 61641 criteria: doors stay closed, hazardous parts do not fly off, no holes form in accessible external parts, vertical indicators do not ignite, equipotential bonding stays effective, the arc stays within a defined area, and the sound part can be made safe for further use.
- Cotton cloth indicators are placed up to 2 m high and 30 cm from the assembly; the seventh criterion is checked by a dielectric test at 1.5 times rated voltage for 1 minute.
- Example test: 65 kA at 462 V for 0.3 s; with the arc on the load side of a current-limiting breaker the duration was 7.7 ms.
- In form 4b the terminals are in a compartment separate from the functional unit.
Using it in design
- Specify the internal arc classification of main distribution boards with test current and duration (65 kA for 0.3 s, for example) and ask for the IEC 61641 test report.
- Where protection settings are delayed for selectivity, consider an arc monitoring system with light detectors to shorten arc duration.
- For passively protected assemblies, mark the gas discharge direction on the electrical room layout and arrange ceiling clearance, cable trays and operator routes around it.
- Choose the form of separation (3b or 4b) from the need for live maintenance; it helps confine an arc to one compartment and keep neighbouring circuits in service.
- Use the arc data (temperature, pressure, sound) to justify personal protective equipment selection and permit-to-work procedures.
Who should read it
Electrical engineers specifying low-voltage switchboards, safety specialists, and electrical room operations teams.
Document contents
- 1 Generalities about LV switchgear and controlgear assemblies
- 1.5 Degree of protection IP
- 1.6 Degree of protection IK
- 1.7 Forms of separation
- 1.8 Temperature-rise inside assemblies
- 1.9 Switchgear and controlgear assemblies - special executions
- 2 The electric arc
- 2.2 Effects of the electric arc inside switchgear and controlgear assemblies
- 2.3 Effects of the electric arc on human beings
- 3 Internal arc-proof switchgear and controlgear assemblies
- 3.2.1 Assemblies mechanically capable of withstanding the electric arc (passive protection)
- 3.2.2 Assemblies equipped with devices limiting internal arc effects (active protection)
- 3.2.3 Switchgear and controlgear assemblies with current limiting circuit-breakers
- 4 ABB SACE arc-proof switchgear
- Annex A: Test on an arc-proof switchboard
Related standards
- IEC 61439-1
- IEC 61439-2
- IEC TR 61641
- IEC 60529
- IEC 62262
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2008
- Document number
- 1SDC007105G0201
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
ABB technical application paper, free download; copyright ABB, no open licence.
Citation
ABB (2008). Technical Application Papers No.6: Arc-proof low voltage switchgear and controlgear assemblies. ABB. 1SDC007105G0201. https://library.e.abb.com/public/ec3c2b32777546e690186c6c77059625/1SDC007105G0201.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
